| Plan Review Stops For Permit 08080113 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-09-16 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-09-16 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-09-09 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-09-09 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-08-22 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-08-22 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2008-08-22 16:14:34 | | | | BUILDING PLAN REVIEW | | | PERMIT: 08080113 | | | ADD: 1558 PBL BLVD SUITE #5 | | | CONT: HALLMARK & SONS INC. | | | TEL: (561)644-3498 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 8-22-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) SHEET A1, THE ACCESSIBLE SINK NEXT TO THE BATH ROOM | | | NEEDS TO BE IN COMPLIANCE WITH SECTION 11-4.24. EVEN | | | THOUGH SHEET A4 SHOWS SOME DETAILS, OTHER IMPORTANT | | | ONES ARE MISSING FROM SHEET A1. SHOW THE CLEAR FLOOR | | | SPACE WHICH SHALL BE AT LEAST 30 INCHES BY 48 INCHES. | | | PLEASE NOTE: DOORS SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE REQUIRED FOR ANY FIXTURE FBC 11- 4.22.2 (NOTE | | | BATH ROOM DOOR NEXT TO SINK). | | | | | | 4) THE WALL LEGEND ON SHEET A1 SHOWS TWO TYPES OF WALL, | | | HOWEVER, SHEET A4 SHOWS FOUR DIFFERENT TYPES OF WALLS | | | WHICH ARE NOT CLEARLY INDICATED ON THE FLOOR PLANS. | | | PLEASE IDENTIFY EACH WALL ON THE FLOOR PLANS WITH A | | | NUMBER OR LETTER SO WE CAN KNOW WHICH WALL WILL BE | | | CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED. FBC 106.1.1 | | | | | | 5) SUBMIT EXISTING AND PROPOSED FLOOR PLANS TO SHOW ALL | | | WALLS TO BE DEMOED AND WHICH ONES ARE NEW. THE | | | ADDITIONAL INFORMATION IS REQUIRED SO WE CAN HAVE AN | | | UNDERSTANDING AS TO WHERE ALL THE CHANGES ARE MADE. FBC | | | 106.1.2* | | | | | | 6) PROVIDE ELEVATION DRAWINGS TO SHOW FRAMED OPENING | | | FOR THE GLASS WINDOWS ON SHEET A1. THE DRAWING SHALL | | | ALSO SHOW HOW HIGH THE BOTTOM OF THE GLASS IS ABOVE THE | | | FINISH FLOOR. ADDITIONAL INFORMATION REQUIRED FBC | | | 106.1.2* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-02 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-02 |
Time |
12:38 |
Sent To |
FIRE |
|
| Notes |
| 2008-10-02 12:40:18 | PLANS ROUTED TO FIRE FOR STAMPING OF E-1 | | 2008-10-02 12:40:03 | REDLINED PLANS AS THE CALCULATIONS STILL INDICATE T-12 | | | FIXTURES AND FIXTURE LEGEND INDICATES T-8. | | | | | | CALLED ENGINEER'S OFFICE, HOWEVER WAS NOT AVAILABE AT | | | REVIEW. SPOKE TO CONTRACTOR AND LET HIM KNOW PLANS WERE | | | BEING REDLINED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-29 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-29 |
Time |
14:27 |
Sent To |
PC |
|
| Notes |
| 2008-09-29 14:28:11 | | | | ** TEMPORARY DENIED ** | | | | | | 1) NOTE: THE LIGHTING CALCULATIONS INDICATE THE | | | FIXTURES AS 2-40WATT T-12 BULBS, YET THE FIXTURE LEGEND | | | CALLS FOR THE SAME FIXTURES AS 4-32W T-8 FIXTURES. | | | CALLED AND SPOKE TO MR. SCHAFFER. HE SAID FIXTURE | | | LEGEND WAS NOT CORRECT AND HE WILL REVISE SHEET E-1. | | | CALLED AND LEFT MESSAGE ON MR. JABLONSKI CELL VOICE | | | MAIL LETTING HIM KNOW PLANS WOULD BE UNDER *H* WAITING | | | FOR NEW SHEETS. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO | | | CONTACT THIS OFFICE. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-17 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-17 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2008-09-17 13:46:08 | ** DENIED REVIEW ** | | | | | | 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS SUBMITTED | | | NEED TO COMPLY WITH FBC 13-415.2.ABC.1.1,AND .1.2. AS | | | SUBMITTED IS NOT THE SAME AS THE FLORIDA BUILDING CODE. | | | LIGHTING PERFORMANCE CALCULATIONS ARE NOT BASED ON | | | CUBIC FEET OR IES LUMENS ETC. THE ENERGY CODE IS FOR | | | ENERGY EFFICIENCY. | | | | | | 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS | | | 13-415.1.ABC.1.1,1.2,. PLEASE SEE THE MAXIMUM TIMES ARE | | | NOT LISTED, THE TYPE OF DEVICES AS SHOWN | | | | | | | | | *** AS STATED ON THE PREVIOUS REVIEWS: IF THERE ARE | | | QUESTIONS PLEASE CALL. | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-08 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-08 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2008-09-08 10:43:53 | | | | | | | | | | | | | | | | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING. | | | | | | | | | | | | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. PLEASE SEE NOTES ON PREVIOUS REVIEW WHICH | | | REQUESTED TO INDICATE THE MINIMUM LIGHTING CONTROLS AS | | | REQUIRED MEETING CODE. | | | THE RESPONSE LETTER MENTIONS CONTROLS CHANGED TO | | | *PHOTOCELL*. PHOTOCELL CONTROLS ARE FOR EXTERIOR | | | LIGHTING MEASURING THE SUNLIGHT LEVELS. | | | OCCUPANCY SENSORS ARE DEVICES FOR INTERIOR LIGHTING | | | CONTROLS IN EITHER CASE THE PLANS STILL INDICATE | | | STANDARD SINGLE POLE SWITCHES WHICH ARE NOT PERMITTED. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT | | | TO THE LIGHTING PERFORMANCE CALCULATIONS REQUIRED. | | | RESPONSE MENTIONS THESE WERE DONE AND ON PLANS. HOWEVER | | | THE PLANS DO NOT INDICATE ANY LIGHTING PERFORMANCE | | | CALCULATIONS.13-415.2.ABC.1.1, .1.2 | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH | | | RESPECT TO SIGN CIRCUIT REQUIRED LOCATION. THE PREVIOUS | | | COMMENT MENTIONED THE PANEL SCHEDULE DID INDICATE THE | | | EXISTING 240V CIRCUIT HOWEVER TO PLEASE INDICATE THE | | | LOCATION SO THAT VERIFICATION OF 600.5 CAN BE MADE. THE | | | RESPONSE MENTIONS THIS WAS DONE HOWEVER THE PLANS DO | | | NOT SHOW ANY EXISTING OR NEW SIGN CIRCUITS ON PLANS AT | | | LOCATIONS REQUIRED PER 600.5. | | | | | | 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH | | | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS | | | ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-13 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-13 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2008-08-13 13:40:36 | | | | ** DENIED PLANS.** | | | | | | | | | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN | | | THE FOLLOWING MINIMUM CODES. | | | FBC 2004 W/ 2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | ( PLANS STATE 2002 NFPA-70) THIS CODE HAS NOT BEEN IN | | | EFFECT IN THE STATE OF FLORIDA SINCE DEC 8TH2006 | | | | | | 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW | | | HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR | | | ADA. | | | | | | 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 | | | FOR AUTOMATED LIGHTING CONTROLS REQUIRED. PLANS SHOW A | | | SWITCH AT FRONT AND REAR OF SPACE WHICH IS NOT | | | ACCEPTABLE. | | | PLEASE BE SURE TO SEE THE SECTIONS AS NOTED FOR | | | SEPARATE SPACES AS WELL AS BREAK ROOMS. | | | | | | 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE | | | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | | | | 5) NOTE: PANEL SCHEDULE INDICATES A 2-POLE CIRCUIT FOR | | | EXISTING SIGNAGE HOWEVER NO SIGN CIRCUIT(S) IS SHOWN ON | | | PLANS AT THE LOCATION REQUIRED PER 600.5. | | | | | | 6) NOTE: PLEASE SEE NOTES FOR COLOR CODING OF | | | CONDUCTORS. THE 277/480V SYSTEMS ARE NOTED FOR BROWN, | | | ORANGE, AND YELLOW.PLEASE KNOW IF ANY THESE SYSTEMS | | | ARE 277/480V, THE COLOR CODING SHALL BE BROWN, PURPLE, | | | AND YELLOW. | | | ** ORANGE IS FOR HIGH-LEG DELTA SYSTEMS> | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-10-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-09 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-09 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2008-10-09 15:09:49 | *****APPROVED***** | | | | | | PLAN SHEET E1 STAMPED, INITIALED, AND DATED; SHEET A1 | | | WAS PREVIOUSLY FIRE-SATAMPED ON 9/22/2008. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-09-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-22 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-09-22 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2008-09-22 13:19:03 | *****PROVISO***** | | | | | | PLAN SHEET A1 STAMPED, INITIALED, AND DATED; SHEET E1 | | | TO BE FIRE-SATAMPED WHEN THE ELECTRICAL REVIEW COMMENTS | | | HAVE BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-09 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-09 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-08-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-20 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-20 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2008-08-20 14:00:37 | ***DENIED*** | | | | | | 1) SHEET INDEX INDICATES FA1.01 SHEET. NO FIRE ALARM | | | LAYOUT WAS FOUND WITH THIS SUBMITTAL. PLEASE SUBMIT | | | PLAN OR REMOVE REFERENCE FROM SHEET INDEX AND | | | ILLUSTRATE ON ELECTRICAL POWER PLAN. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-01 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-01 |
Time |
16:41 |
Sent To |
E |
|
| Notes |
| 2008-10-01 16:41:27 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-24 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-24 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2008-09-24 16:48:05 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-09-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-12 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-12 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2008-09-12 14:45:29 | TO "BOB"#11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-02 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-02 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2008-09-02 10:57:41 | TO "BOB"#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-08-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-07 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2008-08-12 13:32:09 | TO "BOB"#16 | | 2008-08-07 09:29:18 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2008-08-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-13 |
Time |
15:59 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-08-13 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2008-08-13 15:59:54 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-05 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-05 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2008-09-05 09:31:49 | ****************PROVISO**************** | | | INFORMATION ONLY, REVISION NOT REQUIRED. PER FBC-2004 | | | CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION | | | 11-4.1.3(10)(A), WHERE ONLY ONE DRINKING FOUNTAIN IS | | | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN | | | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS | | | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE | | | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS | | | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR | | | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED | | | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-14 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-14 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2008-08-14 11:59:11 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET A1 FLOOR PLAN IS INDICATING THAT A "PORTABLE | | | WATER COOLER TO BE PRESENT PRIOR TO FINAL INSPECTION". | | | A PORTABLE WATER COOLER DOES NOT MEET THE FBC-2004 | | | PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED | | | PLUMBING FIXTURES FOR A BUSSINESS OCCUPANCY. A DRINKING | | | FOUNTAIN IS REQUIRED PER TABLE 403.1. PLEASE KNOW THAT | | | BOTTLED WATER DISPENSERS (PORTABLE WATER COOLERS) SHALL | | | BE PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50 | | | PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE KNOW | | | THIS PORTABLE WATER COOLER IS SUBSTITUTING FOR 100 | | | PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE | | | COMPLY WITH THE REQUIRED DRINKING FOUNTAIN. | | | NOTE: THE REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH | | | THE FOLLOWING FBC-2004 CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE SECTIONS. | | | | | | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS | | | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING | | | INFORMATION) | | | | | | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET | | | MAXIMUM. | | | | | | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN | | | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT | | | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN | | | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" | | | OF THE FRONT OF FOUNTAIN. | | | | | | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE | | | MOUNTED NEAR FRONT EDGE. | | | | | | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR | | | SPACE. CLEARLY INDICATE THE CLEAR FLOOR SPACE ON SHEET | | | A1 FLOOR PLAN. | | | | | | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS | | | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN | | | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS | | | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE | | | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS | | | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR | | | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED | | | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). | | | | | | 2.CLEARLY INDICATE THE REQUIRED CLEAR FLOOR SPACE | | | FOR THE NEW SINK ON SHEET A1, FLOOR PLAN COMPLIANT WITH | | | FBC-2004 CHAPTER 11, FLORIDA ACCESSIBLITY CODE SECTION | | | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR | | | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE | | | SINK. | | | NOTE: THE BATHROOM DOOR SWING IS NOT ALLOWED IN THE | | | CLEAR FLOOR SPACE. PER CHAPTER 11, SECTION 11-4.22.2. | | | | | | 3. SHEET P-1 SANITARY WASTE PLAN AND SANITARY WASTE | | | ISOMETRIC: CLEARLY INDICATE THAT THE 2" WASTE FOR THE | | | NEW SINK WILL DISCHARGE DOWNSTREAM OF THE WET VENTED | | | EXISTING BATHROOM. PER FBC-2004 PLUMBING SECTION 909.1 | | | WET VENT PERMITTED. | | | | | | 4. SHEET P-1 DOMESTIC WATER PLAN AND DOMESTIC WATER | | | ISOMETRIC: PLEASE KNOW THAT A WATER-HAMMER ARRESTOR IS | | | REQUIRED FOR THE COLD WATER SUPPLY TO THE REFRIGERATOR. | | | PER FBC-2004 PLUMBING SECTION 604.9 WATER-HAMMER. A | | | WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK | | | CLOSING VALVES ARE UTILIZED. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-08-25 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-08-25 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|