Plan Review Details - Permit 08080065
Plan Review Stops For Permit 08080065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-15 Cont ID  
Sent By mjacobs Date 2008-09-15 Time 14:11 Rev Time 0.00
Received By mjacobs Date 2008-09-15 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mjacobs Date 2008-08-22 Time 08:02 Rev Time 0.00
Received By mjacobs Date 2008-08-22 Time 06:52 Sent To  
Notes
2008-08-22 08:02:42BUILDING PLAN REVIEW
 PERMIT: 08080065
 ADD: 529 S. FLAGLER DR. #264
 CONT: DESIGN CONTRACTING INC,
 TEL: (561)514-2004
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. THE LEVEL OF ALTERATION SHALL BE STATED ON
 THE PLANS.
  
 5) PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN TO
 SHOW EXACTLY WHERE ALL CHANGES WILL OCCUR THROUGH OUT
 THE SPACE. IT APPEARS THAT THERE WILL BE NEW SOFFITS
 CONSTRUCTED IN VARIOUS ROOMS; PLEASE INDICATE THE
 FASTENERS ATTACHMENT AND SPACING FOR THE TOP METAL
 TRACK. DOES THE MARBLE FLOOR EXIST OR A NEW ONE WILL BE
 INSTALLED? IF THIS IS A NEW FLOOR SYSTEM, PLEASE TAKE
 NOTE THAT FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A SWELLING UNIT AND PUBLIC OR SERVICE
 AREA WITH IN THE STRUCTURE SHALL HAVE AND IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492. FBC 1207.3. PROVIDE THE MANUFACTURE SPECIFICATIONS
 FOR THE CORK.
  
 6) INDICATE ON THE PLANS THE USE AND OCCUPANCY OF THE
 BUILDING AND THE TYPE OF BUILDING PER CHAPTER 3 AND 6
 RESPECTIVELY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By btrobaug Date 2008-09-24 Time 16:19 Rev Time 0.00
Received By btrobaug Date 2008-09-24 Time 16:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 14:08 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By mwennerg Date 2008-09-17 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2008-09-17 Time 15:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 10:48 Rev Time 0.00
Received By mwennerg Date 2008-08-22 Time 10:48 Sent To  
Notes
2008-08-22 10:54:15***DENIED***
  
 1) PLEASE ADD 2003 EDITION TO NFPA 101 UNDER GENERAL
 NOTES.
  
 2) SMOKE DETCTORS ARE SHOWN THAT WOULD IMPLY A DEVICE
 TIED INTO A FIRE ALARM SYSTEM. IF DEVICES ARE SINGLE OR
 MULTIPLE STATION DEVICES THAT RESPOND TO SMOKE AND
 NOTIFY OCCUPANTS, CHANGE REFERENCE TO SMOKE ALARM ON
 PLANS.
  
 3) AC DIFFUSERS IF RELOCATED SHALL BE A MINIMUM OF
 THREE (3) FEET FROM SMOKE ALARMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 11:30 Sent To  
Notes
2008-09-11 11:32:16TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-22 Cont ID  
Sent By mperson Date 2008-08-22 Time 13:54 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 10:56 Sent To PC
Notes
2008-08-12 13:33:30TO "BOB"#2
2008-08-05 10:57:12WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-09-15 Cont ID  
Sent By tgordon Date 2008-09-15 Time 16:45 Rev Time 0.20
Received By tgordon Date 2008-09-15 Time 16:45 Sent To  
Notes
2008-09-15 16:46:01NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT
 NUMBER APPLIED FOR AT THIS TIME.
  
 NOTICE: A MECHANICAL PERMIT AND PLAN WILL BE NEEDED FOR
 ANY MECHANICAL (A/C) WORK BEING DONE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-13 Cont ID  
Sent By tgordon Date 2008-08-13 Time 14:02 Rev Time 0.20
Received By tgordon Date 2008-08-13 Time 14:02 Sent To  
Notes
2008-08-13 14:05:38NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT
 NUMBER APPLIED FOR AT THIS TIME.
  
 NOTICE: A MECHANICAL PERMIT AND PLAN WILL BE NEEDED FOR
 ANY MECHANICAL (A/C) WORK BEING DONE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-11 Cont ID  
Sent By mperson Date 2008-09-11 Time 13:39 Rev Time 0.00
Received By mperson Date 2008-09-11 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mperson Date 2008-08-22 Time 13:34 Rev Time 0.00
Received By mperson Date 2008-08-22 Time 13:34 Sent To I
Notes
2008-08-22 13:54:08PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1: MORE INFORMATION IS REQUIRED DUE TO THE
 FACT THAT THE PERMIT BEING APPLIED FOR STATES "KITCHEN;
 GUEST BATH; POWDER ROOM; MASTER BATH REMODEL". PLEASE
 PROVIDE THE FOLLOWING INFORMATION IF IT PERTAINS TO
 YOUR JOB. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 A} IF THE FLOOR PLAN PLUMBING LAYOUT IS THE SAME AND
 THE PLUMBING FIXTURES ARE ONLY TO BE CHANGED, PLEASE
 INDICATE ON THE RESUBMITTED PLANS, "EXACT FIXTURE
 CHANGEOUT ONLY, NO CHANGES IN PLUMBING FLOOR PLAN
 LAYOUT".
  
 B} IF THE NEW PROPOSED FLOOR PLAN PLUMBING LAYOUT IS
 DIFFERENT FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING
 ON SEPERATE DRAWINGS.
 A) EXISTING FLOOR PLAN LAYOUT.
 B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW
 WHAT IS REQUIRED IN COMMENTS #2 AND #3.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (4)(6)(13). PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (3)(5)(10)(13). PLEASE SUBMIT A PLUMBING
 POTABLE WATER ISOMETRIC RISER DIAGRAM INDICATING ALL
 PIPE SZES, VALVE LOCATIONS, WATER HEATER LOCATION, AND
 LOCATION OF WATER SUPPLY LINE.
  
 4. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 5. DECLARE THE USE AND OCCUPANCY AND THE TYPE OF
 BUILDING. PER FBC-2004 BUILDING CHAPTER 3, AND 6,
 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-12 Cont ID  
Sent By mflis Date 2008-08-12 Time 15:49 Rev Time 0.00
Received By mflis Date 2008-08-12 Time 15:49 Sent To  
Notes
2008-08-12 15:49:56ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR WORK ONLY
  
 MATT FLIS - 822-1445