| 2008-08-06 16:40:05 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: PLANS ARE INDICATING EXISTING GAS METER, HOWEVER |
| | THE PLANS ARE NOT INDICATING THE EXISTING LONGEST |
| | LENGTH OR IF THE WATER HEATER BEING REMOVED IS THE ONLY |
| | APPLIANCE, ALSO NOT ALL CUT SECTIONS OF PIPE ARE |
| | INDICATING CORRESPONDING LENGTHS ON THE PROPOSED GAS. |
| | ONLY ONE CUT SECTION OF PIPE INDICATES 10'. PLEASE |
| | REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS THAT DO |
| | NOT INDICATE CORRESPONDING LENGTHS AND COMPLY ON THE |
| | RESUBMITTAL. |
| | |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: SUBMITTED PLANS ARE NOT INDICATING THE EXISTING |
| | BTU OR PROPOSED BTU LOAD (SEE COMMENT #1). |
| | |
| | 3. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) ON THE |
| | RESUBMITTED PLANS. |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 4. THE SEDIMENT TRAP SHALL BE LOCATED DOWNSTREAM OF |
| | THE EQUIPMENT SHUT OFF VALVE. PER FBC-2004 FUEL GAS |
| | SECTION 408.4. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: SUBMIT TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATION SHEETS OF THE TANKLESS WATER HEATER |
| | CLEARLY INDICATING THE MAKE, MODEL NUMBER, BTU LOAD |
| | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY (EXAMPLES OF LISTINGS = CSA, AGA, |
| | UL) |
| | |
| | 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | (W.P.B. AS AMENDED) SECTION *106.3.4.3. |
| | NOTE: PER FS 471.003(2)(H), THE PLUMBING CONTRACTOR |
| | CAN BE THE DESIGNER OF RECORD IF THEY ARE THE INSTALLER |
| | OF THE SYSTEMS WHICH THEY DESIGN. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |