Plan Review Details - Permit 08080076
Plan Review Stops For Permit 08080076
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-09 Cont ID  
Sent By jwitmer Date 2008-10-09 Time 11:06 Rev Time 0.22
Received By jwitmer Date 2008-10-09 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-07 Cont ID  
Sent By jwitmer Date 2008-10-07 Time 07:35 Rev Time 0.77
Received By jwitmer Date 2008-10-07 Time 07:35 Sent To  
Notes
2008-10-07 07:42:56BUILDING PLAN REVIEW
 PERMIT: 08080076
 ADD: 2461 METROCENTRE BLVD.
 CONT: FRAZEE, INC
 TEL: (407) 448-2410
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) COMPLIED.
  
 2-4B) COMPLIED.
  
 4C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) 2ND REQUEST, SHEET A200 DETAIL# 20 DOES NOT PROVIDE
 THE WIND PRESSURES AND WIND DESIGN CRITERIA.
 1609.6.2 WIND DESIGN PROCEDURES
 A) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 B) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WTIH SECTION1609.5.
  
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By jwitmer Date 2008-08-20 Time 15:56 Rev Time 3.33
Received By jwitmer Date 2008-08-20 Time 15:56 Sent To  
Notes
2008-08-20 16:40:18BUILDING PLAN REVIEW
 PERMIT: 08080076
 ADD: 2461 METROCENTRE BLVD.
 CONT: FRAZEE, INC
 TEL: (407) 448-2410
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) SHEET A001 THE EXISTING BUILDING INFORMATION
 INDICATES IN 1996 THIS WAS A TYPE V-UNPROTECTED UNDER
 THE STANDARD BUILDING CODE. WE ARE CURRENTLY IN THE
 2004 FLORIDA BUILDING CODE AND THE
 CONSTRUCTION TYPE OF COMPARISON BETWEEN THE TWO CODES
 WILL MAKE THIS BUILDING TYPE A TYPE III-B NOT A V-B,
 PLEASE CORRECT .
  
 3) SHEET A-102 INDICATES IN DETAIL# 2 A NEW INFILL
 SECTION OF WALL USING CONCRETE BLOCK, WITH NO
 STRUCTURAL MEMBERS (VERTICAL OR HORIZONTAL STEEL)
 TYING BACK INTO THE EXTERIOR WALL. 1609.6.2.1.
  
 4) A-102 ALSO NOTE # 3 INDICATES TWO NEW WINDOWS, NO
 PRODUCT APPROVALS WERE SUBMITTED. 1609.1.4 PROTECTION
 OF OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60
 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST
 OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS: FIXED WINDOWS.
  
  
 4B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) SHEET A200 DETAIL# 20 DOES NOT PROVIDE THE WIND
 PRESSURES AND WIND DESIGN CRITERIA.
 1609.6.2 WIND DESIGN PROCEDURES
 A) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 B) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WTIH SECTION1609.5.
  
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By dpalmer Date 2008-10-07 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2008-10-07 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 08:12 Sent To  
Notes
2008-08-28 08:12:26 
  
  
  
  
 **DENIED**
  
  
  
 1) NOTE: NO ELECTRICAL LIGHTING PLAN SUBMITTED. NEED TO
 SHOW ALL LIGHTING, AND HOW LIGHTING IS BEING
 CONTROLLED.
 PLEASE ALSO INDICATE THE LIGHTING PERFORMANCE LEVELS.
 13-415.1.ABC.1.1, .1.2.
 13-415.2, 13-415.2.ABC.1.1,.1.2
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION TO BE ON PLANS.
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH MINIMUM
 SIZE CONDUCTORS AND OVER CURRENT PROTECTION.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITS 15/20AMP 120V IN
 AREAS TO BE GFI OR GFI PROTECTED PER 210.8B2
  
 4) NOTE: PLEASE BE SURE THE PLANS STATE THE MINIMUM
 CODES AS FOLLOWS.
 2004 FBC W2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 5) NOTE: PLEASE CONFIRM ANY ADDITIONAL OR RELOCATED
 HORN OR STROBE DEVICES MEETING FBC 11-4.28 FOR ADA.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-17 Cont ID  
Sent By mawillia Date 2008-10-15 Time 13:24 Rev Time 0.00
Received By lmartine Date 2008-10-15 Time 12:46 Sent To  
Notes
2008-10-17 17:09:20PASSED THE OUT STOP FOR MIKE.
2008-10-15 13:24:01*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A102, E101, FA001, AND
 FP001 WERE STAMPED, INTIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-28 Cont ID  
Sent By mawillia Date 2008-08-28 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-08-28 Time 14:02 Sent To  
Notes
2008-08-28 17:06:54*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. SHOW THE LOCATION OF THE EXITS, EXIT LIGHTS,
 EMERGENCY LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE NEW
 FLOOR PLAN.
  
 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS AND
 FIRE ALARM DEVICES FOR THE NEW FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 11:43 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 11:43 Sent To  
Notes
2008-09-18 11:43:20TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-28 Cont ID  
Sent By mawillia Date 2008-08-28 Time 14:02 Rev Time 0.00
Received By mawillia Date 2008-08-06 Time 09:01 Sent To  
Notes
2008-08-06 09:01:53TO "COMM" BD#24