Plan Review Details - Permit 08070871
Plan Review Stops For Permit 08070871
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-19 Cont ID  
Sent By shill Date 2008-09-19 Time 15:35 Rev Time 0.00
Received By shill Date 2008-09-19 Time 15:35 Sent To  
Notes
2008-09-19 15:43:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. SEE OPENING 2. C2 CONNECTION TYPE INTO CONCRETE
 BLOCK REQUIRES 11" SPACING, BUT THE INSTALLATION
 SCHEDULE SPECIFIES 12". PLEASE REVISE AND CHECK ALL.
  
 3RD REVIEW, C1 ALSO REQUIRES 11 INCH SPACING FOR BLOCK
 SUBSTRATE, OPENING 2. PLEASE REVISE AND CHECK ALL. SEE
 ALSO OPENING 1. THIS COMMENT MAY APPLY TO OTHER
 CONNECTIONS/OPENINGS.
  
 NEW COMMENT:
  
 3. PLEASE CORRELATE THE INSTALLATION SCHEDULE WITH THE
 FLOOR PLAN.
  
 4. SHOW THE EMERGENCY MEANS OF ESCAPE ON THE FLOOR PLAN
 FBC R310.4.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-28 Cont ID  
Sent By shill Date 2008-08-28 Time 08:47 Rev Time 0.00
Received By shill Date 2008-08-28 Time 08:47 Sent To  
Notes
2008-08-28 08:54:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE OPENING 1.C2 CONNECTION TYPE, TAPCON
 FASTENER, INTO CONCRETE BLOCK NOT PERMITTED IN SPANS
 OVER 5' (SEE THAT THERE ARE HATCHED LINES IN THAT BOX,
 SHEET 4 OF PRODUCT APPROVAL).PLEASE REVISE.THIS
 COMMENT MAY APPLY TO OTHER OPENINGS.
  
 2.SEE OPENING 2.C2 CONNECTION TYPE INTO CONCRETE
 BLOCK REQUIRES 11" SPACING, BUT THE INSTALLATION
 SCHEDULE SPECIFIES 12".PLEASE REVISE AND CHECK ALL.
  
 3.PLEASE PROVIDE TWO COMPLETE COLLATED SETS OF PERMIT
 DOCUMENTS.OLD SHEETS ARE TO BE SUBMITTED FOR
 REFERENCE, BUT PULLED OUT OF THE BOUND PERMIT PACKAGE
 AND VOIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 13:43 Rev Time 0.00
Received By shill Date 2008-08-04 Time 13:43 Sent To  
Notes
2008-08-04 13:44:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.PLEASE COMPLETE THE INSTALLATION SCHEDULE.IT WAS
 SUBMITTED INCOMPLETE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 13:43 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***