Plan Review Details - Permit 08070802
Plan Review Stops For Permit 08070802
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-07-31 Cont ID  
Sent By lursu Date 2008-07-31 Time 15:27 Rev Time 0.00
Received By lursu Date 2008-07-31 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-06-02 Cont ID  
Sent By jwitmer Date 2009-06-02 Time 08:31 Rev Time 0.77
Received By jwitmer Date 2009-06-02 Time 08:00 Sent To  
Notes
2009-06-02 08:32:21REV# 6 DATED 5-21-09 DRIVE-THRU WINDOW
  
 6-25-09/ FAILED /VOID STAMP APPLIED BECAUSE OF ZONING
 COMMENTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-04-05 Cont ID  
Sent By jwitmer Date 2009-04-05 Time 18:11 Rev Time 1.55
Received By jwitmer Date 2009-04-05 Time 18:11 Sent To  
Notes
2009-04-05 18:21:39BUILDING PLAN REVIEW
 PERMIT: 08070802
 ADD: 10130 NORTHLAKE BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 05/09
  
 BUILDING PROVISO:
  
 1) SHEET S-3 ROOFTOP HVAC EQUIPMENT SEE NOTE 6 NEW HVAC
 TO MEET THE 2004 FBC WINDLOADS OF 140MPH/ 3 SECOND
 GUST, TO PROVIDE ENGINEERED CALCULATIONS.
  
 2) SHEET D, D1 AND D2, NOTE 144REMOVAL OF EXISTING
 GENERAL SEE ELECTRICAL SHEETS FOR ADDITIONAL INFO, E
 SHEETS INDICATE THE INSTALATION OF A NEW GENERATOR.
 PROVIDE ANCHORING DETAIL OF THE NEW GENERATOR TO THE
 EXISTING SLAB. PROVIDE WIND DESIGN INFORMATION ALSO.
 SEE FIGURE 1609 AND SECTION 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIPPAGE BEFORE INSPECTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-02-06 Cont ID  
Sent By jwitmer Date 2009-02-06 Time 16:56 Rev Time 0.55
Received By jwitmer Date 2009-02-06 Time 16:56 Sent To  
Notes
2009-02-06 16:57:25BUILDING PLAN REVIEW
 PERMIT: 08070802
 ADD: 10130 NORTHLAKE BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 FEB.06/09
 3RD REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE THE REMOVAL OF THE DRIVE THROUGH
 WINDOW IT STILL SHOWS UP ON SHEETS A-5, A-7, SUP-1, S-1
 S-2, P-1 E-4 & E-5. PLEASE CORRELATE PLANS. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-16 Cont ID  
Sent By jwitmer Date 2008-10-16 Time 14:20 Rev Time 0.77
Received By jwitmer Date 2008-10-16 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By jwitmer Date 2008-08-13 Time 09:32 Rev Time 2.22
Received By jwitmer Date 2008-08-13 Time 09:32 Sent To  
Notes
2008-08-13 10:00:03BUILDING PLAN REVIEW
 PERMIT: 08070802
 ADD: 10130 NORTHLAKE BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 12, 2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND
 FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF
 AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN
 ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF
 AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN,
 INC.
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. (ARCHITECTS)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. (ENGINEER)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET D-1 NOTE # 140 INDICATES THE INSTALLATION OF A
 NEW OBSEERVATION WINDOW, IS THIS FOR OBSEERVATION ONLY
 OR A PICK UP WINDOW AS WELL? PRODUCT APPROVALS ARE
 REQUIRED FOR GLAZED OPENINGS.
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 3A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 1) OBSERVATION WINDOW OR
 2) PICKUP WINDOW
  
 3B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.)
 SHEET D-1 NOTE 140 INDICATES A NEW THROUGH THE WALL
 OBSERVATION WINDOW, IS THIS A TRUE PICK UP WINDOW? WILL
 NEED PRODUCT APPROVAL FOR GLAZED UNIT.
  
 4) S-3 DETAILS 1 & 3 DO NOT INDICATE ANY INFORMATION AS
 TO WIND DESIGN FOR NEW ROOF TOP A/C UNIT OR NEW
 PHARMACY WINDOW.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 5) SHEET S-1 DETAIL 1 & 2 INDICATE NEW FLOOR SECTIONS
 BUT THERE IS NO MENTION OF SOIL TREATMENT OF TERMITES.
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 6) SHEET D-1A DEMO NOTE# 35 REMOVAL OF EXISTING
 RAILINGS, PLEASE PROVIDE A LOCATION WHERE RAILINGS ARE
 TO BE REMOVED, I COULD NOT LOCATE THIS ITEM ON SHEET
 D-1? ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2009-06-11 Time 10:03 Sent To  
Notes
2009-06-11 10:03:40 
 ** DENIED REVIEW**
  
 1) NOTE: PLEASE KNOW THAT BASED ON THE ZONING REVIEW
 COMMENTS THE SCOPE OF WORK BEING REVISED MAY NOT BE
 PERMITTED AT THIS TIME. THE ELECTRICAL PLANS CAN NOT BE
 STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-04-24 Cont ID  
Sent By dpalmer Date 2009-04-24 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2009-04-24 Time 15:42 Sent To  
Notes
2009-04-24 15:43:00PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR
 PLUMBING REVIEW AT HIS REQUEST.
  
 PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL
 GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE
 PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE
 REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW
 STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER
 WITH MR. ROBERT BROWN ALSO.
 ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS
 REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY
 GENERATOR.
  
  
2009-04-24 15:42:41** REDLINED PLANS/ PROVISO**
  
 STORE 651, 10130 NORTHLAKE BLVD
  
 1) NOTE: THE LOAD CALCULATIONS ON THE EM PANEL STATES A
 DEMAND LOAD WITH A DEMAND FACTOR OF 1.13. IT IS UNCLEAR
 WHERE THE 1.13 FACTOR IS DERIVED. THIS REVIEWER KNOWS
 OF NO CODE SECTIONS IN THE NEC OR ANY OTHER ADOPTED
 CODES WHICH ALLOWS A DEMAND FACTOR OF 1.13.
 THE LOADS AS SHOWN IN THE PANEL *EM* ARE DEFINED AS
 CONTINUOUS LOADS. BASED ON 230.42, 215.3 AND OTHER
 SECTIONS ADOPTED IN THE NEC THESE LOADS NEED TO BE
 SHOWN AT 125%.
 THE PANEL SCHEDULE SHOWS THE LOAD AT 58AMPS. IF THE
 DEMAND OF 125% IS FIGURED THIS WOULD EXCEED THE RATING
 OF THE BREAKER, THE FEEDERS (BASED ON BREAKER) THE ATS
 AND MAIN BREAKER IN PANEL.
 THIS WOULD REQUIRE EQUIPMENT AND OTHER ITEMS NOW SHOWN
 ON PLANS TO BE REVISED/INCREASED.
 A CALLED WAS PLACED TO EDUARDO DE VARONA AND IS AWARE
 OF THE ISSUE.
  
 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO
 BE SHOWN AND FIGURED AT 125%. 215.3,230.42.
  
 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL
 BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE
 INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG
 WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE
 VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT
 APPLICATION.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-04-05 Cont ID  
Sent By dpalmer Date 2009-04-05 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2009-04-05 Time 09:13 Sent To  
Notes
2009-04-05 11:10:15** DENIED 4TH REVIEW **
  
 ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS
 WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE
 NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO
 MEET MINIMUM CODES.
  
  
 1) NOTE: THE PLANS DO NOT SHOW ANY SCALE FOR THE
 ELECTRICAL ROOM. PLEASE SEE NFPA-110
 7.2.2, 7.2.2.1.
 AS THE PLANS DO NOT SHOW A SCALE A DETERMINATION FOR
 MINIMUM CODE COMPLIANCE ON CLEARANCE CAN NOT BE MADE.
  
 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE
 HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE
 INFORMATION. BASED ON THE RISER AND PANELS, THERE IS
 OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED
 SYSTEMS IN THE SAME EQUIPMENT.
 MOST CERTAINLY SHOWING CIRCUITS SUCH AS LOTTO MACHINE
 AND THE FLORAL SCALE CIRCUITS IN PANELS WHICH ARE
 SUPPOSE TO BE FOR LIFE SAFETY SYSTEMS CLEARLY DO NOT
 MEET MINIMUM CODES. THESE ARE ONLY TWO CIRCUITS NOTED
 WHICH ARE NOT PERMITTED TO BE IN THE 700 SYSTEM PANELS.
 THERE ARE MANY OTHERS.
 THIS IS NOT A NEW CODE. PLEASE KNOW THAT ALL LIFE
 SAFETY 700 SYSTEMS ARE REQUIRED TO BE SEPARATE. THIS
 HAS BEEN IN MANY CODE CYCLES FOR BACK MORE THAN TWENTY
 YEARS. THIS BUILDING WAS BUILT IN 1999. THE CODES AT
 THAT TIME REQUIRED SYSTEMS TO BE SEPARATE.
 SEE PLANS AS THERE ARE LIFE SAFETY LOADS (700) , 701
 LOADS AND 702 OPTIONAL STAND-BY LOADS.
 *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT
 DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS
 SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO
 THE CITY OF WEST PALM BEACH.
 ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED,
 THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE
 PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE
 CONTACT/MEETING HAS BEEN HELD.
  
 3) NOTE: THE FEEDERS TO PANEL EB DO NOT MEET
 310.16,110.14,240.4. SHOWS #10 AWG ON 40AMP BREAKER.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE,
 ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE
 MORE THAN ONE.
 ENCLOSURES SHALL MEET NFPA-110 7.2.1.1
 NEC 110.3, 700.6, 90.7 ETC
  
 5) NOTE: AN EXPLANATION FOR THE 5-MINUTE PROPOSED TIME
 AS SHOWN ON RISER NEEDS TO BE PROVIDED. BASED ON THIS
 NOTE ON PLANS, THE 700 SYSTEM WILL NOT ENERGIZE LIFE
 SAFETY LOADS FOR 5MINS.
 THIS DOES NOT MEET NFPA-110, OR NFPA-70 FOR TIMES FOR
 LEVEL ONE, TYPE 10, CLASS 2 SYSTEMS OR ANY 701,TYPE 60
 LOADS.
 PLEASE SEE NEC 700.6, 700.12, 700.16, 700.17 ETC
  
 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR
 FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN
 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL
 BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE
 PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS
 NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE
 COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT
 MEET 225.38, 225.39.
 THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD
 SERVED.
 ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR
 MAY OR MAY NOT MEET READILY ACCESSIBLE.
  
 7) NOTE: CONDUCTORS FROM GENERATOR CAN NOT BE VERIFIED
 AS NO OVER CURRENT PROTECTION OF INFORMATION ON THE
 GENERATOR IS PROVIDED. 445.13, 310.16, 110.14\
  
 8) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL
 BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY
 AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD
 CREATE A SAFETY ISSUE.
 OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH
 AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE
 LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING
 PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING
 INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2
  
 9) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002.
  
 10) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR
 GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF
 NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED
 FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE
 PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER
 REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS
 EXAMINERS.
  
 11) NOTE: NEW NOTE: WHERE IS THE DISCONNECTING MEANS
 FOR TANK-LESS WATER HEATER? 422.31 MAY BE A SNAP SWITCH
 TYPE DEVICE WITH NO OCP.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-02-18 Cont ID  
Sent By dpalmer Date 2009-02-18 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2009-02-18 Time 14:06 Sent To  
Notes
2009-02-18 14:07:10** DENIED THIRD REVIEW **
  
 ** PLEASE SEE NOTES BELOW AS THEY ARE EXACT COMMENTS
 FROM PREVIOUS TWO REVIEWS.
  
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE
 SUBMITTED MEETING PRESCRIPTIVE REQUIREMENTS. 13-415.2,
 13-415.2.ABC.1.1,.1.2,.1.3 ETC
 THIS WAS GONE OVER AT LENGTH IN MEETING HELD WITH
 DESIGNER FROM FIRM YET THE PLANS ARE RESUBMITTED WITH
 NO CALCULATIONS.
  
 2) NOTE: PLANS STILL DO NOT SHOW ANY COMPLIANCE FOR
 PRESCRIPTIVE REQUIREMENTS FOR NEW AREAS AND NEW
 LIGHTING CONTROLS FOR SEPARATE SPACES. THIS COMMENT WAS
 FOR NEW AREAS ONLY AND COMMENTS WERE GONE OVER WITH
 DESIGNER FROM FIRM AT LENGTH. HOWEVER PLANS STILL ONLY
 SHOW STANDARDS DEVICES AND NO COMPLIANCE FOR NEW IS
 SHOWN.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: NO LETTER WAS SUBMITTED WITH RESPECT TO
 REQUIRED LIGHTING FOR EGRESS OR OCCUPANCY NOT PERMITTED
 WHEN UNDER EMERGENCY POWER. THIS WAS ALSO GONE OVER AT
 LENGTH IN MEETING YET NO CHANGES IN PLANS OR STORE
 OPERATIONS ARE PROVIDED.
  
 4) NOTE: A NEW COMMENT AS THE RESPONSE FOR
 ARCHITECTURAL AND ZONING IS THE FACT THE DRIVE THROUGH
 IS SUPPOSE TO BE REMOVED AND NOT INCLUDED IN THE SCOPE
 OF WORK HOWEVER THE ELECTRICAL PLANS AS WELL AS OTHER
 SHEETS STILL SHOW THIS SCOPE OF WORK.
  
 5) NOTE: IN THE PREVIOUS REVIEW A NOTICE IN COMMENTS
 WAS GIVEN WITH RESPECT TO FS 553.80(2)(B). THIS WAS
 ONLY A NOTICE GIVEN AT THAT TIME AS THE SPECIFIC
 COMMENTS HAD ONLY BEEN REPEATED TWO TIMES. THIS IS NOW
 THE THIRD REVIEW WITH THE SAME CODE COMPLIANCE COMMENTS
 BEING REPEATED. THE CODE SECTIONS FOR DEFICIENCIES ARE
 SPECIFIC IN ALL THREE REVIEWS FOR COMMENTS #1 AND #2.
 THE STATUTE STATES THAT IF PLANS ARE BEING REJECTED FOR
 THE SAME SPECIFIC COMMENT THERE SHALL BE A FEE IMPOSED
 BASED ON THE PORTION OF THE PERMIT FEE ATTRIBUTED TO
 PLAN REVIEW. THE PORTION ATTRIBUTED TO PLAN REVIEW IN
 THE CITY OF WEST PALM BEACH IS 30% OF THE BASE PERMIT
 FEE. THIS IS THE FEE TIMES FOUR AS STATED IN THE
 STATUTE. THE BASE PERMIT FEE ON THIS PROJECT IS $4,620
 TIMES 30% IS $1,386 TIMES FOUR. THIS AMOUNT IS $5,544.
 THIS FEE IS NOT FOR OWNER OR CONTRACTOR AS THIS IS A
 SECTION LISTED UNDER STATUTES FOR
  
 6) NOTE: THE RISER AS SHOWN DOES NOT INCLUDE THE MOST
 RECENT ELECTRICAL REVISIONS AS MADE ON SITE WITH THE
 MOST RECENT PERMITTED ELECTRICAL WORK. THIS WILL NEED
 TO BE REVISED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-22 Cont ID  
Sent By dpalmer Date 2008-10-22 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2008-10-22 Time 13:05 Sent To  
Notes
2008-10-22 13:06:18** DENIED 2ND REVIEW**
  
  
  
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 ALL SHEETS SUBMITTED BUT ONE ARE THE SAME.
  
  
 1) NOTE: PLANS DO NOT SHOW ANY LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2,13-415.2.ABC.1.1, .1.2.
 THE RESPONSE LETTER SUBMITTED MAKES NOTE OF COMPLIANCE
 HOWEVER THE PLANS WHICH ARE THE RECORD SET OF DRAWINGS
 ARE REQUIRED TO BE DESIGNED AND SHOW COMPLIANCE WITH
 THE MINIMUM CODE(S). FS 553.73
 PLEASE BE SURE TO SEE ALL LIGHTING SHOWN ON PLANS FOR
 ALL AREAS IN WHICH NEW LIGHTING IS BEING ADDED. IF THE
 EXISTING AMOUNT OF WATTS PER SQUARE FOOT EXCEEDS
 ALLOWANCE NEW LIGHTING MAY NOT SIMPLY BE ADDED. THIS IS
 FOR ALL AREAS IN WHICH NEW LIGHTING IS BEING SHOWN.
 OTHER ALLOWANCES ETC MAY NEED TO BE LOOKED INTO FOR
 DESIGN.
  
 2) NOTE: PLEASE SEE SECTIONS OF THE CODE AS NOTED
 PREVIOUSLY FOR REQUIRED LIGHTING CONTROLS WAS NOT
 ADDRESSED. THE RESPONSE MENTIONS *SWITCHES* ARE AND
 WERE PROVIDED ON PLANS. PLEASE SEE FBC 13-415.1.ABC.1.
 THIS SECTION OF THE CODE REQUIRES AUTOMATED LIGHTING
 CONTROLS FOR ALL BUILDINGS OVER 5K SQ FT. AS THIS
 BUILDING MOST CERTAINLY MEETS THIS DEFINITION CONTROLS
 ARE REQUIRED. THE SUBSEQUENT SECTIONS 13-415.1.ABC.1.1,
 .1.2 AND .1.3 IN THIS SITUATION ALSO APPLY. THIS
 REQUIRES ANY SEPARATE SPACES TO CONTAIN SEPARATE
 CONTROLS. A *STANDARD SWITCH* DOES NOT MEET THESE
 SECTIONS OF THE CODE AS AUTOMATED SHUT OFF OF SOME KIND
 IT REQUIRED. THIS MAY BE DONE BY OCCUPANCY SENSORS, OR
 MANUAL SWITCH WHICH OVER RIDE SOME SORT OF LIGHTING
 CONTROL SYSTEM. THERE ARE LITERALLY DOZENS OF WAYS TO
 ACHIEVE MINIMUM CODE COMPLIANCE. PLEASE ADDRESS THIS
 COMMENT.
 ** THE ENERGY CODE REQUIRES ALL NEW BEING INSTALLED OR
 REPLACED TO MEET PRESCRIPTIVE REQUIREMENTS.
  
 3) NOTE: PLEASE OBTAIN A LETTER FROM PUBLIX CORPORATE
 OFFICES/ LAW DEPARTMENT WHICH NEEDS TO STATE THE STORE
 WILL NOT BE OCCUPIED WHEN THE NORMAL POWER AS WELL AS
 THE OPTIONAL STAND-BY GENERATOR IS LOST AND UNDER LIFE
 SAFETY GENERATOR POWER. (OR WORDS TO THAT AFFECT). THIS
 INCLUDES EMPLOYEES NOT ONLY THE PUBLIC.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By dpalmer Date 2008-08-13 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2008-08-13 Time 15:11 Sent To  
Notes
2008-08-13 15:11:46**DENIED**
  
 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS
 LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN
 IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT
 A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS
 LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE
 WEBSITE.
 PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE
 NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR
 ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL
 BUSINESS.
 PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH)AND FAC
 61G15-23.002, 61G1-16.004.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER
 SHEETS.
 THE LIFE SAFETY PLAN .
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP
 LIGHTING FOR ALL EGRESS PATHS IN AREAS IN WHICH WORK IS
 BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH
 OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT
 OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT
 CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2.
  
 ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION
 UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE
 *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO
 HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION.
 ** THE BACK UP FOR NORMAL IS CURRENTLY THE EMERGENCY
 LIFE SAFETY GENERATOR. BASED ON THIS THE STORE IS
 REQUIRED TO BE EVACUATED UNDER EMERGENCY POWER. IF
 EMERGENCY POWER IS THE *NORMAL* POWER THERE IS *NO*
 BACK UP FOR LIFE SAFETY.
  
 ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH
 BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY
 AREAS, PLEASE INDICATE.
 AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN
 AREAS ARE KNOWN TO BE BATTERY BACK UP.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW
 BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND
 .1.3.
 PLEASE BE SURE TO SEE REQUIREMENTS FOR SEPARATE SPACES
 AND AREAS SUCH A LOUNGE FOR EMPLOYEES.
  
 6) NOTE:ALL CONTINUOUS LOADS SHALL BE SHOWN AT 125%.
 215.3,230.42 ETC
  
 7) NOTE: PLEASE SEE RISER AS ALL CONDUCTORS SHALL BE
 PROTECTED BY THE OVER CURRENT PROTECTION LIMITING THE
 LOAD. 240.4,310.16 ETC
 BASED ON RISER, MDP SHOWS A 225AMP BREAKER FEEDING NEW
 PANEL *T*. (BASED ON RISER)
  
 *** THE EXISTING RISER AS SHOWN WAS NOT REVIEWED FOR
 CODE COMPLIANCE.
  
 *** AS THERE IS MUCH INFORMATION NOT YET SUBMITTED
 THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2009-06-17 Cont ID  
Sent By mawillia Date 2009-06-17 Time 14:21 Rev Time 0.00
Received By mawillia Date 2009-06-17 Time 14:08 Sent To  
Notes
2009-06-17 14:21:20*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE STAMPED WHEN
 THE OTHER PLAN EXAMINERS HAVE BEEN SATISFIED. THE BELOW
 COMMENT WAS TAKEN FROM THE FIRE PLAN REVIEW NOTES OF
 4/06/2009:
  
 PLAN SHEETS LS-2, FA-1, & FA-2 WERE PREVIOUSLY
 FIRE-STAMPED ON 10/29/08; SHEETS WERE LS-1, A-2, A-4,
 AND FP-1 STAMPED, INITIALED, AND DATED. PLAN SHEET E-2
 TO BE FIRE-STAMPED WHEN THE ELECTRICAL SHEETS HAVE BEEN
 APPROVED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 15:17 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 14:36 Sent To  
Notes
2009-04-06 15:00:28*****APPROVED*****
  
  
 PLAN SHEETS LS-2, FA-1, & FA-2 WERE PREVIOUSLY
 FIRE-STAMPED ON 10/29/08; SHEETS WERE LS-1, A-2, A-4,
 AND FP-1 STAMPED, INITIALED, AND DATED. PLAN SHEET E-2
 TO BE FIRE-STAMPED WHEN THE ELECTRICAL SHEETS HAVE BEEN
 APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-03-10 Cont ID  
Sent By mwennerg Date 2009-03-10 Time 11:00 Rev Time 0.00
Received By mwennerg Date 2009-03-10 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-29 Cont ID  
Sent By mwennerg Date 2008-10-29 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-10-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 14:35 Sent To  
Notes
2008-08-29 14:44:52***DENIED***
  
 1) NOTE SHOULD READ NFPA 101, 2003 UNDER BUILDING CODE
 ANALYSIS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) DUCT SMOKE DETCTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 6) REQUIRED ILLUMINATED EXIT SIGNS SHALL NOT EXCEED A
 DISTANCE OF GREATER THAN 100'.
  
 7) PLEASE INDICATE DOORS PROVIDED WITH PANIC OR FIRE
 EXIT HARDWARE ON DOOR SCHEDULE.
  
 8) PLEASE CLARIFY FIRE ALARM REMODEL. IS THE FIRE ALARM
 CONTROL PANEL EXISTING OR WILL IT BE CHANGED OUT?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-04-27 Cont ID  
Sent By dwise Date 2009-04-27 Time 19:56 Rev Time 0.00
Received By dwise Date 2009-04-27 Time 19:56 Sent To PC
Notes
2009-04-27 19:56:52GAS UNDER SEPERATE REVIEW AND PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By kstevens Date 2009-04-02 Time 19:05 Rev Time 0.00
Received By kstevens Date 2009-04-02 Time 19:05 Sent To  
Notes
2009-04-02 19:06:26DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 NFPA-58
  
 A. SHT P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF ITS
 SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE LOCATED
 SO THAT THE FILLING CONNECTION AND FIXED MAXIMUM LIQUID
 LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY EXTERNAL SOURCE
 OF IGNITION. SEE TABLE 6.3.9. TANK IS A MAXIMUM 7 FT TO
 THE FAR SIDE OF THE GENERATOR.
  
 B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE
 GAS PERMIT REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC
 TRANSFER VALVE AND SHUT OFF VALES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT
 WILL BE REMOVED.
  
 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC
 TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS
 TO NATURAL GAS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-05-29 Time 08:50 Sent To  
Notes
2009-05-29 08:51:13TO COMM BD# 10- REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 16:36 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 08:50 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 08:50 Sent To  
Notes
2009-01-29 08:50:51TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 14:45 Sent To  
Notes
2008-09-30 14:54:14TO "COMM" BD#22--PLANS ON RACK--1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2008-07-30 Time 16:33 Sent To  
Notes
2008-07-30 16:38:53TO "COMM" BD#56

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 20:33 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 20:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-08-04 Cont ID  
Sent By tgordon Date 2008-08-04 Time 09:42 Rev Time 0.45
Received By tgordon Date 2008-08-04 Time 09:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-04-02 Cont ID  
Sent By kstevens Date 2009-04-02 Time 19:04 Rev Time 0.00
Received By kstevens Date 2009-04-02 Time 19:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 14:29 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 14:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 12:03 Rev Time 0.00
Received By kstevens Date 2008-10-08 Time 11:30 Sent To  
Notes
2008-10-08 12:06:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. INDICATE THE SUITE/BAY NUMBER ON THE APPLICATION AND
 ON THE PLANS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SUITE/BAY NUMBER IS NOT
 INDICATED ON THE APPLICATION, NOR IN THE TITLE BLOCKS
 OF EACH SHEET.
  
 2. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-07 Cont ID  
Sent By kstevens Date 2008-08-07 Time 08:24 Rev Time 0.00
Received By kstevens Date 2008-08-06 Time 18:08 Sent To  
Notes
2008-08-07 08:31:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. INDICATE THE SUITE/BAY NUMBER ON THE APPLICATION AND
 ON THE PLANS. SECTION 106.1.1.
  
 2. INDICATE THE GROSS SQUARE FOOTAGE OF THE STORE. AS
 INDICATED ON THE PLANS A DRINKING FOUNTAIN HAS BEEN
 DELETED. ONLY ONE DRINKING FOUNTAIN IS SHOWN ON THE
 FLOOR PLAN. PER TABLE 1004.1.2 THE OCCUPANCY IS TO BE
 DETERMINED BY DIVIDING THE GROSS SQUARE FOOTAGE BY 30.
 THEN PER TABLE 403.1 THE MINIMUM DRINKING FOUNTAIN
 REQUIREMENT IS THEN DETERMINED BY DIVIDING THAT NUMBER
 BY 1,000.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 5 Status F Date 2009-06-04 Cont ID  
Sent By lfranco Date 2009-06-04 Time 18:14 Rev Time 0.00
Received By lfranco Date 2009-06-04 Time 18:14 Sent To  
Notes
2009-06-04 18:14:38PLANNING AND ZONING: **** FAILED - RE-SUBMITTAL ADDED
 PHARMACY WINDOW AND DRIVE-THRU LANE.*****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY
 BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR
 THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO
 SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE
 THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE
 STACKING DIAGRAM ACCORDINGLY.
  
 ADDITIONALLY, THE STACKING SHALL NOT INTERFERE WITH THE
 TRAFFIC FLOW OF THE SERVICING RIGHT-OF-WAY OR THE
 INGRESS AND EGRESS OF THE PARKING AREA. EACH QUEUING
 SPACE SHALL BE A MINIMUM OF TEN (10) FEET BY 20 FEET,
 CLEARLY DEFINED AND DESIGNED SO AS NOT TO CONFLICT OR
 INTERFERE WITH OTHER TRAFFIC USING THE SITE. THE
 QUEUING SHALL BE MEASURED FROM THE FRONT OF THE STOPPED
 VEHICLE LOCATED AT THE POINT OF SERVICE TO THE REAR OF
 THE QUEUING LANE.
  
 THE CURRENT SUBMITTAL PLANS SHOW THE STACKING CAR
 DIMENSION AT 6'X15' AND ONE OF THE CAR STACKING
 ENCROACHING INTO THE RIGHT-OF-WAY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-04-09 Cont ID  
Sent By lfranco Date 2009-04-09 Time 17:06 Rev Time 0.00
Received By lfranco Date 2009-04-09 Time 17:06 Sent To  
Notes
2009-04-09 17:22:35PLANNING AND ZONING **** PASSED WITH PROVISO - THIS
 PERMIT DOES NOT INCLUDE THE NEW GENERATOR AND GAS TANK.
 SEPARATE PERMITS WILL HAVE TO BE APPLIED FOR THE NEW
 GENERATOR AND GAS TANK. ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PERMIT DOES NOT INCLUDE THE NEW GENERATOR AND
 GAS TANK. SEPARATE PERMITS WILL HAVE TO BE APPLIED FOR
 THE NEW GENERATOR AND GAS TANK. PLEASE NOTE THE
 FOLLOWING:
  
 THIS PROPERTY IS PART OF THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT ("RPD"), AN APPLICATION FOR A MINOR
 AMENDMENT TO THE IBIS RPD SHOWING THE ADDITIONAL
 GENERATOR AND GAS TANK WILL BE REQUIRED TO BE FILED TO
 THE PLANNING AND ZONING DEPARTMENT AND APPROVED PRIOR
 TO THE APPROVAL OF THE GENERATOR'S BUILDING PERMIT. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 3. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND
 LANDSCAPING DETAIL FOR ALL PROPOSED GENERATOR(S) AND
 THE GAS TANK. INCLUDE WALL HEIGHT, ETC. SCREENING
 ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-02-05 Cont ID  
Sent By lfranco Date 2009-02-05 Time 19:17 Rev Time 0.00
Received By lfranco Date 2009-02-05 Time 19:17 Sent To  
Notes
2009-02-05 19:32:48PLANNING AND ZONING: **** FAILED - 2ND
 RE-SUBMITTAL*****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY
 BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR
 THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO
 SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE
 THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE
 STACKING DIAGRAM ACCORDINGLY. ADDITIONALLY, THE
 STACKING SHALL NOT INTERFERE WITH THE TRAFFIC FLOW OF
 THE SERVICING RIGHT-OF-WAY OR THE INGRESS AND EGRESS OF
 THE PARKING AREA.
  
 RESPONSE TO RESUB: THE APPLICANT INDICATED THAT THE
 WINDOW WAS REMOVED FROM ALL PLANS AND THAT NO
 DRIVE-THRU (WORK) FOR THE PHARMACY WAS PROPOSED.
 HOWEVER, THE FOLLOWING SHEETS STILL REFLECT THE WINDOW
 AND/OR THAT SCOPE OF WORK. THE FOLLOWING SHEETS ARE
 SOME, BUT NOT LIMITED TO: COVER SHEET (EXIT ANALYSIS
 PLAN"), A-2, A-5, A-7, SUP-1, S-1, S-2,P-1, E-4 AND
 E-5). REVISE ALL SHEETS ON PACKETS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-07 Cont ID  
Sent By lfranco Date 2008-10-07 Time 12:34 Rev Time 0.00
Received By lfranco Date 2008-10-07 Time 12:34 Sent To  
Notes
2008-10-07 12:35:03PLANNING AND ZONING: **** FAILED *****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. REPEAT COMMENT: THERE IS A NOTATION FOR AN
 "EXISTING" GENERATOR. HOWEVER, THERE IS AN OUTSTANDING
 PERMIT FOR A GENERATOR THAT WAS FAILED ON 7/14/08
 (PERMIT NUMBER: 08060582). PLEASE CLARIFY DISCREPANCY
 ACCORDINGLY. IS THE NOTATION ON THESE CONSTRUCTION
 PLANS INCORRECT?
  
 3. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY
 BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR
 THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO
 SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE
 THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE
 STACKING DIAGRAM ACCORDINGLY. ADDITIONALLY, THE
 STACKING SHALL NOT INTERFERE WITH THE TRAFFIC FLOW OF
 THE SERVICING RIGHT-OF-WAY OR THE INGRESS AND EGRESS OF
 THE PARKING AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By lfranco Date 2008-08-01 Time 18:35 Rev Time 0.00
Received By lfranco Date 2008-08-01 Time 18:35 Sent To  
Notes
2008-08-01 18:49:17PLANNING AND ZONING:**** NO REVIEW REQUIRED FOR
 INTERIOR WORK, HOWEVER, GENERATOR NOTATION NEEDS TO BE
 REVISED. ****
  
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.THERE IS A NOTATION FOR AN "EXISTING" GENERATOR.
 HOWEVER, THERE IS AN OUTSTANDING PERMIT FOR A GENERATOR
 THAT WAS FAILED ON 7/14/08 (PERMIT NUMBER: 08060582).
 PLEASE CLARIFY DISCREPANCY ACCORDINGLY.IS THE
 NOTATION ON THESE CONSTRUCTION PLANS INCORRECT?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]