2008-09-16 14:46:11BUILDING PLAN REVIEW
 PERMIT: 08070817
 ADD: 4200 N FLAGLER DR
 CONT: PREMIER MODULAR BUILDING LC
 TEL: (407)467-2189
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBER 16,2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) COMPLIED.
 1E) IN THE FIRST ROUND OF REVIEWS THE MANUFACTURER HAD
 THEIR CERTIFICATION LETTER, THIS REVIEW IT IS MISSING.
 106.1.2/ RULE 9B-1
 2) THE SUBMITTED PLANS FOR A MODULAR BUILDING DOES NOT
 APPEAR ON THEIR WEBSITE. MANUFACTURED (MODULAR)
 BUILDING PROGRAM UNDER THE JURISDICTION OF THE
 DEPARTMENET OF COMMUNITY AFFAIRS (DCA). RULE 9B-1 OF
 THE FLORIDA ADMINISTRATIVE CODE.
  
 3) MINIMUM PLAN REVIEW REQUIREMENTS OF 106.3.5.1.1 SITE
 REQUIREMENTS, WILL REQUIRE A SITE PLAN FOR
 3A) PARKING
 3B) ACCESSIBLE PARKING SPACE 11-4.6
 3C) ACCESSIBLE ROUTE 11-41.3 (1)
 3D) COMPLIED.
 3E) COMPLIED.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: THIS STRUCTURE IS LOCATED IN A A-5
 FLOOD ZONE, FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 5A) PLEASE INDICATE COMPLIANCE WITH CODE OF ORDINANCES
 SEC 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION. ALL NEW
 CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY
 COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL
 STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING
 BASEMENT, ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE
 BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT
 UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO
 THAT BELOW SIX INCHES ABOVE THE FLOOD BASE LEVEL THE
 STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY
 IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL
 COMPONENTS HAVING THE CAPABILITY OF RESISTING
 HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF
 BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR
 ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS
 SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE
 PROVIDED TO THE CITY ENGINEER.
  
 5B) SHEET FD2 INDICATES USE OF A FILL TYPE BIRM RAISING
 THE GRADE AROUND THE MODULAR BUILDING. THIS DOES NOT
 MEET THE REQUIRED WATERPROOFING REQUIREMENTS OF SECTION
 94-546. SHEET FD2 STRUCTURAL LOAD LIMITATIONS NOTE # 7
 FLOOD ZONE INDICATES THIS STRUCTURE MAY NEED TO BE SET
 HIGHER THAN PROPOSED, SINCE THE BIRM IS NOT CONSIDERED
 A WATERPROOFING METHOD APPROVED BY THE BUILDING
 OFFICIAL.
  
 5C) SHEET FD2 THE LEFT DETAIL INDICATES THE SKIRTING
 DETAIL IS INDIRECT CONTACT WITH SOILS. THERE IS TWO
 CONCERNS. THE FIRST IS THE STATE APPROVED PLANS DO NOT
 INDICATE THE USE OF NATURALLY DURABLE WOOD OR
 PRESERVATIVE -TREATED WOOD, 2304.11.2.5. THE PLANS DO
 INDICATE THE SOILS BEING TERMITE TREATED.
  
 5D) NORMALLY THERE IS A 6" SPACE AS IN THE DETAIL AT
 THE RIGHT WHERE THERE IS A 12 INCH GAP BETWEEN THE
 MANUFACTURED BUILDING AND BIRM. 2304.11.2.1 JOISTS,
 GIRDERS AND SUBFLOOR. WHERE WOOD JOISTS OR THE BOTTOM
 OF A WOOD STRUCTURAL FLOOR WITHOUT JOISTS ARE CLOSER
 THAN 18 INCHES (457 MM), OR WOOD GIRDERS ARE CLOSER
 THAN 12 INCHES (305 MM) TO THE EXPOSED GROUND IN CRAWL
 SPACES OR UNEXCAVATED AREAS LOCATED WITHIN THE
 PERIMETER OF THE BUILDING FOUNDATION, THE FLOOR
 ASSEMBLY (INCLUDING POSTS, GIRDERS, JOISTS AND
 SUBFLOOR) SHALL BE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 5E) NOW THAT THE PLANS INDICATE THIS SOILS BIRM AROUND
 THE PERIMETER OF THE MANUFACTURED BUILDING PLEASE
 PROVIDE COMPLIANCE WITH 1209.1 CRAWL SPACES.
 CRAWL SPACES SHALL BE PROVIDED WITH A MINIMUM OF ONE
 ACCESS OPENING NOT LESS THAN 18 INCHES BY 24 INCHES
 (457 MM BY 610 MM).
  
 5F) TERMITE PROTECTION, THE STATE APPROVED PLANS
 COVERSHEET SITE INSTALLED NOTE #2, INDICATES GUTTERS
 AND DOWNSPOUTS IF APPLICABLE.PLEASE REVIEW 1503.6. THE
 STATE PLANS DOES NOT HAVE ANY OVERHANGSOR EAVES.
  
 6) FOUNDATION SYSTEMS, SHEET FD-1 NEITHER THE PLANS NOR
 THE PERMIT APPLICATION PROJECT DETAILS INDICATE THE
 LENGTH OF TIME THIS STRUCTURE IS TO BE ISSUED A C.O.
 FORE. IF THIS IS A TEMPORARY STRUCTURE OR PERMANENT
 STRUCTURE, SEE DEFINITIONS FOR TEMPORARY BUT SHALL NOT
 BE PERMITTED FOR MORE THAN 180 DAYS. THE BUILDING
 OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR
 DEMONSTRATED CAUSE. IF THIS IS TO BE A TEMPORARY
 STRUCTURE THE INFORMATION LISTED IN 6A-B WILL BE
 REQUIRED.
  
 6A) COMPLIED AS TO TITLE BLOCK.
  
 6B)COMPLIED.
 6C) IF THE DECISION FOR A PERMANENT STRUCTURE IS
 PROVIDED THEN THE REQUIREMENTS FOR A PERMANENT
 FOUNDATION SHALL BE MET:
 6C) (1) COMPLIED
 6C)(2) 1816.1 TRMITE TREATMENT SEE STATEMENTS ABOVE.
 6C)(3) 1209.1 CRAWL SPACE AND REQUIRED OPENING 6C)(4)
 1203.3.1 OPENINGS FOR UNDER-FLOOR VENTILATION 6C)(5)
 THE FOUNDATION IS DESIGNED FOR AN B EXPOSURE WHILE THE
 BUILDING IS DESIGNED FOR A C EXPOSURE AND LOCATED IN A
 C ZONE.1609.4. SEE STATEMENTS ABOVE.
  
 7) SINCE THE SUBMITTED FOUNDATION PLANS DOES NOT HAVE
 APPROVAL THE FOLLOWING ITEMS MAY STILL HAVE ISSUES ONCE
 5A & 5B ARE RESUBMITTED THESE ITEMS WILL BE REVIEWED
 AGAIN FOR CODE COMPLIANCE. PLEASE PROVIDE AN ACCESSIBLE
 RAMP MEETING THE FOLLOWING REQUIREMENTS:
  
 7A) 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE
 SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A
 RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM
 RISE FOR RUN SHALL BE 30" (SEE FIGURE 16).
  
 11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH OF A
 RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE LESS THAN 44
 INCHES WIDE.
  
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARENCE.
  
 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT LANDINGS, THE
 MINIMUM LANDING SIZE SHALL BE 60" X 60".
  
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7B) PLEASE PROVIDE DESIGN CRITERIA FOR STAIRS,
 HANDRAILS AND GUARDRAILS, 11-4.8/ 11-4.8. & 1607.7.
  
 7C)COMPLIED.
  
 8) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 9A) SLIDDING GLASS DOORS- SITE INSTALLED
  
 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) COMPLIED.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) INSPEAKING WITH ROBERT LORENZO FROM DCA ABOUT THE
 STATE APPROVED PLAN FROM PRECISION HOMES, PLAN #
 2056-1552F MR LORENZO COULD NOT FIND THIS PLAN ON THEIR
 LIST OF APPROVED PLANS. MR LORENZO PROVIDED US WITH THE
 THIRD PARTY HILBORN WERNER CARTER AND ASSOCIATES
 ADMINISTRATOR SCOTT FRANCIS. MR FRANCIS INDICATED THESE
 ARE NOT STATE APPROVED AS OF TODAY. I ALSO SPOKE ABOUT
 ISSUES WE SEE WITH
 WINDOW TYPE "B" NOA LISTED AS SMALL MISSILE IMPACT,
 WINDOW TYPE C& D REQUIRE MULLIONS WHICH ARE NOT LISTED,
 DOOR TYPE 3 & 8 NOT HAVING WATER INFILTRATION TEST AND
 NO ROOFING INFORMATION, PRODUCT APPROVALS.
 MR FRANCIS INDICATED THEY WOULD CORRECT THE PLANS WHILE
 ALSO WAITING FOR THE FINAL VERSION OF TRUSS DRAWINGS
 AND NOT TO ISSUE THESE PLANS SINCE THERE IS NO STATE
 APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By jwitmer Date 2008-08-20 Time 07:34 Rev Time 2.22
Received By jwitmer Date 2008-08-20 Time 07:34 Sent To  
Notes
2008-08-20 09:39:44BUILDING PLAN REVIEW
 PERMIT: 08070817
 ADD: 4200 N FLAGLER DR
 CONT: PREMIER MODULAR BUILDING LC
 TEL: (407)467-2189
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THE SUBMITTED PLANS FOR A MODULAR BUILDING DO NOT
 CONTAIN THE THIRD PARTY AGENCY STAMP INDICATING THE
 PLANS HAVE BEEN REVIEWED AND MEET THE 2004 FBC AND THE
 MANUFACTURED (MODULAR) BUILDING PROGRAM UNDER THE
 JURISDICTION OF THE DEPARTMENET OF COMMUNITY AFFAIRS
 (DCA). RULE 9B-1 OF THE FLORIDA ADMINISTRATIVE CODE.
  
 3) MINIMUM PLAN REVIEW REQUIREMENTS OF 106.3.5.1.1 SITE
 REQUIREMENTS, WILL REQUIRE A SITE PLAN FOR
 3A) PARKING
 3B) ACCESSIBLE PARKING SPACE 11-4.6
 3C) ACCESSIBLE ROUTE 11-41.3 (1)
 3D) FBC 2004 TABLE 602 & TABLE 704.8.
 3E) WITH NOT HAVING THE LOCATION OF STRUCTURE THIS MAY
 BE CONSIDERED A "C" ZONE, 2004 FBC/ 2007 SUPPLEMENETS,
 1609.4 "C" TYPE ZONE EXPOSURES
  
 4) PLEASE PROVIDE SOILS REPORT PROVIDING THE MINIMUM
 SAFE BEARING VALUE OF THE SOILS. 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) BUILDING PROVISO: THIS STRUCTURE IS LOCATED IN A A-5
 FLOOD ZONE, FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 6) FOUNDATION SYSTEMS, SHEET FD-1 NEITHER THE PLANS NOR
 THE PERMIT APPLICATION PROJECT DETAILS INDICATE THE
 LENGTH OF TIME THIS STRUCTURE IS TO BE ISSUED A C.O.
 FORE. IF THIS IS A TEMPORARY STRUCTURE OR PERMANENT
 STRUCTURE, SEE DEFINITIONS FOR TEMPORARY BUT SHALL NOT
 BE PERMITTED FOR MORE THAN 180 DAYS. THE BUILDING
 OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR
 DEMONSTRATED CAUSE. IF THIS IS TO BE A TEMPORARY
 STRUCTURE THE INFORMATION LISTED IN 6A-B WILL BE
 REQUIRED.
  
 6A) SHEET FD-1 IS A SITE SPECIFIC FOUNDATION ENGINEERED
 SHEET, REQUIRED TO HAVE THE SITE LOCATION INFORMATION
 IN THE TITLEBLOCK. 106.1.1 CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF WORK PROPOSED UNDERTHIS PERMIT.
  
 6B) SHEET FD-1 PLEASE INDICATE WHICH TYPE OF PIER
 SYSTEM WILL BE USED AND IF IT IS THE ALTERNATE SYSTEM.
 PLEASE SPECIFY IF THE PIERS ARE TO BE FILLED CELL WITH
 CONCRETE OR TYPE M OR S MORTAR OR HOLLOW
 CONCRETE MASONARY UNIT. PLEASE SEE 1805.5.7 (3) (3.2)
 EXCEPTION: 4 TIMES THE LEAST DIMENSION AND DESIGNS
 EMPLOYING LATERAL BEARINGWILL BE REQUIRED.
  
 6C) IF THE DECISION FOR A PERMANENT STRUCTURE IS
 PROVIDED THEN THE REQUIREMENTS FOR A PERMANENT
 FOUNDATION SHALL BE MET:
 6C) (1) 1805.2 DEPTH OF FOUNDATION
 6C)(2) 1816.1 TRMITE TREATMENT
 6C)(3) 1209.1 CRAWL SPACE AND REQUIRED OPENING 6C)(4)
 1203.3.1 OPENINGS FOR UNDER-FLOOR VENTILATION 6C)(5)
 THE FOUNDATION IS DESIGNED FOR AN B EXPOSURE WHILE THE
 BUILDING IS DESIGNED FOR A C EXPOSURE AND LOCATED IN A
 C ZONE.1609.4.
  
 7) SINCE THE SUBMITTED PLANS DON NOT HAVE STATE
 APPROVAL THROUGH THE DCA FOR MODULAR BUILDINGS A
 THROUGH REVIEW OF THE PLANS WILL BE REQUIRED. PLEASE
 PROVIDE AN ACCESSIBLE RAMP MEETING THE FOLLOWING
 REQUIREMENTS:
  
 7A) 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE
 SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A
 RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM
 RISE FOR RUN SHALL BE 30" (SEE FIGURE 16).
  
 11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH OF A
 RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE LESS THAN 44
 INCHES WIDE.
  
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARENCE.
  
 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT LANDINGS, THE
 MINIMUM LANDING SIZE SHALL BE 60" X 60".
  
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN
 IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7B) PLEASE PROVIDE DESIGN CRITERIA FOR STAIRS,
 HANDRAILS AND GUARDRAILS, 11-4.8/ 11-4.8. & 1607.7.
  
 7C) WALL SECTIONS THROUGH PROVIDING A CONTINIOUS LOAD
 PATH 1609.6.2.1 MAIN WIND-FORCE RESISTING SYSTEM.
  
 8) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 9A) FIXED WINDOWS NOA 08-0429.10 MISSILE IMPACT RATING:
 NONE
 9B) MULLIONS
 9C) SWING EXTERIOR DOORS
 9D) SLIDDING GLASS DOORS
 9E) LOUVER
 9F) HARDIPLANK SIDING
 9G) STORM SHUTTERS - NON-IMPACT WINDOWS PROVIDE STORM
 PANEL INFORMATION WITH INSTALLATION SCHEDULE AND KEY
 PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING. FBC 1606.1.4.
 9H) ROOFING ASSEMBLIES
  
  
 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) ENERGY CALCULATIONS ARE MISSING THE INPUT DATA
 REPORT, CODE COMPLIANCE CAN NOT BE CHECKED WITHOUT THE
 INPUT DATA REPORT.13-415.2.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 10:05 Sent To  
Notes
2008-10-21 10:07:01SEPARATE PERMIT FOR THE ELECTRICAL SERVCIE FEEDING THE
 BUILDINGS.
  
 *** NO CHANGES ARE PERMITTED TO THE BASE BUILDING
 INCLUDING LOW VOLTAGE WILL VOID THE STATE APPROVAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 11:57 Sent To  
Notes
2008-09-30 11:57:34 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE VERSION OF THE SUBMITTED ENERGY
 CALCULATIONS IS NOT CORRECT. PLEASE SEE 13-400.3.A AS
 THE VERSION ADOPTED BY THE FLORIDA BUILDING CODE IS
 2.5. THE SUBMITTED IS VERSION 3.0. PLEASE KNOW IT IS
 THE UNDERSTANDING OF THIS OFFICE THAT A FREE PATCH IS
 AVAILABLE ON ENERGY GAUGE WEBSITE TO CHANGE TO VERSION
 2.5.
 ** PLEASE ALSO SEE THE COUNT OF FIXTURES IN THE INPUT
 DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS IS NOT
 POSSIBLE AS EACH TYPE IS SHOWN AS ONE FIXTURE. PLEASE
 SEE THE PLANS HAVE NUMEROUS FIXTURES NOT ONLY ONE IS
 EACH LOCATION/ZONE/SPACE.
 PLEASE BE SURE TO SEE 13-415.2.,13-415.2.ABC.1.1,.1.2
 AND .1.3.
 PLEASE ALSO SEE THE EXTERIOR LIGHTING AS THE SUBMITTED
 INPUT DATA REPORT ONLY INDICATES A TOTAL OF FIVE
 FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS
 SUBMITTED. THE PLANS SHOW A SUBSTANTIALLY HIGHER NUMBER
 OF FIXTURES. THE WATTAGE OF EACH OF THESE FIXTURES IS
 ALSO NOT THE SAME AS SHOWN ON THE IDR. THE IDR SHOWS A
 TOTAL OF 60WATTS, YET THE PLANS INDICATE 100WATT
 FIXTURES.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURE SON PLANS
 WITH THE INPUT DATA REPORT FOR TYPES, WATTAGES, NUMBER
 OF FIXTURES ETC.
 ** PLEASE SEE THE JURISDICTION IS NOT CORRECT. THE
 APPLICATION IS LOCATED IN THE CITY OF WEST PALM BEACH
  
 2) NOTE: IF PLANS HAVE A * STATE APPROVAL* PLEASE BE
 SURE ALL PLANS CONTAIN THE STATE STAMPS. THE ELECTRICAL
 PLANS AS SUBMITTED DO NOT CONTAIN ANY STAMPS FROM ANY
 OF THE LISTED REVIEWERS.
  
 3) NOTE: PLEASE SEE THE PACKAGE DOES INCLUDE ANY
 ELECTRICAL RISER FOR SERVICE TO CONNECTION OF
 ELECTRICAL SERVICE OR EQUIPMENT.
 230.70.230.71.230.72.230.76,230.79, 250.50, 215.5, 545
 ETC
 FBC 106.1.1,106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE OR
 SPECIFIC AS REQUIRED PER 408.4 OF THE 2005 NFPA-70.
 PLEASE SEE COMMENTARY UNDER THE NEC SECTION GIVEN AS
 LISTING *LIGHTING* OR *RECEPTACLES* IN LIEU OF SPECIFIC
 ROOMS OR LOCATIONS IS NOT ACCEPTABLE.
  
 5) NOTE: PLEASE SEE FBC 13-413.2.ABC.2.1 AND2.2 FOR
 MISSING NOTES REQUIRED ON PLANS.
  
 6) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1 AND .1.2 FOR
 MISSING VOLTAGE DROP CALCULATIONS FOR WORST CASE
 SCENARIO.
  
 7) NOTE: PLANS INDICATE SOME SORT OF NOTES FOR HORNS
 AND STROBES HOWEVER THERE IS NOT INDICATION OR SHOWN
 DESIGN MEETING MINIMUM LEVELS AND LOCATIONS FOR FBC
 11-4.28.1,.2 AND .3 FOR ADA COMPLIANCE.
 PLEASE COMPLETE PLANS AND MINIMUM DEVICE LOCATIONS,
 HEIGHTS, AND LEVELS FOR MINIMUM CODE COMPLIANCE.
  
 8) NOTE: AS SOME INFORMATION HAS NOT BEEN SUBMITTED OR
 SHOWN AT THIS TIME THERE MAY VERY WELL BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME. BASED ON PLANS SUBMITTED A REVIEW WAS DONE AS
 PLANS DID NOT CONTAIN STAMPS. IN EITHER CASE PLANS ARE
 STILL REQUIRED TO MEET MINIMUM CODE DESIGN AND
 COMPLIANCE PER FBC AND OTHER ADOPTED CODES PER FS
 553.73.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By dpalmer Date 2008-08-13 Time 16:19 Rev Time 0.00
Received By dpalmer Date 2008-08-13 Time 16:19 Sent To  
Notes
2008-08-13 16:19:35 
  
 ** NO STATE APPROVAL OR STAMPS ON PLANS.
  
  
 **DENIED**
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE ENERGY CODE IS
 NOT MET. PLEASE SEE THE CERTIFICATION SHEETS IN BOTH
 SETS ARE NOT ORIGINAL. IN FACT THEY DO NOT CONTAIN A
 SIGNATURE, DATE, OR SEAL FROM THE LISTING DESIGN
 PROFESSIONAL AS REQUIRED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002, FBC 13-103.1.
  
 2) NOTE: PLANS SUBMITTED ARE NOT COMPLETE, NO RISER
 DIAGRAM, NO GROUNDING, NO SERVICE ENTRANCE CONDUCTORS,
 NO FEEDERS, NO AIC RATINGS, NO LOAD CALCULATIONS ETC
 230.70,230.71,230.72,215.5,215.3,240.4,310.16,408.4,220
 ETC.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE INCOMPLETE. PLEASE SEE PAGE TWO WHICH SPECIFICALLY
 STATES THE INPUT DATA REPORT SHALL ACCOMPANY THE
 CALCULATIONS.
 AS THESE ARE NOT COMPLETE AT THIS TIME, NO VERIFICATION
 OF CODE COMPLIANCE CAN BE DONE.
 PLEASE SEE ADDRESS IS NOT COMPLETE.
 PLEASE SEE JURISDICTION IS NOT CORRECT.
 PLEASE SEE INFORMATION FOR MOST OTHER ITEMS ON COVER
 SHEET ARE ALSO NOT COMPLETE.
  
 ** PLEASE BE SURE TO SEE 13-415.2,
 13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. NO
 COMPLIANCE FOR ADA DEVICES IS SHOWN ON PLANS.
 BASE PLANS ARE REQUIRED TO SHOW AT LEAST THE MINIMUM
 FOR CODE COMPLIANCE.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 CONTROLS FOR EXTERIOR LIGHTS. STATING *TIMER* ON PLANS
 DOES NOT SHOW MINIMUM.
  
 6) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING, ALL
 DESIGNATIONS ON PLANS AND COORDINATE WITH PANEL
 SCHEDULES, FIXTURE LEGEND.
 FBC 106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY .
 NEC 2005, FBC 2004W/2007 REVS.
  
 *** AS THERE IS MUCH INFORMATION NOT YET SUBMITTED
 THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-10-20 Cont ID  
Sent By   Date 2008-10-20 Time 9:15 Rev Time 1.00
Received By   Date 2008-10-20 Time 8:15 Sent To  
Notes
2008-10-20 08:55:52PASSED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-09-19 Cont ID  
Sent By rchokshi Date 2008-09-19 Time 11:08 Rev Time 0.00
Received By rchokshi Date 2008-09-19 Time 10:49 Sent To  
Notes
2008-09-19 11:07:43FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE SILT FENCE AROUND THE
 WHOLE SITE, & TURBIDITY AROUND CATCH BASINS, WATER
 FALLS, LAKE, CANAL IF YOU HAVE THEM DURING CONSTRUCTION
 AND ALL DEMOLITION PHASE. HEIGHT OF FENCE SHOULD BE
 HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25,50,100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 5. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH REPORT &
 STORM WATER QUALITY CALCULATIONS TO 1000 45TH STREET
 FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT.
  
  
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL WITH REFERENCE
 DRAWINGS TO EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By rchokshi Date 2008-08-22 Time 14:48 Rev Time 0.00
Received By rchokshi Date 2008-08-22 Time 14:42 Sent To  
Notes
2008-08-22 14:48:35FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OFPOLLUTION PREVENTION . PLEASE
 SHOW ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE,
 & TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE.HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS TO 1000
 45TH STREET FOR THEIR APPROVAL BEFORE WE ISSUE A
 PERMIT.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL WITH REFERENCE
 DRAWINGSTO EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-30 Cont ID  
Sent By mwennerg Date 2008-09-30 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2008-09-30 Time 15:37 Sent To  
Notes
2008-09-30 15:37:25***DENIED***
  
 1) PLEASE SEE NEW COMMENT. (1A)
  
 2) WHERE RAMPS ARE PROVIDED, WORK TO COMPLY WITH
 APPLICABLE BUILDING CODES AND NFPA 101, SEC. 7.2.5.
  
 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 4) ADDRESS REQUIRED ON ALL BUILDINGS THAT SHALL BE
 MINIMUM 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND.
  
 5) PLEASE PROVIDED DISTANCE FROM BUILDING TO CLOSEST
 FIRE HYDRANT.
  
 NEW COMMENTS:
  
 1A) SHEET E1 INDICATES MANUEL PULL STATIONS AND HORNS
 BUT NO VISUAL APPLIANCES. PLEASE ADD TO DRAWINGS AND
 ELECTRICAL SYMBOLS.
  
 6) EXIT SIGNS APPEAR TO BE COMBINATION TYPE WITH
 EMERGENCY LIGHTING BUT NOT SHOWN UNDER ELECTRICAL
 SYMBOLS FOR VERIFICATION.
  
 7) IF A FIRE ALARM SYSTEM IS PART OF THIS PROJECT,
 PLEASE SHOW ALL EQUIPMENT INCLUDING THE FIRE ALARM
 CONTROL PANEL.
  
 8) VERIFY THE LOCATIONS OF EMERGENCY LIGHTING
 FACILITIES ON SHEET E2.
  
 9) OCCUPANT LOAD SIGN WILL BE REQUIRED AT TIME OF FINAL
 INSPECTION. CONTACT BUREAU OF FIRE PREVENTION AT (561)
 804-4724 FOR ASSISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-26 Cont ID  
Sent By mwennerg Date 2008-08-26 Time 13:54 Rev Time 0.00
Received By mwennerg Date 2008-08-26 Time 13:54 Sent To  
Notes
2008-08-26 13:59:57***DENIED***
  
 1) PLANS INDICATE A FIRE ALARM SYSTEM ON SHEET CV AND
 SHEET EV1 BUT NO EQUIPMENT IS ILLUSTRATED ON DRAWINGS
 OR UNDER ELECTRICAL SYMBOLS. ADDITIONALLY, SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION.
  
 2) WHERE RAMPS ARE PROVIDED, WORK TO COMPLY WITH
 APPLICABLE BUILDING CODES AND NFPA 101, SEC. 7.2.5.
  
 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 4) ADDRESS REQUIRED ON ALL BUILDINGS THAT SHALL BE
 MINIMUM 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND.
  
 5) PLEASE PROVIDED DISTANCE FROM BUILDING TO CLOSEST
 FIRE HYDRANT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 08:53 Sent To M
Notes
2008-10-24 08:54:31TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 14:24 Sent To M
Notes
2008-10-22 14:24:25TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-06 Cont ID  
Sent By shill Date 2008-10-06 Time 16:28 Rev Time 0.00
Received By shill Date 2008-10-06 Time 16:27 Sent To  
Notes
2008-10-06 16:32:58TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-09 Cont ID  
Sent By adarroug Date 2008-09-09 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-09-09 Time 09:06 Sent To  
Notes
2008-09-09 09:06:34TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-26 Cont ID  
Sent By mwennerg Date 2008-08-26 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2008-07-30 Time 16:19 Sent To  
Notes
2008-07-30 16:22:22TO "COMM" BD#54

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-11-08 Cont ID  
Sent By rregueir Date 2008-11-08 Time 15:36 Rev Time 0.00
Received By rregueir Date 2008-11-08 Time 15:36 Sent To PC
Notes
2008-11-08 15:37:20MECH DETAIL FOR CU ATTACHMENT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By rregueir Date 2008-10-22 Time 15:18 Rev Time 0.00
Received By rregueir Date 2008-10-22 Time 15:11 Sent To PC
Notes
2008-11-08 15:39:10CONDITIONS OF PROVISO SATISFIED FOR PLAN REVIEW.
2008-10-22 15:18:39***************PROVISO*******************
 DETAIL FOR INSTALLATION OF OUTDOOR CONDENSING UNITS HAS
 BEEN SUBMITTED. THE DETAIL IS NTO SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. PROVIDE SIGNED AND SEALED
 DETAIL FOR PLAN REVIEW PRIOR TO MECHANICAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-09-29 Cont ID  
Sent By rregueir Date 2008-09-29 Time 10:09 Rev Time 0.00
Received By rregueir Date 2008-09-29 Time 08:51 Sent To  
Notes
2008-09-29 10:09:11***NOTE***
  
 SUBMIT A SEPARATE PLAN AND PERMIT APPLICATION FOR THE
 SITE INSTALLED MECHANICAL COMPONENTS. PLANS INDICATE
 THIS WORK IS TO BE PERFORMED BY "OTHERS."
  
 PREVIOUS REVIEW COMMENTS HAVE NOT BEEN ADDRESSED.
 HOWEVER, AS OF 9/26/08, THIS PLAN IS APPROVED AND
 LISTED ON THE DCA WEBSITE UNDER PLAN #: 2056-1552F.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By rregueir Date 2008-08-21 Time 11:04 Rev Time 0.00
Received By rregueir Date 2008-08-20 Time 15:29 Sent To  
Notes
2008-08-21 11:04:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THESE PLANS ARE FOR A MODULAR BUILDING. HOWEVER,
 THERE IS NO INDICATION ON PLANS THAT THEY HAVE BEEN
 SUBMITTED UNDER THE DCA MODULAR BUILDING PROGRAM
 ESTABLISHED UNDER F.S. 553. THEREFORE, THESE PLANS MUST
 BE REVIEWED FOR THE REQUIREMENTS OF NEW SITE-BUILT
 CONSTRUCTION IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE.
  
 2. SHOW THE SIZES OF ALL SUPPLY AND RETURN AIR DUCTS AS
 WELL AS THE CFM BEING SUPPLIED OR RETURNED AT EACH
 REGISTER, GRILL OR DIFFUSER. AN AIR DISTRIBUTION SYSTEM
 SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1. SHOW
 BALANCED RETURN AIR IN ACCORDANCE WITH FBCM 601.4.
  
 3. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 4. SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION. A SECONDARY DRAIN OR AUXILIARY DRAIN PAN
 SHALL BE REQUIRED FOR EACH COOLING OR EVAPORATOR COIL
 WHERE DAMAGE TO ANY BUILDING COMPONENTS WILL OCCUR AS A
 RESULT OF OVERFLOW FROM THE EQUIPMENT DRAIN PAN OR
 STOPPAGE IN THE CONDENSATE DRAIN PIPING IN ACCORDANCE
 WITH FBCM 307.2.3.
  
 5. PROVIDE OUTSIDE AIR CALCULATIONS SHOWING THE
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, OUTSIDE AIR
 PROVIDED AND OUTSIDE AIR REQUIRED FOR EACH SPACE OF THE
 BUILDING IN ACCORDANCE WITH FBCM 403.3.
  
 6. PROVIDE A COMPLETE EQUIPMENT SCHEDULE FOR A/C AND
 EXHAUST EQUIPMENT WHICH SHOWS ALL REQUIRED NAMEPLATE
 INFORMATION, ENERGY EFFICIENCY RATING OF THE APPLIANCES
 AND AIR MOVED (IN CFM) IN ACCORDANCE WITH FBCM 301.2,
 301.6, 403.3, 601.4, 603.1.
  
 7. PROVIDE AN AIR BALANCE SCHEDULE SHOWING THE SPACE TO
 BE PRESSURIZED WITH RESPECT TO THE OUTDOORS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.2
  
 8. SHOW THE SIZE AND LOCATION OF ALL OUTSIDE AIR AND
 EXHAUST OPENINGS IN THE EXTERIOR OF THE BUILDING TO
 DEMONSTRATE COMPLIANCE WITH FBCM 401.5 AND 401.6. A
 SITE PLAN IS ALSO REQUIRED TO DETERMINE COMPLIANCE WITH
 THESE SECTIONS.
  
 9. SHEET MP HAS A HAND-WRITTEN NOTE INDICATING A
 "SCREENED AUTOMATIC LOUVER." WHAT IS THE PURPOSE OF
 THIS LOUVER? HOW AND WHY IS IT AUTOMATED? WHAT TYPE OF
 LOUVER IS BEING USED? LOUVERS ARE CLASSIFIED AS PANEL
 WALLS IN ACCORDANCE WITH FAC RULE 9B-72. PROVIDE
 PRODUCT APPROVAL FOR ALL OUTDOOR LOUVERS IN ACCORDANCE
 WITH THIS RULE AND FBCB SECTION 1609. ALSO, PLANS SHALL
 NOT BE MODIFIED OR AMENDED BY HAND OR BY ANYONE OTHER
 THAN THE DESIGNER OF RECORD IN ACCORDANCE WITH F.S. 471
 AND FAC RULE 61G15.
  
 10. WHAT TYPE OF MATERIALS ARE THE A/C CLOSET LOUVERED
 DOORS CONSTRUCTED? THESE A/C CLOSETS APPEAR TO BE
 DESIGNED TO FUNCTION AS RETURN AIR PLENUMS. MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 11. NO INFORMATION COULD BE FOUND ON PLANS REGARDING
 THE INSTALLATION OF THE OUTDOOR CONDENSING UNITS.
 PROVIDE INSTALLATION DETAILS AS WELL AS LOCATIONS ON
 PLANS SHOWING COMPLIANCE WITH FBCM 301.13 FOR WIND
 RESISTANCE, SECTIONS 303, 304 AND 306.
  
 12. IF THE AIR HANDLERS ARE CAPABLE OF PRODUCING MORE
 THAN 2,000 CFM, COMPLIANCE WITH FBCM 606.2 IS REQUIRED.
 SHOW COMPLIANCE BY PROVIDING SMOKE DETECTORS WITH
 AUDIBLE AND VISIBLE NOTIFICATION DEVICES OR PROVIDE
 MANUFACTURER'S SUBMITTAL DATA SHOWING THESE UNITS ARE
 NOT CAPABLE OF PRODUCING MORE THAN 2,000 CFM.
  
 13. THE ENERGY CODE COMPLIANCE FORM SHALL BE SIGNED AND
 SEALED BY THE PREPARER IN ACCORDANCE WITH FBCB
 13-103.1.1 AND FBCB 13-103.2.
  
 14. PAGE 2 OF THE ENERGY CODE COMPLIANCE FORM REQUIRES
 THAT THE INPUT REPORT BE SUBMITTED WITH THE COMPLIANCE
 REPORT. SEE "IMPORTANT NOTE" ON THAT PAGE. NO SUCH
 REPORT WAS PROVIDED. THE ENERGY CALCULATIONS CAN NOT BE
 REVIEWED WITHOUT THE INPUT REPORT AND THEREFORE ARE NOT
 BEING REVIEWED AT THIS TIME.
  
 15. COOLING LOAD CALCULATIONS SHALL BE PROVIDED AND
 APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCB 13-407.1 ABC.1.
  
 16. NOTE: PLEASE BE AWARE THAT DUE TO THE LARGE AMOUNT
 OF MISSING INFORMATION, THAT A THOROUGH REVIEW OF THE
 PLANS CAN NOT BE PERFORMED AT THIS TIME. NEW COMMENTS
 ARE LIKELY ONCE PLANS ARE RESUBMITTED WITH MORE
 COMPLETE INFORMATION. IT IS NOT POSSIBLE TO MAKE A
 COMPLETE LIST OF ALL MISSING ITEMS AND POSSIBLE CODE
 VIOLATIONS.
  
 17. NOTE: AS THIS PLAN WAS NOT SUBMITTED UNDER THE DCA
 MODULAR BUILDING PROGRAM, THIS MODULAR BUILDING MAY NOT
 BE DELIVERED WITH ANY ELEMENTS OF "CLOSED
 CONSTRUCTION." ALL STRUCTURAL, BUILDING ENVELOPE,
 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS AND
 COMPONENTS MUST REMAIN EXPOSED FOR COMPLETE ROUGH
 INSPECTIONS AS REQUIRED IN ACCORDANCE WITH FBCB SECTION
 109. ANY PORTIONS THAT DO NOT COMPLY WITH THE
 REQUIREMENTS OF THE CODE SHALL BE CORRECTED AND SUCH
 PORTION SHALL NOT BE COVERED OR CONCEALED UNTIL
 AUTHORIZED BY THE BUILDING OFFICIAL IN ACCORDANCE WITH
 FBCB 109.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status N Date 2008-10-22 Cont ID  
Sent By kstevens Date 2008-10-22 Time 10:16 Rev Time 0.00
Received By kstevens Date 2008-10-22 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By kstevens Date 2008-09-10 Time 14:14 Rev Time 0.00
Received By kstevens Date 2008-09-10 Time 12:41 Sent To  
Notes
2008-09-10 14:17:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SITE PLAN OR SURVEY IS REQUIRED. SHOW THE LOCATION
 OF THE WATER SOURCE, (METER), RPZV BACKFLOW, SEWER
 LATERAL, BUILDING SEWER & WATER SERVICE. SECTION
 106.1.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. ALSO SHOW THE
 LOCATION OF THE MODULAR BUILDING ON THE SITE PLAN.
  
 2. N/A
 3. N/A
 4. N/A
 5. N/A
 6. N/A
 7. N/A
 8. N/A
 9. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-06 Cont ID  
Sent By kstevens Date 2008-08-06 Time 09:54 Rev Time 0.00
Received By kstevens Date 2008-08-06 Time 09:54 Sent To  
Notes
2008-08-06 10:56:57DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. A SITE PLAN OR SURVEY IS REQUIRED. SHOW THE LOCATION
 OF THE WATER SOURCE, (METER), RPZV BACKFLOW, SEWER
 LATERAL, BUILDING SEWER & WATER SERVICE. SECTION
 106.1.2.
  
 2. INDICATE THE OCCUPANCY OF THE BUILDING. SECTION
 106.3.5.1.1(2). THIS WILL DETERMINE THE REQUIRED
 FIXTURES. TABLES 1004.1.2 & 403.1.
  
 3. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.6 DISPENSERS
 ___FOR URINALS
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ___FOR STALLS
 A. 11-4.17.3 (FIG. 30E) - SHOWN AS 5'11" WIDE. AS
 CONFIGURED A MINIMUM 7'1" WIDTH IS REQUIRED FOR THE
 ACCESSIBLE STALL.
  
 4. SHT FP1 INDICATE THE WATER CLOSETS TO BE 1'6" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28),
 AND THE LAV TO THE MIN. 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30"
 WIDTH OF THE REQUIRED CLEAR FLOOR SPACE.
  
 5. SUBMIT A DETAIL FOR THE SINK IN THE UTILITY ROOM.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH IS
 REQUIRED. CABINET DOORS ARE NOT APPROVED IN THE CLEAR
 FLOOR SPACE.
  
 6. SHT FP2 SUBMIT A HORIZONTAL BUILDING DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES, CLEANOUTS &
 INDICATED THE DRAINAGE FIXTURE UNITS AS THEY ACCUMULATE
 IN THE SYSTEM. SECTIONS 106.3.5.1.3 , 708 & 709.1.
  
 7. SHT FP2 NO RISER SUBMITTED FOR THE DRINKING
 FOUNTAINS. PLEASE SUBMIT. SECTION 106.3.5.1.3.
  
 8. SHT FP2 WATER SUPPLY RISER DIAGRAM. WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE ICE MACHINE AND AT EACH
 REF. SECTION 604.9. -- A FULL OPEN VALVE IS REQUIRED ON
 THE SUPPLY LINE TO THE WATER HEATER. SECTION 606.1(7).
 -- A FULL OPEN VALVE IS REQUIRED ON THE WATER
 DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE TO THE
 BUILDING. SECTION 606.1(2). -- SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO THE HOSE BIBBS. SECTION
 606.2(2).
  
 9. SHT FP2 RISER FOR THE SINKS IS MISLABELED AS LAVS
 AND DOES NOT REFLECT THE FLOOR PLAN. SINKS ARE ON
 DIFFERENT SIDES OF THE WALL. RISER SHOWS THEM ON THE
 SAME SIDE OF THE WALL. PLEASE CORRELATE. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-14 Cont ID  
Sent By jroach Date 2008-10-14 Time 21:08 Rev Time 0.00
Received By jroach Date 2008-10-14 Time 21:08 Sent To  
Notes
2008-10-14 21:09:06***PROVISOS***
  
 1) THIS APPROVAL IS ONLY VALID FOR THE INSTALLATION OF
 THE MODULAR BUILDING.
  
 2) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING, THE FOLLOWING ITEMS SHALL BE
 COMPLETED:
  
 2A) ALL SITE WORK (PERMIT #08080158) INCLUDING
 LANDSCAPING, SHALL BE INSTALLED. A LANDSCAPE INSPECTION
 SHALL BE REQUESTED AND PASSED BY THE CITY'S LANDSCAPE
 PLANNER (ROBERT KUSSNER).
  
 2B) PURSUANT TO A MEETING WITH THE OWNER ON SEPTEMBER
 22, 2008, AN ON-SITE INSPECTION SHALL BE SCHEDULED WITH
 THE PROJECT PLANNER (JOHN ROACH) BY THE OWNER AND/OR
 CONTRACTOR. SUCH INSPECTION SHALL INCLUDE THE AESTHETIC
 APPEARANCE OF THE STRUCTURE, INCLUDING ITS
 COMPATIBILITY WITH THE REMAINDER OF THE DEVELOPMENT AND
 THE ADJACENT PROPERTIES. ANY IMPROVEMENTS REQUIRED AS
 PART OF THIS INSPECTION SHALL BE COMPLETED IN
 ACCORDANCE WITH A AGREED-UPON SCHEDULE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By jroach Date 2008-09-24 Time 20:14 Rev Time 0.00
Received By jroach Date 2008-09-24 Time 20:14 Sent To  
Notes
2008-09-24 20:23:11***PROVISOS***
  
 1) THIS ZONING APPROVAL IS ONLY VALID FOR THE
 INSTALLATION OF THE MODULAR BUILDING.
  
 2) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING, THE FOLLOWING ITEMS SHALL BE
 COMPLETED:
  
 2A) ALL SITE WORK, AS APPROVED BY PERMIT #08080158,
 INCLUDING LANDSCAPING, SHALL BE INSTALLED. A LANDSCAPE
 INSPECTION SHALL BE REQUESTED AND PASSED BY THE CITY'S
 LANDSCAPE PLANNER (ROBERT KUSSNER).
  
 2B) PURSUANT TO A MEETING WITH THE OWNER ON SEPTEMBER
 22, 2008, AN ON-SITE INSPECTION SHALL BE SCHEDULED WITH
 THE PROJECT PLANNER (JOHN ROACH) BY THE OWNER AND/OR
 CONTRACTOR. SUCH INSPECTION SHALL INCLUDE THE AESTHETIC
 APPEARANCE OF THE STRUCTURE, INCLUDING ITS
 COMPATIBILITY WITH THE REMAINDER OF THE DEVELOPMENT AND
 THE ADJACENT PROPERTIES. ANY IMPROVEMENTS REQUIRED AS
 PART OF THIS INSPECTION SHALL BE COMPLETED IN
 ACCORDANCE WITH A AGREED-UPON SCHEDULE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By jroach Date 2008-08-08 Time 13:53 Rev Time 0.00
Received By jroach Date 2008-08-08 Time 13:53 Sent To  
Notes
2008-08-08 14:06:57***FAILED***
  
 1) TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED
 SHOWING THE LOCATION OF THE PROPOSED MODULAR
 BUILDINGS.
  
 2) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE
 PROVIDED.
  
 3) AS THE PROPERTY IS LOCATED WITH A PLANNED
 DEVELOPMENT (PD), ADDITIONAL ARCHITECTURAL ELEMENTS
 SHALL BE PROVIDED ON THE ELEVATION TO ENSURE THAT THE
 DESIGN IS CONSISTENT WITH THE REMAINDER OF DEVELOPMENT,
 AS WELL AS PRESENTS A AESTHETIC APPEARACE TO/FROM
 ADJACENT PROPERTIES.THE ELEVATIONS APPEAR TO BE
 NOTHING LIKE WHAT WAS SUBMITTED AS A CONCEPTUAL DURING
 THE SITE PLAN REVIEW PROCESS.PLEASE PROVIDE
 ADDITIONAL ARCHITECTURAL FEATURES AND DESIGN ELEMENTS
 TO IMPROVE THE ARCHITECTURE OF THE BUILDING.
  
 4) FYI....THE PERMIT FOR THE MODULAR BUILDINGS WILL BE
 SUBJECT TO THE ISSUANCE OF A PERMIT FOR THE REMAINDER
 OF THE SITE IMPROVEMENTS (I.E. PARKING LOT,
 LANDSCAPING, ETC.).NO CERTIFICATE OF OCCUPANCY (CO)
 WILL BE ISSUED UNTIL THESE IMPROVEMENTS ARE INSTALLED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.