Plan Review Details - Permit 08070728
Plan Review Stops For Permit 08070728
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-08-01 Cont ID  
Sent By mperson Date 2008-08-01 Time 15:25 Rev Time 0.00
Received By mperson Date 2008-08-01 Time 15:25 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-07-28 Cont ID  
Sent By mperson Date 2008-07-28 Time 08:53 Rev Time 0.00
Received By mperson Date 2008-07-28 Time 08:53 Sent To I
Notes
2008-07-28 09:35:18GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET THE CITY OF WEST PALM BEACH GAS
 PERMIT APPLICATION REQUIREMENTS FOR CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRICDOES NOT SHOW
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 THAT DO NOT INDICATE CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 *NOTE: SOME PIPING MATERIAL AND PIPE SIZES ARE NOT
 CLEARLY BEING INDICATED. CLEARLY SIZE THE PIPING
 MANIFOLD AT THE GAS METER, RISER TO THE BBQ, RISER TO
 THE POOL HEATER MUST BE 1 INCH (1") AND CAN BE REDUCED
 AT THE HEATER. PIPING FROM THE METER OUTLET TO THE POOL
 HEATER TEE MUST BE 1-1/4 INCH (1-1/4").
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THE LONGEST LENGTH OF 13'-6" IS INCORRECT ON
 THE DRAWING. UNTIL COMMENT #1 IS COMPLETELY ADDRESSED
 AND THE RESUBMITTED PLANS ARE CORRELATED TO REFLECT THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE THE
 GAS PLANS WILL NOT PASS PLAN REVIEW. TABLES BEING USED
 FOR PLAN REVIEW ARE 401.4(2) AND 401.4(20), PLEASE
 REFERENCE THESE TABLES ATTACHED TO THE COMMENTS TO HELP
 IN THE RESUBMITTAL.
  
 4. PLEASE CLEARLY INDICATE ON THE RESUBMITTED DRAWINGS
 IF THE TANKLESS WATER HEATER IS AN INTERIOR OR AN
 EXTERIOR MODEL. PER FBC-2004 FUEL GAS SECTION 401.1
 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 10:01 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 10:01 Sent To G
Notes
2008-08-01 10:01:37TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-28 Cont ID  
Sent By mperson Date 2008-07-28 Time 09:35 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 16:34 Sent To PC
Notes
***NONE***