| 2008-08-15 10:45:29 | ***DENIED*** |
| | |
| | 1) PLANS SEEM TO SUGGEST SMOKE DETECTORS CONNECTED TO |
| | THE FIRE ALARM SYSTEM THROUGHOUT THE GUEST SUITES. |
| | PLEASE NOTE NFPA 101, SEC. 28.3.4.5 REQUIRESAPPROVED |
| | SINGLE STATION SMOKE ALARMS IN EVERY GUEST ROOM AND |
| | EVERY LIVING AREA AND SLEEPING ROOM. |
| | |
| | 2) NFPA 101, SEC. 28.3.4.2 (2) REQUIRES A MANUAL FIRE |
| | ALARM BOX AT THE HOTEL DESK OR OTHER CENTRAL LOCATION |
| | UNDER CONTINUOUS SUPERVISION BY RESPONSIBLE EMPLOYEES. |
| | PLEASE ILLUSTRATE ON PLANS |
| | |
| | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE |
| | ADD NOTE TO PLANS |
| | |
| | 4) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL |
| | STATION SERVICE PRIOR TO FINAL INSPECTION. PLEASE ADD |
| | NOTE TO PLANS |
| | |
| | 5) MORE INFORMATION REQUIRED WITH REGARD TO ELECTRIC |
| | LOCKS. SPECIAL LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| | NFPA 101, SEC. 7.2.1.6. ADDITIONALLY, SEPARATE SHOP |
| | DRAWINGS AND PERMIT IS REQUIRED PRIOR TO INSTALLATION. |
| | AT TIME OF PERMIT APPLICATION, MANUFACTURER |
| | SPECIFICATION SHEETS REQUIRED. |
| | |
| | 6) ALL WORK TO COMPLY WITH NFPA 72, 2002. |
| | |
| | 7) PLEASE INDICATE TYPE OF DETECTION COVERAGE PER NFPA |
| | 72 AS THERE DOES NOT APPEAR TO BE COVERAGE IN |
| | ELECTRICAL, MECHANICAL, STORAGE AREAS ETC. |
| | |
| | 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. |
| | |
| | 9) PLEASE PROVIDE SEQUENCE OF OPERATION TO DRAWINGS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |