| 2008-09-22 13:13:42 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS.. |
| | |
| | 1- REVISE INSTALLATION SCHEDULE: |
| | A) OPENING SIZE IS NOT CLEAR. EG: WHAT'S 18.8, 8.9 AND |
| | 19.6. |
| | B) MISSING THE NEGATIVE WALL OPENING PRESSURES. ONLY |
| | THE POSITIVE PRESSURES WERE SHOWN. |
| | C) SHUTTER SPAN DOESN'T CORRESPOND TO OPENING SIZE |
| | SHOWN. |
| | D) ACCORDION SHUTTERS ARE INSTALLED VERTICALLY, NOT |
| | HORIZONTALLY. REVISE AS REQUIRED. SEE SHEET 1 OF 13. |
| | E) EDGE DISTANCE IS INCORRECT. THIS APPLIES TO EDGE |
| | DISTANCE FROM THE OPENING TO THE EXACT LOCATION OF THE |
| | ANCHOR TO BE USED. SEE PRODUCT APPROVAL PAGE 8 OF 13 |
| | FOR PROPER EDGE DISTANCE CONSIDERATIONS. |
| | F) REVISE ANCHOR SPACING. SEE SHEET 8 OF 13. ANCHOR |
| | SPACING IS IN RELATION TO THE DESIGN PRESSURES, EDGE |
| | DISTANCE, CONNECTION TYPE PANEL SPAN AND STRUCTURE TO |
| | BE ATTACHED TO. |
| | G) SIZE OF TAPCON IS TO SMALL. 3/16 TAPCONS ARE NOT |
| | USED IN THE PRODUCT APPROVAL. MARK SPECIFIC TYPE OF |
| | ANCHOR TO BE USED. SEE SHEET 8 OF 13. |
| | |
| | ***NOTE: YOU MAY USE OPENING DESIGN PRESSURES SHOWN ON |
| | ATTACHED INSTALLATION SCHEDULE OR YOU MAY PROVIDE |
| | ACTUAL DESIGN PRESSURES FOR EACH OPENING. KEEP IN MIND |
| | THAT PROPERTY IS LOCATED IN EXPOSURE "C" WHEN |
| | CALCULATING THE DESIGN PRESSURES. |
| | |
| | 2- CLEARLY CIRCLE ON SHUTTER DRAWINGS SPECIFIC MOUNTING |
| | CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC) AND |
| | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED ACCORDING |
| | TO THE DESIGN PRESSURES, EDGE DISTANCE, PANEL SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE ATTACHED TO ( |
| | CONCRETE, CONCRETE BLOCK OR WOOD). (REPEAT COMMENT. |
| | ANCHOR TYPE AND SPACING WAS NOT MARKED ON DRAWINGS). |
| | |
| | 3- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | PERMIT VALUATION TO INCLUDE ALL LABOR AND MATERIALS. |
| | OTHERWISE VALUATION WILL BE ESTIMATED USING THE |
| | MARSHALL AND SWIFT ESTIMATING BOOK. NEED CORRECT |
| | OPENING SIZE TO CALCULATE SHUTTERS TOTAL SQUARE FOOTAGE |
| | AND DETERMINE THE VALUATION. |
| | |
| | 4- NOTICE OF COMMENCEMENT MAY BE REQUIRED ONCE UPDATE |
| | PERMIT VALUATION IS PERFORMED. |
| | |
| | ***NOTE: IF YOU HAVE ANY QUESTIONS REGARDING HOW TO |
| | COMPLETE THE INSTALLATION SCHEDULE, PLEASE CALL ME TO |
| | CLARIFY ANY ISSUE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |