Plan Review Details - Permit 08070732
Plan Review Stops For Permit 08070732
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 13:27 Rev Time 0.77
Received By jwitmer Date 2008-09-11 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By jwitmer Date 2008-08-13 Time 07:40 Rev Time 1.22
Received By jwitmer Date 2008-08-13 Time 07:40 Sent To  
Notes
2008-08-13 07:48:03BUILDING PLAN REVIEW
 PERMIT: 08070732
 ADD: 5851 45TH ST
 CONT: T D FARRELL CONSRUCTION
 TEL: (404)661-6221
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 AUGUSST 13,2008
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) CIVIL PLANS ARE SIGNED BUT NOT SEALED.PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) SE-1 INDICATES THE LIGHT POLES AND LIGHTS ARE
 DESIGNED TO A 100 MPH WIND LOAD. PLEASE SEE WIND MAPS
 INDICATE THIS JURISDICTION IS LOCATED WITHIN A 140 MPH,
 3 SECOND GUST WIND ZONE.
 2004 FBC CHAPTER 35 REFERENECED STANDARDS RECOGNIZES
 ASCE 7-02 .ALSO 1603.1.4 WIND DESIGN DATA.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 11:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 15:44 Sent To  
Notes
2008-08-12 15:44:18 
 ** DENIED PLANS.**
  
  
 1) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS PLANS
 SPECIFICALLY STATE POLES ARE TO BE RATED FOR *100
 MPH*.
 PLEASE KNOW THE MINIMUM DESIGN IN THIS AREA FOR THE
 CITY OF WEST PALM BEACH WIND ZONE IS 140MPH 3-SECOND
 GUST.
 THIS IS NOTED FOR INFORMATION ONLY AND NOT A BUILDING
 PLAN REVIEW NOTE.
  
 2) NOTE: PLEASE SEE *C* SHEETS WHICH ONLY CONTAIN A
 SIGNATURE AND DO NOT CONTAIN ANY RAISED SEAL AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE PROVIDE SITE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.ABC.1.3
  
 4) NOTE: PLEASE PROVIDE INFORMATION FOR LIGHTING
 CONTROLS PER 13-415.1.ABC.1.4.
  
 5) NOTE: PLEASE PROVIDE VOLTAGE DROP PER
 13-413.1.ABC.1.1, .1.2
  
 6) NOTE: RECORD PLANS NEED TO INDICATE THE NEW ADDED
 LOADS TO EXISTING SERVICE AND EQUIPMENT.
 NEC 220
 FBC 106.5, 106.1.1
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-09-17 Cont ID  
Sent By rchokshi Date 2008-09-17 Time 11:06 Rev Time 0.00
Received By rchokshi Date 2008-09-17 Time 11:03 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-09-04 Cont ID  
Sent By rchokshi Date 2008-09-04 Time 11:25 Rev Time 0.00
Received By rchokshi Date 2008-09-04 Time 11:11 Sent To  
Notes
2008-09-04 11:25:32JEFF RENAULT APPROVED STORM WATER REQUIREMENTS PER HIS
 E-MAIL OF 08-29-08, AT 2:18PM.
 MANNY GONZALEZ APPROVED WATER & SEWER REQUIREMENTS PER
 HIS E-MAIL OF 08-29-08 AT 4:03PM, ALSO MANNY'S E-MAIL
 OF 09/15/08 APPROVED THE FOLLOWING BOND REQUIREMENTS
  
 FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-08-21 Cont ID  
Sent By rchokshi Date 2008-08-21 Time 11:27 Rev Time 0.00
Received By rchokshi Date 2008-08-21 Time 11:15 Sent To  
Notes
2008-08-21 11:25:50FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS & DETAILS OF FILTER FABRIC USED FOR
 CATCH BASINS FOR POLLUTION PREVENTION . HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS TO 1000
 45TH STREET FOR THEIR APPROVAL BEFORE WE ISSUE A
 PERMIT.
  
 10. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-16 Cont ID  
Sent By mwennerg Date 2008-09-16 Time 09:34 Rev Time 0.00
Received By mwennerg Date 2008-09-16 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2008-08-22 Time 13:06 Sent To  
Notes
2008-08-22 13:22:43***DENIED***
  
 1) MINIMUM HEIGHT FOR OVERHANGS, CANOPIES ETC SHALL BE
 MINIMUM 13'-6" CLEARANCE TO ALLOW FOR EMERGENCY
 VEHICULAR APPARATUS.
  
 2) FIRE HYDRANTS, AND OTHER FIRE PROTECTION EQUIPMENT
 MAY REQUIRE PROTECTION AGAINST POSSIBLE MECHANICAL
 DAMAGE. PROPER CLEARANCES SHALL BE MAINTAINED.
  
 3) ALL OTHER GENERAL ACCESS REQUIREMENTS TO COMPLY WITH
 NFPA 1, 2003 CHAPTER-18.
  
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 14:21 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 14:21 Sent To  
Notes
2008-09-03 14:28:18TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 13:26 Rev Time 0.00
Received By mwennerg Date 2008-07-29 Time 08:36 Sent To  
Notes
2008-07-29 08:36:43TO "COMM" BD#35

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-12 Cont ID  
Sent By jroach Date 2008-09-12 Time 10:54 Rev Time 0.00
Received By jroach Date 2008-09-12 Time 10:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By bpowell Date 2008-09-10 Time 10:40 Rev Time 0.00
Received By bpowell Date 2008-09-10 Time 10:39 Sent To  
Notes
2008-09-10 10:52:371. PLEASE MAKE SURE THAT ALL OF THE PLANS THAT ARE
 WITHIN THE PACKET ARE CONSISTENT AND MATCH WHAT WAS
 APPROVED DURING THE MINOR AMENDMENT. FOR EXAMPLE THE
 EMPLOYEE PARKING ON SHEET C1 DOES NOT MATCH WHAT IS
 SHOWN ON C4.
  
 2. PLEASE INCLUDE A PARKING DETAIL INDICATING THAT ALL
 PARKING SPACES WILL BE DOUBLE STRIPPED. PER SECTION
 94-485(G) REQUIRED OFF-STREET PARKING SHALL BE
 DELINEATED BY FOUR INCH WHITE DOUBLE STRIPED LINES.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT
 BOBBY POWELL JR., PLANNER, (561) 822-1401,
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By bpowell Date 2008-08-11 Time 17:21 Rev Time 0.00
Received By bpowell Date 2008-08-11 Time 17:21 Sent To  
Notes
2008-08-11 17:23:361.A MINOR AMENDMENT MUST BE COMPLETED BEFORE
 SUBMITTING FOR BUILDING PERMIT.
  
 2.THE SITE PLAN SHALL REFLECT THE CONDITIONS SHOWN ON
 THE SITE.
  
 FOR ANY QUESTIONS OR COMMENTS PLEASE CONTACT; BOBBY
 POWELL JR., [email protected], 822-1401