| 2008-08-18 11:27:59 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 2, FLOOR PLAN: THE CLEAR FLOOR SPACE FOR THE |
| | S-1 SINK IN THE LOUNGE IS BEING INDICATED WRONG. PER |
| | FBC-2004 CHAPTER 11, SECTION 11-4.24.5 CLEAR FLOOR |
| | SPACE SHALL BE 30" X 48" AND CLEAR FLOOR SPACE SHALL |
| | EXTEND A MAXIMUM OF 19" UNDERNEATH SINK. PLEASE PROVIDE |
| | AN ELEVATION DETAIL WITH THE OTHER FOLLOWING |
| | REQUIREMENTS FOR THE ACCESSIBLE SINK PER FBC- 2004 |
| | CHAPTER 11 SECTIONS. |
| | |
| | 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| | COUNTER. |
| | |
| | 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE, |
| | AND 19" DEEP. |
| | |
| | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| | |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. SINK CABINETS SHALL BE OPEN FRONT FOR SINK, |
| | PLEASE REFERENCE COMMENT #1.. |
| | |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | |
| | 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. |
| | |
| | 2. SHEET 3, SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY |
| | INDICATE THE SIZE OF THE FIXTURE DRAINS AND TRAPS FOR |
| | THE PROPOSED EWC DRINKING FOUNTAIN AND S-1 SINK. PLEASE |
| | KNOW THAT THE RELOCATED S-1 SINK FIXTURE DRAIN SHALL BE |
| | 2 INCH (2") WITH AN 1-1/2 INCH (1-1/2") TRAP. PER |
| | FBC-2004 PLUMBING TABLE 906.1 MAXIMUM DISTANCE OF |
| | FIXTURE TRAPS FROM VENT. PER (W.P.B. AS AMENDED) |
| | SECTION 106.3.5.1.3 PLUMBING (4)(13). |
| | |
| | 3. NOTE: A POTABLE WATER ISOMETRIC RISER DIAGRAM IS |
| | REQUIRED FOR THE PROPOSED EWC DRINKING FOUNTAIN AND S-1 |
| | SINK. CLEARLY INDICATE THE PIPE SIZE PER FBC-2004 |
| | PLUMBING SECTION 601.1 SCOPE, A WATER HAMMER ARRESTOR |
| | FOR THE REF. ICE MAKER PER FBC-2004 PLUMBING SECTION |
| | 604.9 WATER HAMMER, AND CLEARLY INDICATE THAT THERE IS |
| | AN EXISTING BACKFLOW PREVENTER PER FBC-2004 PLUMBING |
| | SECTION 608 PROTECTION OF POTABLE WATER SUPPLY. PER |
| | (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING |
| | (3)(13). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |