Plan Review Details - Permit 08080043
Plan Review Stops For Permit 08080043
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-15 Cont ID  
Sent By btrobaug Date 2008-08-15 Time 11:35 Rev Time 0.00
Received By btrobaug Date 2008-08-15 Time 10:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 11:52 Rev Time 0.00
Received By btrobaug Date 2008-08-04 Time 11:44 Sent To I
Notes
2008-08-04 11:52:00THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE WHAT CALCULATION WAS USED TO DETERMINE THE
 DEMAND OF 80% USED IN THE CALCULATION GIVEN.
  
 2} THE SERVICE ENTRANCE CONDUCTORS MUST BE SIZED PER
 310.15(B)(6) AS THEY ARE IN CONDUIT., OR 310.16, 310.17
 DOES NOT APPLY TO FPL SERVICE DROPS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 11:52 Rev Time 0.00
Received By btrobaug Date 2008-08-04 Time 09:59 Sent To PC
Notes
2008-08-04 10:00:08TO "E" BOX