Plan Review Details - Permit 08070815
Plan Review Stops For Permit 08070815
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-29 Cont ID  
Sent By tgordon Date 2008-07-29 Time 16:09 Rev Time 0.00
Received By tgordon Date 2008-07-29 Time 16:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-01 Cont ID  
Sent By tgordon Date 2008-08-01 Time 14:39 Rev Time 0.40
Received By tgordon Date 2008-08-01 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By tgordon Date 2008-07-30 Time 14:09 Rev Time 0.30
Received By tgordon Date 2008-07-30 Time 14:09 Sent To  
Notes
2008-07-30 14:30:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE HOOD EXHAUST FAN BEING INSTALLED IS 2,175 CFM'S,
 THE BUILDING MAKE UP AND OUTDOOR AIR IS 1,510 CFM'S,
 THIS WOULD PUT THE BUILDING AT A NEGATIVE PRESSURE. PER
 2004 FBC 13-409.1.ABC.2 BUILDING PRESSURES. MECHANICAL
 SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE
 PRESSURIZED WITH RESPECT TO OUTDOORS. PLEASE HAVE THE
 BUILDING PLANS ENGINEER MARTIN WHITELOCKE REVIEW THE
 HOOD INFORMATION AND REVISE MECHANICAL PLAN 1 OF 1 SO
 THE BUILDING WILL NOT BE AT A NEGATIVE PRESSURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By tgordon Date 2008-07-29 Time 16:09 Rev Time 0.30
Received By tgordon Date 2008-07-29 Time 16:09 Sent To  
Notes
2008-07-29 16:22:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A PLAN SHOWING THE DUCT WORK FROM THE
 HOOD TO THE EXHAUST FAN, LISTING THE SIZES AND
 MATERIALS ETC. PER 2004 FBC/M 506.3.
  
 2) THE SUBMITTED DETAIL FOR THE EXHAUST FAN LISTS THREE
 DIFFERENT MODELS, PLEASE MARK WHICH ONE IS BEING
 INSTALLED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved