Plan Review Details - Permit 08070713
Plan Review Stops For Permit 08070713
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-16 Cont ID  
Sent By mjacobs Date 2008-09-16 Time 07:24 Rev Time 0.00
Received By mjacobs Date 2008-09-16 Time 07:07 Sent To PC
Notes
2008-09-16 07:07:27PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-11 Cont ID  
Sent By mjacobs Date 2008-09-11 Time 15:36 Rev Time 0.00
Received By mjacobs Date 2008-09-11 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By mjacobs Date 2008-08-20 Time 15:44 Rev Time 0.00
Received By mjacobs Date 2008-08-20 Time 14:08 Sent To PC
Notes
2008-08-20 15:44:36 
 BUILDING PLAN REVIEW
 PERMIT: 08070713
 ADD: 2491 OKEECHOBEE BLVD SUITE D
 CONT:?
 TEL: (561)635-0097
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)SHEET A2.01 FLOOR PLAN NEEDS TO INDICATE THE
 DIMENSIONS OF THE NEW UTILITY AND WAX ROOM. THE
 DIMENSION OF THE HALLWAY SHALL ALSO BE SHOWN ON THE
 PLANS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN TO A MINIMUM 1/8 INCH SCALE. 106.1.1
  
 6)SHOW THE LAYOUT OF THE EXISTING SPRINKLER HEADS ON
 THE REFLECTED CEILING PLANS SHEET A6.01.
  
 NOTE: BEFORE A PERMIT CAN BE ISSUED A CONTRACTOR MUST
 BE SIGNED ON THE APPLICATION AND A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE APPLICATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT EXCLUDING LAND. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-04 Cont ID  
Sent By btrobaug Date 2008-09-04 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2008-09-04 Time 15:17 Sent To  
Notes
2008-09-04 15:33:48 
  
 ELECTRICAL ON SHEET A6.01 IS NOTED AS "EXISTING"./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By btrobaug Date 2008-08-08 Time 09:49 Rev Time 0.00
Received By btrobaug Date 2008-08-08 Time 09:34 Sent To  
Notes
2008-08-08 09:37:57 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} WHEN SUBMITTING FOR PERMIT THE ARCHITECTURAL FIRM
 MUST DISPLAY THE CERTIFICATE OF AUTHORIZATION ON THE
 TITLE BLOCK PER 481.221 (8).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-15 Cont ID  
Sent By mawillia Date 2008-09-15 Time 13:47 Rev Time 0.00
Received By mawillia Date 2008-09-15 Time 13:36 Sent To B1
Notes
2008-09-15 13:47:03*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A2.01 AND A6.01 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By mwennerg Date 2008-08-12 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2008-08-12 Time 14:16 Sent To  
Notes
2008-08-12 14:19:28***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #1 REGARDING
 REQUIREMENTS FOR PLANS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. PLEASE
 MAKE CORRECTION UNDER LIFE SAFETY SUMMARY ON SHEET
 A-2.01.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:25 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:25 Sent To  
Notes
2008-09-03 16:27:27TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 15:29 Rev Time 0.00
Received By btrobaug Date 2008-07-28 Time 10:40 Sent To  
Notes
2008-09-04 15:31:41 
 NO OUT FOR THE I STOP ON FIRST REVIEW, I ADDED THAT OUT
 9/4/08./WRT.
2008-08-05 09:19:23TO "BOB"#17
2008-07-28 10:40:33WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By tgordon Date 2008-08-05 Time 09:51 Rev Time 0.30
Received By tgordon Date 2008-08-05 Time 09:50 Sent To  
Notes
2008-08-05 09:51:32NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-05 Cont ID  
Sent By mperson Date 2008-09-05 Time 11:12 Rev Time 0.00
Received By mperson Date 2008-09-05 Time 11:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-06 Cont ID  
Sent By mperson Date 2008-08-06 Time 11:02 Rev Time 0.00
Received By mperson Date 2008-08-06 Time 11:02 Sent To  
Notes
2008-08-06 12:00:20PLUMBING PLAN REVIEW:
 DENIED, NOTE **FOR PLAN REVIEW ONLY NOT FOR PERMIT**:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1: PLEASE CORRELATE THE BRANCH DRAINS TO THE
 PEDICURE SPA. THE PLUMBING SANITARY PLAN INDICATES 2"
 FOR THE DRAIN, HOWEVER THE SANITARY ISOMETRIC RISER IS
 INDICATING 3". PER FBC-2004 PLUMBING SECTION 701.1
 SCOPE.
  
 2. SHEET P1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 CORRECT THE FOLLOWING ITEMS PER THE FBC-2004 PLUMBING
 SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE FOR ALL WAST PIPING AND
 WATER-SEAL FIXTURE TRAPS. NOTE THE WASHING MACHINE
 STACK AND WATER-SEAL TRAP ARE NOT SIZED (WASHING
 MACHINE STACK SHALL BE 3" AND THE TRAP SHALL BE 2", PER
 SECTION 406.3) AS WELL AS THE WATER-SEAL TRAPS FOR THE
 LAVATORIES AND DRINKING FOUNTAIN ARE NOT SIZED (MINIMUM
 SIZE TRAP FOR THE LAVS AND DRINKING FOUNTAIN IS 1-1/4",
 PER TABLE 709.1). PER SECTION 701.1 SCOPE AND (W.P.B.
 AS AMENDED) SECTION 106.3.5.1.3 PLUMBING (13).
  
 B} CLEARLY INDICATE THAT THE PEDICURE SPA CHAIRS AS
 BEING DRAINED INDIRECTLY INTO EITHER A FLOOR SINK OR
 HUB DRAIN. PER SECTION 801.1 SCOPE, SECTION 802.2.2 AIR
 BREAK, SECTION 802.3 WASTE RECEPTORS, AND SECTION
 802.3.2 OPEN HUB WASTE RECEPTOR.
  
 C} CLEARLY INDICATE THE STUDER VENT (AIR ADMITTANCE
 VALVE OR A.A.V.) TO BE 4" ABOVE THE HORIZONTAL BRANCH
 DRAIN OF FIXTURE DRAIN BEING VENTED. PER SECTION 917.4
 LOCATION.
  
 D} CLEARLY INDICATE THE STUDER VENT (A.A.V.) TO BE 2"
 NOT 2: PER SECTION 901.1 SCOPE.
  
 E} CLEARLY INDICATE THAT THE STUDOR VENT (A.A.V.)
 SHALL BE PROVIDED WITH ACCESS AND THAT THE VALVE IS
 LOCATED WITHIN A VENTILATED SPACE THAT ALLOWS AIR TO
 ENTER THE VALVE. IT APPEARS THAT THE A.A.V. IS LOCATED
 IN THE PLUMBING CHASE. PER SECTION 917.5 ACCESS AND
 VENTILATION.
  
 3. SHEET P1 PLUMBING SANITARY PLAN INDICATES THE 3/4"
 P & T DRAIN TO MS. WHAT IS A MS? MS IS NOT INDICATED ON
 SHEET A1.01 OR P2 ABBREVIATIONS, PLEASE CLARIFY THIS.
 PLEASE NOTE THAT SHEET P2 CLEARLY INDICATES THE P & T
 VALVE TERMINATION TO THE EXTERIOR OF BUILDING. PER
 SECTION 501.1 SCOPE AND SECTION504.6.1 DISCHARGE.
  
 4. SHEET P2 PLUMBING SPECIFICATIONS NOTE #8 STATES THE
 FOLLOWING "ALL OTHER FIXTURES & SUPPLIES TO HAVE AIR
 CHAMBERS" PLEASE KNOW THAT AIR CHAMBERS ARE NOT
 APPROVED BY THE FBC-2004 PLUMBING CODE SECTION 604.9
 WATER HAMMER AND SHOULD BE DELETED FROM THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]