Plan Review Details - Permit 08070786
Plan Review Stops For Permit 08070786
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By jgomez Date 2008-08-11 Time 14:07 Rev Time 0.00
Received By jgomez Date 2008-08-11 Time 13:45 Sent To PC
Notes
2008-08-11 15:39:17RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULE SUBMITTED SHOWS EDGE DISTANCE
 TO BE 3". NEED TO REVISE ANCHOR SPACING AS REQUIRED BY
 EDGE DISTANCE VERSUS SPACING FOR ANCHORS ON SHEET7 OF
 10OF DRAWING 07-085 SUBMITTED (NEW PRODUCT APPROVAL
 SUBMITTED THIS TIME).ANCHOR SPACING IS BASED ON EDGE
 DISTANCE OF 3 1/2". OTHERWISE NEED TO REDUCE THE ANCHOR
 SPACINGBY MULTIPLYINGBY 0.83 SINCE EDGE DISTANCE
 SHOWN ON INSTALLATION SCHEDULE IS 3". (REPEAT
 COMMENT).
  
 2-CLARIFY SHUTTER SPAN SHOWN ON COLUMN 6 OF
 INSTALLATION SCHEDULE.EG: IFOPENING #1 IS 64" HIGH
 HOW COME SHUTTER SPAN IS ONLY 68"IF THE EDGE DISTANCE
 ON COLUMN 8 IS 3".SEE SHEET 4 OF 10 OF DRAWING
 07-085 TO SEE HOW IS THE PANEL SPAN DIMENSIONED.THIS
 COMMENT APPLIES TO ALL OPENINGS.PANEL SPAN DOESN'T
 REFLECT SIZE OF OPENING AND EDGE DISTANCE.ALSO,
 REMEMBER THAT EDGE DISTANCE EXCLUDES STUCCO FINISH OR
 ANY OTHER WALL FINISH. REVISE AS REQUIRED. (REPEAT
 COMMENT).
  
 3- REVISE TAPCON SIZE TO REFLECT MINIMUM EMBEDMENT
 REQUIRED FOR CONCRETE AND CONCRETE BLOCKSUBSTRATE.
 SEE SHEET 7 OF 10FOR MINIMUM EMBEDMENT REQUIRED AND
 REVISE AS REQUIRED. (REPEAT COMMENT).
 NOTE:MINIMUM EMBEDMENT DOESN'T INCLUDE STUCCO
 THICKNESS.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT).
  
 5- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE, OWES
 $32.81 FOR UPDATED VALUATION. (REPEAT COMMENT. FEES NOT
 PAID YET).
  
 6- NEW PRODUCT APPROVAL WAS SUBMITTED.THE MAXIMUM
 PANEL SPAN IS 7'-6".SEE SHEET 8 OF 10 OF DRAWING
 07-085.ACCORDING TO THIS LIMITATION PRODUCT APPROVAL
 IS NOT GOOD FOR OPENINGS 4 THRU 8.NEED TO PROVIDE
 ANOTHER PRODUCT APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By jgomez Date 2008-07-29 Time 16:55 Rev Time 0.00
Received By jgomez Date 2008-07-29 Time 16:55 Sent To PC
Notes
2008-07-29 16:57:25RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULE SUBMITTED SHOWS EDGE DISTANCE
 TO BE 3". NEED TO REVISE ANCHOR SPACING AS REQUIRED BY
 EDGE DISTANCE VERSUS SPACING FOR ANCHORS ON SHEET14
 OF 28.ANCHOR SPACING IS BASED ON EDGE DISTANCE OF 3
 1/2". OTHERWISE NEED TO REDUCE THE ANCHOR SPACINGBY
 MULTIPLYING0.83 SINCE EDGE DISTANCE SHOWN ON
 INSTALLATION SCHEDULE IS 3".
  
 2-PRODUCT APPROVAL SUBMITTED FL7288-R1WITH DRAWING
 06-174 WAS REVISED BY FL7288-R2 WITH DRAWING 07-184.
 NEED TO PROVIDE CURRENT FLORIDA PRODUCT APPROVAL
 FL7288-R2 AND CORRESPONDING DRAWING 07-184.
  
 3- CLARIFY SHUTTER SPAN SHOWN ON COLUMN 5 OF
 INSTALLATION SCHEDULE.EG: IFOPENING #1 IS 64" HIGH
 HOW COME SHUTTER SPAN IS ONLY 43".THIS COMMENT
 APPLIES TO ALL OPENINGS.PANEL SPAN DOESN'T REFLECT
 SIZE OF OPENING. REVISE AS REQUIRED.
  
 4- REVISE ANCHOR SPACING.INSTALLATION SCHEDULE CALLS
 FOR2 1/4" TAPCONS, BUT ANCHOR TYPE HIGHLIGHTED ON
 SHEET13 OF 26IS FOR ALL POINTS SOLID-SET ANCHOR.
 AND ANCHOR TYPE HIGHLIGHTED ON SHEET 15 OF 26IS FOR
 WEDGE-BOLT.REVISE AS REQUIRED TO MATCH ANCHOR SPACING
 FOR TAPCONS AS SHOWN ON INSTALLATION SCHEDULE. (NOTE:
 KEEP THIS IN CONSIDERATION WHEN USING REVISED DRAWING
 07-184. SEE ITEM #2 ABOVE).
  
 5- REVISE TAPCON SIZE TO REFLECT MINIMUM EMBEDMENT
 REQUIRED FOR CONCRETE AND CONCRETE BLOCKSUBSTRATE.
 SEE SHEET 14 OF 26 FOR MINIMUM EMBEDMENT REQUIRED AND
 REVISE AS REQUIRED.
  
 6- INFORMATION SHOWN ON THE SUBSTRATE COLUMN OF
 INSTALLATION SCHEDULE IS NOT CLEAR.IS IT CONCRETE,
 CONCRETE BLOCK OR WOOD?
  
 7-PERMIT APPLICATION AND KEY PLAN SHOW 8OPENINGS,
 WHILE INSTALLATION SCHEDULE ONLY SHOW 7 OPENINGS.
 PROVIDE COMPLETE INFORMATION.
  
 8-PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 9- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE, OWES
 $32.81 FOR UPDATED VALUATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 13:56 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 13:56 Sent To B
Notes
2008-08-08 13:57:13TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-29 Cont ID  
Sent By jgomez Date 2008-07-29 Time 16:57 Rev Time 0.00
Received By jgomez Date 2008-07-29 Time 16:55 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved