Plan Review Details - Permit 08080113
Plan Review Stops For Permit 08080113
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-16 Cont ID  
Sent By mjacobs Date 2008-09-16 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2008-09-16 Time 10:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By mjacobs Date 2008-09-09 Time 11:49 Rev Time 0.00
Received By mjacobs Date 2008-09-09 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mjacobs Date 2008-08-22 Time 16:14 Rev Time 0.00
Received By mjacobs Date 2008-08-22 Time 14:22 Sent To  
Notes
2008-08-22 16:14:34 
 BUILDING PLAN REVIEW
 PERMIT: 08080113
 ADD: 1558 PBL BLVD SUITE #5
 CONT: HALLMARK & SONS INC.
 TEL: (561)644-3498
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-22-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A1, THE ACCESSIBLE SINK NEXT TO THE BATH ROOM
 NEEDS TO BE IN COMPLIANCE WITH SECTION 11-4.24. EVEN
 THOUGH SHEET A4 SHOWS SOME DETAILS, OTHER IMPORTANT
 ONES ARE MISSING FROM SHEET A1. SHOW THE CLEAR FLOOR
 SPACE WHICH SHALL BE AT LEAST 30 INCHES BY 48 INCHES.
 PLEASE NOTE: DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE FBC 11- 4.22.2 (NOTE
 BATH ROOM DOOR NEXT TO SINK).
  
 4) THE WALL LEGEND ON SHEET A1 SHOWS TWO TYPES OF WALL,
 HOWEVER, SHEET A4 SHOWS FOUR DIFFERENT TYPES OF WALLS
 WHICH ARE NOT CLEARLY INDICATED ON THE FLOOR PLANS.
 PLEASE IDENTIFY EACH WALL ON THE FLOOR PLANS WITH A
 NUMBER OR LETTER SO WE CAN KNOW WHICH WALL WILL BE
 CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1
  
 5) SUBMIT EXISTING AND PROPOSED FLOOR PLANS TO SHOW ALL
 WALLS TO BE DEMOED AND WHICH ONES ARE NEW. THE
 ADDITIONAL INFORMATION IS REQUIRED SO WE CAN HAVE AN
 UNDERSTANDING AS TO WHERE ALL THE CHANGES ARE MADE. FBC
 106.1.2*
  
 6) PROVIDE ELEVATION DRAWINGS TO SHOW FRAMED OPENING
 FOR THE GLASS WINDOWS ON SHEET A1. THE DRAWING SHALL
 ALSO SHOW HOW HIGH THE BOTTOM OF THE GLASS IS ABOVE THE
 FINISH FLOOR. ADDITIONAL INFORMATION REQUIRED FBC
 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-10-02 Cont ID  
Sent By dpalmer Date 2008-10-02 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2008-10-02 Time 12:38 Sent To FIRE
Notes
2008-10-02 12:40:18PLANS ROUTED TO FIRE FOR STAMPING OF E-1
2008-10-02 12:40:03REDLINED PLANS AS THE CALCULATIONS STILL INDICATE T-12
 FIXTURES AND FIXTURE LEGEND INDICATES T-8.
  
 CALLED ENGINEER'S OFFICE, HOWEVER WAS NOT AVAILABE AT
 REVIEW. SPOKE TO CONTRACTOR AND LET HIM KNOW PLANS WERE
 BEING REDLINED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-29 Cont ID  
Sent By dpalmer Date 2008-09-29 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2008-09-29 Time 14:27 Sent To PC
Notes
2008-09-29 14:28:11 
 ** TEMPORARY DENIED **
  
 1) NOTE: THE LIGHTING CALCULATIONS INDICATE THE
 FIXTURES AS 2-40WATT T-12 BULBS, YET THE FIXTURE LEGEND
 CALLS FOR THE SAME FIXTURES AS 4-32W T-8 FIXTURES.
 CALLED AND SPOKE TO MR. SCHAFFER. HE SAID FIXTURE
 LEGEND WAS NOT CORRECT AND HE WILL REVISE SHEET E-1.
 CALLED AND LEFT MESSAGE ON MR. JABLONSKI CELL VOICE
 MAIL LETTING HIM KNOW PLANS WOULD BE UNDER *H* WAITING
 FOR NEW SHEETS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-17 Cont ID  
Sent By dpalmer Date 2008-09-17 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2008-09-17 Time 13:45 Sent To  
Notes
2008-09-17 13:46:08** DENIED REVIEW **
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS SUBMITTED
 NEED TO COMPLY WITH FBC 13-415.2.ABC.1.1,AND .1.2. AS
 SUBMITTED IS NOT THE SAME AS THE FLORIDA BUILDING CODE.
 LIGHTING PERFORMANCE CALCULATIONS ARE NOT BASED ON
 CUBIC FEET OR IES LUMENS ETC. THE ENERGY CODE IS FOR
 ENERGY EFFICIENCY.
  
 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS
 13-415.1.ABC.1.1,1.2,. PLEASE SEE THE MAXIMUM TIMES ARE
 NOT LISTED, THE TYPE OF DEVICES AS SHOWN
  
  
 *** AS STATED ON THE PREVIOUS REVIEWS: IF THERE ARE
 QUESTIONS PLEASE CALL.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-08 Cont ID  
Sent By dpalmer Date 2008-09-08 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2008-09-08 Time 10:43 Sent To  
Notes
2008-09-08 10:43:53 
  
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3. PLEASE SEE NOTES ON PREVIOUS REVIEW WHICH
 REQUESTED TO INDICATE THE MINIMUM LIGHTING CONTROLS AS
 REQUIRED MEETING CODE.
 THE RESPONSE LETTER MENTIONS CONTROLS CHANGED TO
 *PHOTOCELL*. PHOTOCELL CONTROLS ARE FOR EXTERIOR
 LIGHTING MEASURING THE SUNLIGHT LEVELS.
 OCCUPANCY SENSORS ARE DEVICES FOR INTERIOR LIGHTING
 CONTROLS IN EITHER CASE THE PLANS STILL INDICATE
 STANDARD SINGLE POLE SWITCHES WHICH ARE NOT PERMITTED.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO THE LIGHTING PERFORMANCE CALCULATIONS REQUIRED.
 RESPONSE MENTIONS THESE WERE DONE AND ON PLANS. HOWEVER
 THE PLANS DO NOT INDICATE ANY LIGHTING PERFORMANCE
 CALCULATIONS.13-415.2.ABC.1.1, .1.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO SIGN CIRCUIT REQUIRED LOCATION. THE PREVIOUS
 COMMENT MENTIONED THE PANEL SCHEDULE DID INDICATE THE
 EXISTING 240V CIRCUIT HOWEVER TO PLEASE INDICATE THE
 LOCATION SO THAT VERIFICATION OF 600.5 CAN BE MADE. THE
 RESPONSE MENTIONS THIS WAS DONE HOWEVER THE PLANS DO
 NOT SHOW ANY EXISTING OR NEW SIGN CIRCUITS ON PLANS AT
 LOCATIONS REQUIRED PER 600.5.
  
 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By dpalmer Date 2008-08-13 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2008-08-13 Time 13:40 Sent To  
Notes
2008-08-13 13:40:36 
 ** DENIED PLANS.**
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 FBC 2004 W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ( PLANS STATE 2002 NFPA-70) THIS CODE HAS NOT BEEN IN
 EFFECT IN THE STATE OF FLORIDA SINCE DEC 8TH2006
  
 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW
 HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR
 ADA.
  
 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR AUTOMATED LIGHTING CONTROLS REQUIRED. PLANS SHOW A
 SWITCH AT FRONT AND REAR OF SPACE WHICH IS NOT
 ACCEPTABLE.
 PLEASE BE SURE TO SEE THE SECTIONS AS NOTED FOR
 SEPARATE SPACES AS WELL AS BREAK ROOMS.
  
 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PANEL SCHEDULE INDICATES A 2-POLE CIRCUIT FOR
 EXISTING SIGNAGE HOWEVER NO SIGN CIRCUIT(S) IS SHOWN ON
 PLANS AT THE LOCATION REQUIRED PER 600.5.
  
 6) NOTE: PLEASE SEE NOTES FOR COLOR CODING OF
 CONDUCTORS. THE 277/480V SYSTEMS ARE NOTED FOR BROWN,
 ORANGE, AND YELLOW.PLEASE KNOW IF ANY THESE SYSTEMS
 ARE 277/480V, THE COLOR CODING SHALL BE BROWN, PURPLE,
 AND YELLOW.
 ** ORANGE IS FOR HIGH-LEG DELTA SYSTEMS>
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-09 Cont ID  
Sent By mawillia Date 2008-10-09 Time 15:11 Rev Time 0.00
Received By mawillia Date 2008-10-09 Time 15:04 Sent To  
Notes
2008-10-09 15:09:49*****APPROVED*****
  
 PLAN SHEET E1 STAMPED, INITIALED, AND DATED; SHEET A1
 WAS PREVIOUSLY FIRE-SATAMPED ON 9/22/2008.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-09-22 Cont ID  
Sent By mawillia Date 2008-09-22 Time 13:33 Rev Time 0.00
Received By mawillia Date 2008-09-22 Time 13:08 Sent To  
Notes
2008-09-22 13:19:03*****PROVISO*****
  
 PLAN SHEET A1 STAMPED, INITIALED, AND DATED; SHEET E1
 TO BE FIRE-SATAMPED WHEN THE ELECTRICAL REVIEW COMMENTS
 HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By mwennerg Date 2008-09-09 Time 15:28 Rev Time 0.00
Received By mwennerg Date 2008-09-09 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By mwennerg Date 2008-08-20 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2008-08-20 Time 13:55 Sent To  
Notes
2008-08-20 14:00:37***DENIED***
  
 1) SHEET INDEX INDICATES FA1.01 SHEET. NO FIRE ALARM
 LAYOUT WAS FOUND WITH THIS SUBMITTAL. PLEASE SUBMIT
 PLAN OR REMOVE REFERENCE FROM SHEET INDEX AND
 ILLUSTRATE ON ELECTRICAL POWER PLAN.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 16:41 Sent To E
Notes
2008-10-01 16:41:27TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 16:47 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 16:47 Sent To E
Notes
2008-09-24 16:48:05TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-12 Cont ID  
Sent By adarroug Date 2008-09-12 Time 14:26 Rev Time 0.00
Received By adarroug Date 2008-09-12 Time 14:26 Sent To  
Notes
2008-09-12 14:45:29TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 10:57 Sent To  
Notes
2008-09-02 10:57:41TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-22 Time   Rev Time 0.00
Received By adarroug Date 2008-08-07 Time 09:29 Sent To  
Notes
2008-08-12 13:32:09TO "BOB"#16
2008-08-07 09:29:18WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-13 Cont ID  
Sent By tgordon Date 2008-08-13 Time 15:59 Rev Time 0.20
Received By tgordon Date 2008-08-13 Time 15:59 Sent To  
Notes
2008-08-13 15:59:54NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-05 Cont ID  
Sent By mperson Date 2008-09-05 Time 09:27 Rev Time 0.00
Received By mperson Date 2008-09-05 Time 09:27 Sent To  
Notes
2008-09-05 09:31:49****************PROVISO****************
 INFORMATION ONLY, REVISION NOT REQUIRED. PER FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.1.3(10)(A), WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By mperson Date 2008-08-14 Time 11:19 Rev Time 0.00
Received By mperson Date 2008-08-14 Time 11:19 Sent To  
Notes
2008-08-14 11:59:11PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A1 FLOOR PLAN IS INDICATING THAT A "PORTABLE
 WATER COOLER TO BE PRESENT PRIOR TO FINAL INSPECTION".
 A PORTABLE WATER COOLER DOES NOT MEET THE FBC-2004
 PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES FOR A BUSSINESS OCCUPANCY. A DRINKING
 FOUNTAIN IS REQUIRED PER TABLE 403.1. PLEASE KNOW THAT
 BOTTLED WATER DISPENSERS (PORTABLE WATER COOLERS) SHALL
 BE PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE KNOW
 THIS PORTABLE WATER COOLER IS SUBSTITUTING FOR 100
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE
 COMPLY WITH THE REQUIRED DRINKING FOUNTAIN.
 NOTE: THE REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH
 THE FOLLOWING FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE. CLEARLY INDICATE THE CLEAR FLOOR SPACE ON SHEET
 A1 FLOOR PLAN.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2.CLEARLY INDICATE THE REQUIRED CLEAR FLOOR SPACE
 FOR THE NEW SINK ON SHEET A1, FLOOR PLAN COMPLIANT WITH
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBLITY CODE SECTION
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 NOTE: THE BATHROOM DOOR SWING IS NOT ALLOWED IN THE
 CLEAR FLOOR SPACE. PER CHAPTER 11, SECTION 11-4.22.2.
  
 3. SHEET P-1 SANITARY WASTE PLAN AND SANITARY WASTE
 ISOMETRIC: CLEARLY INDICATE THAT THE 2" WASTE FOR THE
 NEW SINK WILL DISCHARGE DOWNSTREAM OF THE WET VENTED
 EXISTING BATHROOM. PER FBC-2004 PLUMBING SECTION 909.1
 WET VENT PERMITTED.
  
 4. SHEET P-1 DOMESTIC WATER PLAN AND DOMESTIC WATER
 ISOMETRIC: PLEASE KNOW THAT A WATER-HAMMER ARRESTOR IS
 REQUIRED FOR THE COLD WATER SUPPLY TO THE REFRIGERATOR.
 PER FBC-2004 PLUMBING SECTION 604.9 WATER-HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK
 CLOSING VALVES ARE UTILIZED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-25 Cont ID  
Sent By jroach Date 2008-08-25 Time 15:02 Rev Time 0.00
Received By jroach Date 2008-08-25 Time 15:02 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved