Plan Review Details - Permit 08070815
| Plan Review Stops For Permit 08070815 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-29 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-07-29 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-01 |
Time |
14:39 |
Rev Time |
0.40 |
| Received By |
tgordon |
Date |
2008-08-01 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-30 |
Time |
14:09 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-07-30 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2008-07-30 14:30:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) THE HOOD EXHAUST FAN BEING INSTALLED IS 2,175 CFM'S, | | | THE BUILDING MAKE UP AND OUTDOOR AIR IS 1,510 CFM'S, | | | THIS WOULD PUT THE BUILDING AT A NEGATIVE PRESSURE. PER | | | 2004 FBC 13-409.1.ABC.2 BUILDING PRESSURES. MECHANICAL | | | SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE | | | PRESSURIZED WITH RESPECT TO OUTDOORS. PLEASE HAVE THE | | | BUILDING PLANS ENGINEER MARTIN WHITELOCKE REVIEW THE | | | HOOD INFORMATION AND REVISE MECHANICAL PLAN 1 OF 1 SO | | | THE BUILDING WILL NOT BE AT A NEGATIVE PRESSURE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-29 |
Time |
16:09 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-07-29 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2008-07-29 16:22:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT A PLAN SHOWING THE DUCT WORK FROM THE | | | HOOD TO THE EXHAUST FAN, LISTING THE SIZES AND | | | MATERIALS ETC. PER 2004 FBC/M 506.3. | | | | | | 2) THE SUBMITTED DETAIL FOR THE EXHAUST FAN LISTS THREE | | | DIFFERENT MODELS, PLEASE MARK WHICH ONE IS BEING | | | INSTALLED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
|