| Plan Review Stops For Permit 08070802 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-07-31 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-07-31 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-07-31 |
Time |
15:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-06-02 |
Time |
08:31 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-06-02 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2009-06-02 08:32:21 | REV# 6 DATED 5-21-09 DRIVE-THRU WINDOW | | | | | | 6-25-09/ FAILED /VOID STAMP APPLIED BECAUSE OF ZONING | | | COMMENTS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-04-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-05 |
Time |
18:11 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2009-04-05 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2009-04-05 18:21:39 | BUILDING PLAN REVIEW | | | PERMIT: 08070802 | | | ADD: 10130 NORTHLAKE BLVD. | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | APRIL 05/09 | | | | | | BUILDING PROVISO: | | | | | | 1) SHEET S-3 ROOFTOP HVAC EQUIPMENT SEE NOTE 6 NEW HVAC | | | TO MEET THE 2004 FBC WINDLOADS OF 140MPH/ 3 SECOND | | | GUST, TO PROVIDE ENGINEERED CALCULATIONS. | | | | | | 2) SHEET D, D1 AND D2, NOTE 144REMOVAL OF EXISTING | | | GENERAL SEE ELECTRICAL SHEETS FOR ADDITIONAL INFO, E | | | SHEETS INDICATE THE INSTALATION OF A NEW GENERATOR. | | | PROVIDE ANCHORING DETAIL OF THE NEW GENERATOR TO THE | | | EXISTING SLAB. PROVIDE WIND DESIGN INFORMATION ALSO. | | | SEE FIGURE 1609 AND SECTION 1609.1.3 ANCHORAGE AGAINST | | | OVERTURNING, UPLIFT AND SLIPPAGE BEFORE INSPECTION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-06 |
Time |
16:56 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2009-02-06 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2009-02-06 16:57:25 | BUILDING PLAN REVIEW | | | PERMIT: 08070802 | | | ADD: 10130 NORTHLAKE BLVD. | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | FEB.06/09 | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS INDICATE THE REMOVAL OF THE DRIVE THROUGH | | | WINDOW IT STILL SHOWS UP ON SHEETS A-5, A-7, SUP-1, S-1 | | | S-2, P-1 E-4 & E-5. PLEASE CORRELATE PLANS. 106.1.2 | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953. | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL | | | ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO | | | OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE | | | PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. | | | YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO | | | PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-16 |
Time |
14:20 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-10-16 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-13 |
Time |
09:32 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-08-13 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2008-08-13 10:00:03 | BUILDING PLAN REVIEW | | | PERMIT: 08070802 | | | ADD: 10130 NORTHLAKE BLVD. | | | CONT: OAK CONSTRUCTION | | | TEL: (954)583-9625 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | AUGUST 12, 2008 | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND | | | FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF | | | AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN | | | ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF | | | AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN, | | | INC. | | | 481.219 F.S. CERTIFICATE OF AUTHORIZATION. (ARCHITECTS) | | | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH | | | SHEET. | | | THIS MAY BE ADDED BY HAND. | | | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. (ENGINEER) | | | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 3) SHEET D-1 NOTE # 140 INDICATES THE INSTALLATION OF A | | | NEW OBSEERVATION WINDOW, IS THIS FOR OBSEERVATION ONLY | | | OR A PICK UP WINDOW AS WELL? PRODUCT APPROVALS ARE | | | REQUIRED FOR GLAZED OPENINGS. | | | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 3A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | 1) OBSERVATION WINDOW OR | | | 2) PICKUP WINDOW | | | | | | 3B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.) | | | SHEET D-1 NOTE 140 INDICATES A NEW THROUGH THE WALL | | | OBSERVATION WINDOW, IS THIS A TRUE PICK UP WINDOW? WILL | | | NEED PRODUCT APPROVAL FOR GLAZED UNIT. | | | | | | 4) S-3 DETAILS 1 & 3 DO NOT INDICATE ANY INFORMATION AS | | | TO WIND DESIGN FOR NEW ROOF TOP A/C UNIT OR NEW | | | PHARMACY WINDOW. | | | | | | 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | | | | 5) SHEET S-1 DETAIL 1 & 2 INDICATE NEW FLOOR SECTIONS | | | BUT THERE IS NO MENTION OF SOIL TREATMENT OF TERMITES. | | | 1816.1 TERMITE PROTECTION. | | | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED | | | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, | | | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR | | | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED | | | FOR USE AS A PREVENTATIVE TREATMENT TO NEW | | | CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE. | | | UPON COMPLETION OF THE APPLICATION OF THE TERMITE | | | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL | | | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED | | | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING | | | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE | | | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. | | | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS | | | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE | | | AND CONSUMER SERVICES.? | | | | | | 6) SHEET D-1A DEMO NOTE# 35 REMOVAL OF EXISTING | | | RAILINGS, PLEASE PROVIDE A LOCATION WHERE RAILINGS ARE | | | TO BE REMOVED, I COULD NOT LOCATE THIS ITEM ON SHEET | | | D-1? ADDITIONAL INFORMATION REQUIRED 106.1.2. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-11 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-11 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2009-06-11 10:03:40 | | | | ** DENIED REVIEW** | | | | | | 1) NOTE: PLEASE KNOW THAT BASED ON THE ZONING REVIEW | | | COMMENTS THE SCOPE OF WORK BEING REVISED MAY NOT BE | | | PERMITTED AT THIS TIME. THE ELECTRICAL PLANS CAN NOT BE | | | STAMPED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2009-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-24 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-24 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2009-04-24 15:43:00 | PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR | | | PLUMBING REVIEW AT HIS REQUEST. | | | | | | PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL | | | GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE | | | PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE | | | REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW | | | STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER | | | WITH MR. ROBERT BROWN ALSO. | | | ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS | | | REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY | | | GENERATOR. | | | | | | | | 2009-04-24 15:42:41 | ** REDLINED PLANS/ PROVISO** | | | | | | STORE 651, 10130 NORTHLAKE BLVD | | | | | | 1) NOTE: THE LOAD CALCULATIONS ON THE EM PANEL STATES A | | | DEMAND LOAD WITH A DEMAND FACTOR OF 1.13. IT IS UNCLEAR | | | WHERE THE 1.13 FACTOR IS DERIVED. THIS REVIEWER KNOWS | | | OF NO CODE SECTIONS IN THE NEC OR ANY OTHER ADOPTED | | | CODES WHICH ALLOWS A DEMAND FACTOR OF 1.13. | | | THE LOADS AS SHOWN IN THE PANEL *EM* ARE DEFINED AS | | | CONTINUOUS LOADS. BASED ON 230.42, 215.3 AND OTHER | | | SECTIONS ADOPTED IN THE NEC THESE LOADS NEED TO BE | | | SHOWN AT 125%. | | | THE PANEL SCHEDULE SHOWS THE LOAD AT 58AMPS. IF THE | | | DEMAND OF 125% IS FIGURED THIS WOULD EXCEED THE RATING | | | OF THE BREAKER, THE FEEDERS (BASED ON BREAKER) THE ATS | | | AND MAIN BREAKER IN PANEL. | | | THIS WOULD REQUIRE EQUIPMENT AND OTHER ITEMS NOW SHOWN | | | ON PLANS TO BE REVISED/INCREASED. | | | A CALLED WAS PLACED TO EDUARDO DE VARONA AND IS AWARE | | | OF THE ISSUE. | | | | | | 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO | | | BE SHOWN AND FIGURED AT 125%. 215.3,230.42. | | | | | | 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL | | | BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE | | | INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG | | | WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE | | | VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT | | | APPLICATION. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2009-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-05 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-05 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2009-04-05 11:10:15 | ** DENIED 4TH REVIEW ** | | | | | | ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS | | | WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE | | | NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO | | | MEET MINIMUM CODES. | | | | | | | | | 1) NOTE: THE PLANS DO NOT SHOW ANY SCALE FOR THE | | | ELECTRICAL ROOM. PLEASE SEE NFPA-110 | | | 7.2.2, 7.2.2.1. | | | AS THE PLANS DO NOT SHOW A SCALE A DETERMINATION FOR | | | MINIMUM CODE COMPLIANCE ON CLEARANCE CAN NOT BE MADE. | | | | | | 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE | | | HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE | | | INFORMATION. BASED ON THE RISER AND PANELS, THERE IS | | | OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED | | | SYSTEMS IN THE SAME EQUIPMENT. | | | MOST CERTAINLY SHOWING CIRCUITS SUCH AS LOTTO MACHINE | | | AND THE FLORAL SCALE CIRCUITS IN PANELS WHICH ARE | | | SUPPOSE TO BE FOR LIFE SAFETY SYSTEMS CLEARLY DO NOT | | | MEET MINIMUM CODES. THESE ARE ONLY TWO CIRCUITS NOTED | | | WHICH ARE NOT PERMITTED TO BE IN THE 700 SYSTEM PANELS. | | | THERE ARE MANY OTHERS. | | | THIS IS NOT A NEW CODE. PLEASE KNOW THAT ALL LIFE | | | SAFETY 700 SYSTEMS ARE REQUIRED TO BE SEPARATE. THIS | | | HAS BEEN IN MANY CODE CYCLES FOR BACK MORE THAN TWENTY | | | YEARS. THIS BUILDING WAS BUILT IN 1999. THE CODES AT | | | THAT TIME REQUIRED SYSTEMS TO BE SEPARATE. | | | SEE PLANS AS THERE ARE LIFE SAFETY LOADS (700) , 701 | | | LOADS AND 702 OPTIONAL STAND-BY LOADS. | | | *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT | | | DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS | | | SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO | | | THE CITY OF WEST PALM BEACH. | | | ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED, | | | THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE | | | PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE | | | CONTACT/MEETING HAS BEEN HELD. | | | | | | 3) NOTE: THE FEEDERS TO PANEL EB DO NOT MEET | | | 310.16,110.14,240.4. SHOWS #10 AWG ON 40AMP BREAKER. | | | | | | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE, | | | ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE | | | MORE THAN ONE. | | | ENCLOSURES SHALL MEET NFPA-110 7.2.1.1 | | | NEC 110.3, 700.6, 90.7 ETC | | | | | | 5) NOTE: AN EXPLANATION FOR THE 5-MINUTE PROPOSED TIME | | | AS SHOWN ON RISER NEEDS TO BE PROVIDED. BASED ON THIS | | | NOTE ON PLANS, THE 700 SYSTEM WILL NOT ENERGIZE LIFE | | | SAFETY LOADS FOR 5MINS. | | | THIS DOES NOT MEET NFPA-110, OR NFPA-70 FOR TIMES FOR | | | LEVEL ONE, TYPE 10, CLASS 2 SYSTEMS OR ANY 701,TYPE 60 | | | LOADS. | | | PLEASE SEE NEC 700.6, 700.12, 700.16, 700.17 ETC | | | | | | 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR | | | FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN | | | 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL | | | BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE | | | PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS | | | NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE | | | COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT | | | MEET 225.38, 225.39. | | | THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD | | | SERVED. | | | ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR | | | MAY OR MAY NOT MEET READILY ACCESSIBLE. | | | | | | 7) NOTE: CONDUCTORS FROM GENERATOR CAN NOT BE VERIFIED | | | AS NO OVER CURRENT PROTECTION OF INFORMATION ON THE | | | GENERATOR IS PROVIDED. 445.13, 310.16, 110.14\ | | | | | | 8) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL | | | BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY | | | AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD | | | CREATE A SAFETY ISSUE. | | | OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH | | | AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE | | | LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING | | | PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING | | | INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2 | | | | | | 9) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002. | | | | | | 10) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR | | | GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF | | | NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED | | | FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE | | | PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER | | | REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS | | | EXAMINERS. | | | | | | 11) NOTE: NEW NOTE: WHERE IS THE DISCONNECTING MEANS | | | FOR TANK-LESS WATER HEATER? 422.31 MAY BE A SNAP SWITCH | | | TYPE DEVICE WITH NO OCP. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-18 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-18 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2009-02-18 14:07:10 | ** DENIED THIRD REVIEW ** | | | | | | ** PLEASE SEE NOTES BELOW AS THEY ARE EXACT COMMENTS | | | FROM PREVIOUS TWO REVIEWS. | | | | | | | | | | | | 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE | | | SUBMITTED MEETING PRESCRIPTIVE REQUIREMENTS. 13-415.2, | | | 13-415.2.ABC.1.1,.1.2,.1.3 ETC | | | THIS WAS GONE OVER AT LENGTH IN MEETING HELD WITH | | | DESIGNER FROM FIRM YET THE PLANS ARE RESUBMITTED WITH | | | NO CALCULATIONS. | | | | | | 2) NOTE: PLANS STILL DO NOT SHOW ANY COMPLIANCE FOR | | | PRESCRIPTIVE REQUIREMENTS FOR NEW AREAS AND NEW | | | LIGHTING CONTROLS FOR SEPARATE SPACES. THIS COMMENT WAS | | | FOR NEW AREAS ONLY AND COMMENTS WERE GONE OVER WITH | | | DESIGNER FROM FIRM AT LENGTH. HOWEVER PLANS STILL ONLY | | | SHOW STANDARDS DEVICES AND NO COMPLIANCE FOR NEW IS | | | SHOWN. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 3) NOTE: NO LETTER WAS SUBMITTED WITH RESPECT TO | | | REQUIRED LIGHTING FOR EGRESS OR OCCUPANCY NOT PERMITTED | | | WHEN UNDER EMERGENCY POWER. THIS WAS ALSO GONE OVER AT | | | LENGTH IN MEETING YET NO CHANGES IN PLANS OR STORE | | | OPERATIONS ARE PROVIDED. | | | | | | 4) NOTE: A NEW COMMENT AS THE RESPONSE FOR | | | ARCHITECTURAL AND ZONING IS THE FACT THE DRIVE THROUGH | | | IS SUPPOSE TO BE REMOVED AND NOT INCLUDED IN THE SCOPE | | | OF WORK HOWEVER THE ELECTRICAL PLANS AS WELL AS OTHER | | | SHEETS STILL SHOW THIS SCOPE OF WORK. | | | | | | 5) NOTE: IN THE PREVIOUS REVIEW A NOTICE IN COMMENTS | | | WAS GIVEN WITH RESPECT TO FS 553.80(2)(B). THIS WAS | | | ONLY A NOTICE GIVEN AT THAT TIME AS THE SPECIFIC | | | COMMENTS HAD ONLY BEEN REPEATED TWO TIMES. THIS IS NOW | | | THE THIRD REVIEW WITH THE SAME CODE COMPLIANCE COMMENTS | | | BEING REPEATED. THE CODE SECTIONS FOR DEFICIENCIES ARE | | | SPECIFIC IN ALL THREE REVIEWS FOR COMMENTS #1 AND #2. | | | THE STATUTE STATES THAT IF PLANS ARE BEING REJECTED FOR | | | THE SAME SPECIFIC COMMENT THERE SHALL BE A FEE IMPOSED | | | BASED ON THE PORTION OF THE PERMIT FEE ATTRIBUTED TO | | | PLAN REVIEW. THE PORTION ATTRIBUTED TO PLAN REVIEW IN | | | THE CITY OF WEST PALM BEACH IS 30% OF THE BASE PERMIT | | | FEE. THIS IS THE FEE TIMES FOUR AS STATED IN THE | | | STATUTE. THE BASE PERMIT FEE ON THIS PROJECT IS $4,620 | | | TIMES 30% IS $1,386 TIMES FOUR. THIS AMOUNT IS $5,544. | | | THIS FEE IS NOT FOR OWNER OR CONTRACTOR AS THIS IS A | | | SECTION LISTED UNDER STATUTES FOR | | | | | | 6) NOTE: THE RISER AS SHOWN DOES NOT INCLUDE THE MOST | | | RECENT ELECTRICAL REVISIONS AS MADE ON SITE WITH THE | | | MOST RECENT PERMITTED ELECTRICAL WORK. THIS WILL NEED | | | TO BE REVISED. | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-22 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-22 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2008-10-22 13:06:18 | ** DENIED 2ND REVIEW** | | | | | | | | | | | | | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | ALL SHEETS SUBMITTED BUT ONE ARE THE SAME. | | | | | | | | | 1) NOTE: PLANS DO NOT SHOW ANY LIGHTING PERFORMANCE | | | CALCULATIONS PER FBC 13-415.2,13-415.2.ABC.1.1, .1.2. | | | THE RESPONSE LETTER SUBMITTED MAKES NOTE OF COMPLIANCE | | | HOWEVER THE PLANS WHICH ARE THE RECORD SET OF DRAWINGS | | | ARE REQUIRED TO BE DESIGNED AND SHOW COMPLIANCE WITH | | | THE MINIMUM CODE(S). FS 553.73 | | | PLEASE BE SURE TO SEE ALL LIGHTING SHOWN ON PLANS FOR | | | ALL AREAS IN WHICH NEW LIGHTING IS BEING ADDED. IF THE | | | EXISTING AMOUNT OF WATTS PER SQUARE FOOT EXCEEDS | | | ALLOWANCE NEW LIGHTING MAY NOT SIMPLY BE ADDED. THIS IS | | | FOR ALL AREAS IN WHICH NEW LIGHTING IS BEING SHOWN. | | | OTHER ALLOWANCES ETC MAY NEED TO BE LOOKED INTO FOR | | | DESIGN. | | | | | | 2) NOTE: PLEASE SEE SECTIONS OF THE CODE AS NOTED | | | PREVIOUSLY FOR REQUIRED LIGHTING CONTROLS WAS NOT | | | ADDRESSED. THE RESPONSE MENTIONS *SWITCHES* ARE AND | | | WERE PROVIDED ON PLANS. PLEASE SEE FBC 13-415.1.ABC.1. | | | THIS SECTION OF THE CODE REQUIRES AUTOMATED LIGHTING | | | CONTROLS FOR ALL BUILDINGS OVER 5K SQ FT. AS THIS | | | BUILDING MOST CERTAINLY MEETS THIS DEFINITION CONTROLS | | | ARE REQUIRED. THE SUBSEQUENT SECTIONS 13-415.1.ABC.1.1, | | | .1.2 AND .1.3 IN THIS SITUATION ALSO APPLY. THIS | | | REQUIRES ANY SEPARATE SPACES TO CONTAIN SEPARATE | | | CONTROLS. A *STANDARD SWITCH* DOES NOT MEET THESE | | | SECTIONS OF THE CODE AS AUTOMATED SHUT OFF OF SOME KIND | | | IT REQUIRED. THIS MAY BE DONE BY OCCUPANCY SENSORS, OR | | | MANUAL SWITCH WHICH OVER RIDE SOME SORT OF LIGHTING | | | CONTROL SYSTEM. THERE ARE LITERALLY DOZENS OF WAYS TO | | | ACHIEVE MINIMUM CODE COMPLIANCE. PLEASE ADDRESS THIS | | | COMMENT. | | | ** THE ENERGY CODE REQUIRES ALL NEW BEING INSTALLED OR | | | REPLACED TO MEET PRESCRIPTIVE REQUIREMENTS. | | | | | | 3) NOTE: PLEASE OBTAIN A LETTER FROM PUBLIX CORPORATE | | | OFFICES/ LAW DEPARTMENT WHICH NEEDS TO STATE THE STORE | | | WILL NOT BE OCCUPIED WHEN THE NORMAL POWER AS WELL AS | | | THE OPTIONAL STAND-BY GENERATOR IS LOST AND UNDER LIFE | | | SAFETY GENERATOR POWER. (OR WORDS TO THAT AFFECT). THIS | | | INCLUDES EMPLOYEES NOT ONLY THE PUBLIC. | | | | | | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-13 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-13 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2008-08-13 15:11:46 | **DENIED** | | | | | | 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS | | | LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN | | | IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT | | | A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS | | | LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE | | | WEBSITE. | | | PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE | | | NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR | | | ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL | | | BUSINESS. | | | PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH)AND FAC | | | 61G15-23.002, 61G1-16.004. | | | | | | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED | | | ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER | | | SHEETS. | | | THE LIFE SAFETY PLAN . | | | | | | 2004 FBC W/2007 REVISIONS. | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP | | | LIGHTING FOR ALL EGRESS PATHS IN AREAS IN WHICH WORK IS | | | BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH | | | OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT | | | OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT | | | CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED. | | | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2. | | | | | | ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION | | | UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE | | | *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO | | | HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION. | | | ** THE BACK UP FOR NORMAL IS CURRENTLY THE EMERGENCY | | | LIFE SAFETY GENERATOR. BASED ON THIS THE STORE IS | | | REQUIRED TO BE EVACUATED UNDER EMERGENCY POWER. IF | | | EMERGENCY POWER IS THE *NORMAL* POWER THERE IS *NO* | | | BACK UP FOR LIFE SAFETY. | | | | | | ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH | | | BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY | | | AREAS, PLEASE INDICATE. | | | AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN | | | AREAS ARE KNOWN TO BE BATTERY BACK UP. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING | | | INSTALLED. | | | PLEASE SEE13-415.2.ABC.1.1, .1.2. | | | | | | 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW | | | BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND | | | .1.3. | | | PLEASE BE SURE TO SEE REQUIREMENTS FOR SEPARATE SPACES | | | AND AREAS SUCH A LOUNGE FOR EMPLOYEES. | | | | | | 6) NOTE:ALL CONTINUOUS LOADS SHALL BE SHOWN AT 125%. | | | 215.3,230.42 ETC | | | | | | 7) NOTE: PLEASE SEE RISER AS ALL CONDUCTORS SHALL BE | | | PROTECTED BY THE OVER CURRENT PROTECTION LIMITING THE | | | LOAD. 240.4,310.16 ETC | | | BASED ON RISER, MDP SHOWS A 225AMP BREAKER FEEDING NEW | | | PANEL *T*. (BASED ON RISER) | | | | | | *** THE EXISTING RISER AS SHOWN WAS NOT REVIEWED FOR | | | CODE COMPLIANCE. | | | | | | *** AS THERE IS MUCH INFORMATION NOT YET SUBMITTED | | | THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING | | | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2009-06-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-06-17 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-06-17 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2009-06-17 14:21:20 | *****PROVISO***** | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE STAMPED WHEN | | | THE OTHER PLAN EXAMINERS HAVE BEEN SATISFIED. THE BELOW | | | COMMENT WAS TAKEN FROM THE FIRE PLAN REVIEW NOTES OF | | | 4/06/2009: | | | | | | PLAN SHEETS LS-2, FA-1, & FA-2 WERE PREVIOUSLY | | | FIRE-STAMPED ON 10/29/08; SHEETS WERE LS-1, A-2, A-4, | | | AND FP-1 STAMPED, INITIALED, AND DATED. PLAN SHEET E-2 | | | TO BE FIRE-STAMPED WHEN THE ELECTRICAL SHEETS HAVE BEEN | | | APPROVED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-06 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-06 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2009-04-06 15:00:28 | *****APPROVED***** | | | | | | | | | PLAN SHEETS LS-2, FA-1, & FA-2 WERE PREVIOUSLY | | | FIRE-STAMPED ON 10/29/08; SHEETS WERE LS-1, A-2, A-4, | | | AND FP-1 STAMPED, INITIALED, AND DATED. PLAN SHEET E-2 | | | TO BE FIRE-STAMPED WHEN THE ELECTRICAL SHEETS HAVE BEEN | | | APPROVED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-03-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-03-10 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-03-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-29 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-29 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-29 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-29 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2008-08-29 14:44:52 | ***DENIED*** | | | | | | 1) NOTE SHOULD READ NFPA 101, 2003 UNDER BUILDING CODE | | | ANALYSIS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS AND GUARDRAILS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) DUCT SMOKE DETCTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 6) REQUIRED ILLUMINATED EXIT SIGNS SHALL NOT EXCEED A | | | DISTANCE OF GREATER THAN 100'. | | | | | | 7) PLEASE INDICATE DOORS PROVIDED WITH PANIC OR FIRE | | | EXIT HARDWARE ON DOOR SCHEDULE. | | | | | | 8) PLEASE CLARIFY FIRE ALARM REMODEL. IS THE FIRE ALARM | | | CONTROL PANEL EXISTING OR WILL IT BE CHANGED OUT? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2009-04-27 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-04-27 |
Time |
19:56 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-04-27 |
Time |
19:56 |
Sent To |
PC |
|
| Notes |
| 2009-04-27 19:56:52 | GAS UNDER SEPERATE REVIEW AND PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-02 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-02 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2009-04-02 19:06:26 | DENIED | | | REFERENCE: | | | FBC-2004 FUEL GAS | | | NFPA-58 | | | | | | A. SHT P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF ITS | | | SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE LOCATED | | | SO THAT THE FILLING CONNECTION AND FIXED MAXIMUM LIQUID | | | LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY EXTERNAL SOURCE | | | OF IGNITION. SEE TABLE 6.3.9. TANK IS A MAXIMUM 7 FT TO | | | THE FAR SIDE OF THE GENERATOR. | | | | | | B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE | | | GAS PERMIT REQUIRED: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC | | | TRANSFER VALVE AND SHUT OFF VALES. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 5. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT | | | WILL BE REMOVED. | | | | | | 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC | | | TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS | | | TO NATURAL GAS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-05-29 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2009-05-29 08:51:13 | TO COMM BD# 10- REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-02 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-02 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-29 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-29 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2009-01-29 08:50:51 | TO "COMM" BD#38 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-30 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-30 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2008-09-30 14:54:14 | TO "COMM" BD#22--PLANS ON RACK--1 ROLL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-29 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-30 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2008-07-30 16:38:53 | TO "COMM" BD#56 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-02 |
Time |
20:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-02 |
Time |
20:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-04 |
Time |
09:42 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-08-04 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-02 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-02 |
Time |
19:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-03 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-08 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-08 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2008-10-08 12:06:02 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. INDICATE THE SUITE/BAY NUMBER ON THE APPLICATION AND | | | ON THE PLANS. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE SUITE/BAY NUMBER IS NOT | | | INDICATED ON THE APPLICATION, NOR IN THE TITLE BLOCKS | | | OF EACH SHEET. | | | | | | 2. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-07 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-06 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2008-08-07 08:31:20 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | | | | 1. INDICATE THE SUITE/BAY NUMBER ON THE APPLICATION AND | | | ON THE PLANS. SECTION 106.1.1. | | | | | | 2. INDICATE THE GROSS SQUARE FOOTAGE OF THE STORE. AS | | | INDICATED ON THE PLANS A DRINKING FOUNTAIN HAS BEEN | | | DELETED. ONLY ONE DRINKING FOUNTAIN IS SHOWN ON THE | | | FLOOR PLAN. PER TABLE 1004.1.2 THE OCCUPANCY IS TO BE | | | DETERMINED BY DIVIDING THE GROSS SQUARE FOOTAGE BY 30. | | | THEN PER TABLE 403.1 THE MINIMUM DRINKING FOUNTAIN | | | REQUIREMENT IS THEN DETERMINED BY DIVIDING THAT NUMBER | | | BY 1,000. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2009-06-04 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-06-04 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-06-04 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2009-06-04 18:14:38 | PLANNING AND ZONING: **** FAILED - RE-SUBMITTAL ADDED | | | PHARMACY WINDOW AND DRIVE-THRU LANE.***** | | | | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY | | | BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR | | | THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO | | | SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE | | | THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE | | | STACKING DIAGRAM ACCORDINGLY. | | | | | | ADDITIONALLY, THE STACKING SHALL NOT INTERFERE WITH THE | | | TRAFFIC FLOW OF THE SERVICING RIGHT-OF-WAY OR THE | | | INGRESS AND EGRESS OF THE PARKING AREA. EACH QUEUING | | | SPACE SHALL BE A MINIMUM OF TEN (10) FEET BY 20 FEET, | | | CLEARLY DEFINED AND DESIGNED SO AS NOT TO CONFLICT OR | | | INTERFERE WITH OTHER TRAFFIC USING THE SITE. THE | | | QUEUING SHALL BE MEASURED FROM THE FRONT OF THE STOPPED | | | VEHICLE LOCATED AT THE POINT OF SERVICE TO THE REAR OF | | | THE QUEUING LANE. | | | | | | THE CURRENT SUBMITTAL PLANS SHOW THE STACKING CAR | | | DIMENSION AT 6'X15' AND ONE OF THE CAR STACKING | | | ENCROACHING INTO THE RIGHT-OF-WAY. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-04-09 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-04-09 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-04-09 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2009-04-09 17:22:35 | PLANNING AND ZONING **** PASSED WITH PROVISO - THIS | | | PERMIT DOES NOT INCLUDE THE NEW GENERATOR AND GAS TANK. | | | SEPARATE PERMITS WILL HAVE TO BE APPLIED FOR THE NEW | | | GENERATOR AND GAS TANK. **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THIS PERMIT DOES NOT INCLUDE THE NEW GENERATOR AND | | | GAS TANK. SEPARATE PERMITS WILL HAVE TO BE APPLIED FOR | | | THE NEW GENERATOR AND GAS TANK. PLEASE NOTE THE | | | FOLLOWING: | | | | | | THIS PROPERTY IS PART OF THE IBIS RESIDENTIAL PLANNED | | | DEVELOPMENT ("RPD"), AN APPLICATION FOR A MINOR | | | AMENDMENT TO THE IBIS RPD SHOWING THE ADDITIONAL | | | GENERATOR AND GAS TANK WILL BE REQUIRED TO BE FILED TO | | | THE PLANNING AND ZONING DEPARTMENT AND APPROVED PRIOR | | | TO THE APPROVAL OF THE GENERATOR'S BUILDING PERMIT. SEE | | | HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER | | | DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD | | | AMENDMENT. | | | | | | 3. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND | | | LANDSCAPING DETAIL FOR ALL PROPOSED GENERATOR(S) AND | | | THE GAS TANK. INCLUDE WALL HEIGHT, ETC. SCREENING | | | ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING | | | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES | | | PLANTED AT TWO-FOOT INTERVALS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-02-05 |
Time |
19:17 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-02-05 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2009-02-05 19:32:48 | PLANNING AND ZONING: **** FAILED - 2ND | | | RE-SUBMITTAL***** | | | | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY | | | BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR | | | THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO | | | SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE | | | THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE | | | STACKING DIAGRAM ACCORDINGLY. ADDITIONALLY, THE | | | STACKING SHALL NOT INTERFERE WITH THE TRAFFIC FLOW OF | | | THE SERVICING RIGHT-OF-WAY OR THE INGRESS AND EGRESS OF | | | THE PARKING AREA. | | | | | | RESPONSE TO RESUB: THE APPLICANT INDICATED THAT THE | | | WINDOW WAS REMOVED FROM ALL PLANS AND THAT NO | | | DRIVE-THRU (WORK) FOR THE PHARMACY WAS PROPOSED. | | | HOWEVER, THE FOLLOWING SHEETS STILL REFLECT THE WINDOW | | | AND/OR THAT SCOPE OF WORK. THE FOLLOWING SHEETS ARE | | | SOME, BUT NOT LIMITED TO: COVER SHEET (EXIT ANALYSIS | | | PLAN"), A-2, A-5, A-7, SUP-1, S-1, S-2,P-1, E-4 AND | | | E-5). REVISE ALL SHEETS ON PACKETS ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-07 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-10-07 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-10-07 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2008-10-07 12:35:03 | PLANNING AND ZONING: **** FAILED ***** | | | | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. REPEAT COMMENT: THERE IS A NOTATION FOR AN | | | "EXISTING" GENERATOR. HOWEVER, THERE IS AN OUTSTANDING | | | PERMIT FOR A GENERATOR THAT WAS FAILED ON 7/14/08 | | | (PERMIT NUMBER: 08060582). PLEASE CLARIFY DISCREPANCY | | | ACCORDINGLY. IS THE NOTATION ON THESE CONSTRUCTION | | | PLANS INCORRECT? | | | | | | 3. PLANS SHOW A NEW DRIVE-THRU WINDOW FOR THE PHARMACY | | | BY THE NORTH WALL WITH THE QUEUEING (STACKING LANE) FOR | | | THE VEHICLES AT WHAT IS THE PORTE-COCHERE. PURSUANT TO | | | SECTION 94-486, TABLE XV-6, THE DRIVE-THRU SHALL HAVE | | | THE STACKING LANE TO ACCOMMODATE FIVE (5) CARS. PROVIDE | | | STACKING DIAGRAM ACCORDINGLY. ADDITIONALLY, THE | | | STACKING SHALL NOT INTERFERE WITH THE TRAFFIC FLOW OF | | | THE SERVICING RIGHT-OF-WAY OR THE INGRESS AND EGRESS OF | | | THE PARKING AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-08-01 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-08-01 |
Time |
18:35 |
Sent To |
|
|
| Notes |
| 2008-08-01 18:49:17 | PLANNING AND ZONING:**** NO REVIEW REQUIRED FOR | | | INTERIOR WORK, HOWEVER, GENERATOR NOTATION NEEDS TO BE | | | REVISED. **** | | | | | | | | | 1.RESPOND TO COMMENTS IN WRITING. | | | | | | 2.THERE IS A NOTATION FOR AN "EXISTING" GENERATOR. | | | HOWEVER, THERE IS AN OUTSTANDING PERMIT FOR A GENERATOR | | | THAT WAS FAILED ON 7/14/08 (PERMIT NUMBER: 08060582). | | | PLEASE CLARIFY DISCREPANCY ACCORDINGLY.IS THE | | | NOTATION ON THESE CONSTRUCTION PLANS INCORRECT? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|