Plan Review Details - Permit 08070710
Plan Review Stops For Permit 08070710
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-05-08 Cont ID  
Sent By shill Date 2009-05-08 Time 15:01 Rev Time 0.00
Received By shill Date 2009-05-08 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-26 Cont ID  
Sent By mjacobs Date 2008-12-26 Time 10:17 Rev Time 0.00
Received By mjacobs Date 2008-12-26 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-08 Cont ID  
Sent By mjacobs Date 2008-12-08 Time 10:18 Rev Time 0.00
Received By mjacobs Date 2008-12-08 Time 10:18 Sent To  
Notes
2008-12-08 10:17:05BUILDING PLAN REVIEW
 PERMIT: 08070710
 ADD: 480 HIBISCUS ST. #103
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-8-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) OK
  
 **THE SHOP DRAWING STAMP SHALL BE ON THE FRONT OF EACH
 SHEET NOT THE BACK.**
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
 THE REVIEW STAMP IS MISSING ON PLANS.
  
 5) OK
 7) OK
 8) OK
 NEW:
 A) OK
 B) OK
 C) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-07 Cont ID  
Sent By mjacobs Date 2008-11-07 Time 07:52 Rev Time 0.00
Received By mjacobs Date 2008-11-07 Time 07:52 Sent To  
Notes
2008-11-07 07:49:42BUILDING PLAN REVIEW
 PERMIT: 08070710
 ADD: 480 HIBISCUS ST. #103
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-7-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 ** PARTIALY ADDRESSED. PLEASE READ THE NOTE BELOW AND
 SUPPLY ALL THE INFORMATION REQUESTED.**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD.
  
 **NOT ADDREDDED ON THE PLANS**
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
 THE REVIEW STAMP IS MISSING ON PLANS.
  
 ** RESPONSE NOTED, HOWEVER IF THIS IS NEW CONSTRUCTION
 TO A SPACE OR BUILDING WHICH HAS NOT RECEIVE A
 CERTIFICATE OF OCCUPANCY, AN ALTERATION LEVEL IS NOT
 RREQUIRED. AT THIS TIME OF REVIEW A CERTIFICATE OF
 OCCUPANCY IS NOT ISSUED TO THIS BUILDING.**
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; FBC(EXISTING) 305.1. IS THIS THE
 CASE FOR THIS PROJECT? IF NOT PLEASE SEE SECTION 304 OF
 THE FBC (EXISTING) ALTERATION LEVEL 2.
  
 7) OK
 8) OK
  
 NEW:
 A) PROVIDE A DOOR SCHEDULE SHOWING THE TYPE AND SIZE OF
 DOORS TO BE INSTALLED AT THEIR RESPECTIVE LOCATION
 ALONG WITH THE INTERIOR FINISH SCHEDULE THE SHOW ALL
 WALL FINISHES. SHEET A.2 SHOWS TWO SINGLE HUNG DOORS
 ACCORDING TO DETAIL #3, HOWEVER, THERE ARE TWO DETAILS
 REFERENCING THE #3. ON SHEET M1 THE DOORS ARE SHOWN AS
 DOUBLE SWING DOORS. CLARIFY. THE DETAIL FOR THE DRYWALL
 CEILING ON THE FIRST FLOOR IS MISSING FROM THE PLANS.
  
 B) SHEET A.4 NOTE #10 INDICATES THE FINISH DRYWALL TO
 BE FINISHED WITH ENAMEL PAINT: THEN REFERS TO FINISH
 SCHEDULE WHICH WAS NOT SUBMITTED. FBC 1210.2 WALL
 WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. SHOW COMPLIANCE.
  
 C) SHEET A.2. PROVIDE DETAIL DRAWINGS SHOWING THE
 STRUCTURAL SUPPORT FOR THE SUSPENDED WOOD CEILING AND
 THE SUSPENDED TRACK LIGHTING. ADDITIONAL INFORMATION IS
 REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-15 Cont ID  
Sent By mjacobs Date 2008-08-15 Time 16:20 Rev Time 0.00
Received By mjacobs Date 2008-08-15 Time 14:45 Sent To  
Notes
2008-08-15 16:20:54BUILDING PLAN REVIEW
 PERMIT: 08070710
 ADD: 480 HIBISCUS ST. #103
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD.
  
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
  
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; FBC(EXISTING) 305.1. IS THIS THE
 CASE FOR THIS PROJECT? IF NOT PLEASE SEE SECTION 304 OF
 THE FBC (EXISTING) ALTERATION LEVEL 2.
  
 7) FBC 1013.3 (EXCEPTION #5) SHOW THE COMMON PATH OF
 EGRESS TRAVEL WHICH SHALL BE 100 FEET IN BUILDINGS WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED THROUGHOUT.
  
 8) FBC 1009.5 ALL STAIRS SHALL BE BUILT OF MATERIALS
 CONSISTENT WITH THE CONSTRUCTION TYPE OF THE BUILDING
 WHICH IS TYPE IB. ONLY THE HANDRAILS CAN BE CONSTRUCTED
 OF WOOD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 11:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 08:39 Sent To PC
Notes
2009-05-15 08:40:49REDLINED PLANS.
 THERE IS NO REV #6 AS SHOWN IN TITLE BLOCKS.
  
 THE EM LT FIXTURE SHOWN IN SPACE WHICH WAS FROM
 ORIGINAL BASE BUILDING SHELL SPACE IS TO BE DELETED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-05-07 Cont ID  
Sent By dpalmer Date 2009-05-07 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2009-05-07 Time 08:43 Sent To  
Notes
2009-05-07 08:44:04**DENIED PLANS**
  
  
  
 1) NOTE: PLEASE SEE THE TITLE BLOCKS WHICH INDICATE A
 REVISION #6 HOWEVER THE PLANS ARE NOT LABELED WITH ANY
 REVISION #6.
 PLEASE COORDINATE ALL PLANS AND REVISIONS.
 FBC 106.1.1, 106..5 FOR CLARITY AND COORDINATION OF
 RECORD PLANS.
 NEC 2005 AS THERE ARE REVISIONS TO PLANS WHICH ARE NOT
 IDENTIFIED. SEE COMMENT #2.
  
 2) NOTE: PLANS NOW INDICATE AN EXISTING EMERGENCY LIGHT
 FIXTURE TO REMAIN. PLEASE INDICATE WHERE THE
 DISCONNECTING MEANS OF THIS BASE BUILDING BRANCH
 CIRCUIT IS LOCATED. IT IS BEING *ASSUMED* THIS IS PART
 OF THE BASE BUILDING CIRCUIT AS IT WAS REQUIRED TO BE
 INSTALLED BECAUSE IT WAS A SHELL SPACE ON ORIGINAL
 PLANS. THE FIXTURES AND WIRING WHICH WERE INSTALLED FOR
 SHELL SPACES WERE TO BE REMOVED OR BE CONTROLLED FROM
 TENANT SPACE ELECTRICAL SYSTEMS. IS THIS ELECTRICAL IN
 ONE TENANT SPACE FED FROM TWO COMPLETELY SEPARATE
 SERVICES?
 THIS IS A HAZARD IF THIS IS INDEED HOW THIS IS
 INSTALLED AND WIRED.
 PLEASE REVISE PLANS AND CLEAR UP WHAT THE DESIGN IS
 BEING PROPOSED. AS NOTED ABOVE, THE EMERGENCY LIGHT
 FIXTURES PLANS ON ORIGINAL SHELL TENANT SPACES WERE
 REQUIRED ONLY TO BE FED FROM BASE BUILDING UNTIL
 SEPARATE TENANTS WHICH ARE FED FROM A SEPARATE SERVICE
 ARE BUILT OUT.
 240.24B, 210.25
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 11:51 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 11:51 Sent To  
Notes
2008-12-26 11:51:29** PROVISO**
  
 1) NOTE: THE FIXTURE TYPES AND NUMBER OF FIXTURES HAVE
 NOW BEEN REVISED. THE LIGHTING CALCULATION TABLE NOW
 INDICATE AN ADDITIONAL ALLOWANCE FOR DISPLAY AREAS.
 HOWEVER PLEASE SEE 13-415.2.B.2. THE FOLLOWING IS
 EXTRACTED DIRECTLY FROM THE CODE. THIS IS NOT A RETAIL
 OCCUPANCY.
  
 **
 FOR LIGHTING EQUIPMENT INSTALLED IN RETAIL SPACES THAT
 IS SPECIFICALLY DESIGNED AND DIRECTED TO HIGHLIGHT
 MERCHANDISE, PROVIDED THAT THE ADDITIONAL LIGHTING
 POWER SHALL NOT EXCEED:
 (1) 1.6 WATTS PER SQUARE FOOT TIMES THE AREA OF
 SPECIFIC DISPLAY OR
 **
  
 ** PLEASE REVISE TO REMOVE ADDITIONAL ALLOWANCES.
  
 PLEASE SEE THE FIXTURE LEGEND WHICH GIVES THE FIXTURE
 COUNT AND WATTAGES. THERE ARE MORE TYPE *C* FIXTURES ON
 PLANS THAN ON TABLE. THE TOTAL ALLOWANCE BASED ON THIS
 SPACE AND OCCUPANCY IS 2596. THE DESIGN WATTAGE WHICH
 IS BASED ON FIXTURES ON PLANS AND WATTAGES SHOWN IS
 2584.
 AS THIS DOES NOT EXCEED ALLOWANCE PER THE FBC A PROVISO
 TO REVISE PLANS AT LATER DATE IS GIVEN.
 ** IF THERE ARE OTHER REVISIONS PLEASE REVISE BEFORE
 ROUGH. IF THESE BECOME THE ONLY REVISED ITEM PLEASE
 REVISE BEFORE FINAL.
  
 13-415.2,13-415.2.ABC.1.1, .1.2. ETC
  
 2) NOTE: SIGN REQUIRED FOR DOORS AT TRANSFORMER
 LOCATION.
  
 *ELECTRICAL ROOM/ NO STORAGE*
  
 OR WORDS TO THAT AFFECT. 240.24,110.26
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-09 Cont ID  
Sent By dpalmer Date 2008-12-09 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2008-12-09 Time 10:47 Sent To  
Notes
2008-12-12 08:35:11*** PER PREVIOUS NOTICE TO REPEAT COMMENTS FOR CODE
 COMPLIANCE, THE CODE SECTIONS WERE REPEATED THREE OR
 MORE TIMES. THE CODE SECTIONS FOR FBC CHAPTER 13 FOR
 LIGHTING COMPLIANCE ALONG WITH OTHER SECTIONS WERE
 REPEATED AND COMPLIANCE HAS STILL NOT BEEN ACHEIVED. TH
 IS A STATUTORY REQUIREMENT AND IS REQUIRED. THIS IS NOT
 AN OPTIONAL FEE TO BE ASSESED. THE AMOUNT OF $960 WILL
 BE DUE.
 ONE COPY OF ELECTRICAL PLANS WERE RETAINED BY THIS
 OFFICE AS REQUIRED.
2008-12-09 10:48:20 
 ** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE BE SURE ALL SETS ARE PLACED TOGETHER IN
 COMPLETE SETS WHEN RESUBMITTING. PLEASE REMOVE ANY
 OLD/VOIDED SHEETS.
  
 2) NOTE: PLANS SUBMITTED WHICH WERE REVISED ON 11/25/08
 ARE ACTUALLY SIGNED, DATED AND SEALED WITH A DATE OF
 10/25/08. THIS IS NOT POSSIBLE.
 FS 471.025
  
 3) NOTE: PLANS SHALL CONTAIN THE * SHOP DRAWING REVIEW
 STAMP* AND SIGNATURE OF THE BASE BUILDING DESIGNERS OF
 RECORD ON EACH AND EVERY SHEET. THIS IS REQUIRED TO BE
 ON THE PLANS AND NOT ON THE BACK OF THE SHEETS. RECORD
 PLANS ARE SCANNED AND SCANNING OF THE BACK OF THE
 SHEETS WHICH ARE *BLANK* DOES NOT SHOW ACTUAL RECORD OF
 ANYTHING.
 PLEASE ALSO BE SURE THESE STAMPS ARE SIGNED BY THE
 RESPONSIBLE DESIGNER OF RECORD. THE SIGNATURES FOR BOTH
 PERSONS AS STAMPED ARE NOT FROM THE DESIGNERS OF
 RECORD.
 FS481.221,471.025
  
 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1,.1.2 FOR
 LIGHTING POWER ALLOWANCES. THE AMOUNT OF FIXTURES AND
 WATTAGE ON PLANS EXCEEDS MAXIMUM ALLOWANCE UNDER THE
 ENERGY CODE. PLEASE SEE EXAMPLES SUCH AS FIXTURE *A*.
 THE AMOUNT OF FIXTURES ON PLANS IS GREATER THAN THE
 AMOUNT IN THE CALCULATIONS. THIS IS ONE FIXTURE AND
 THERE ARE OTHERS WHICH ARE OVER. THE DESIGN WATTAGE ON
 PLANS COMES TO OVER 3000 WATTS WHEN ALLOWANCE BASED ON
 THE 1236 SQ FT IS 2595.
  
 5) NOTE: PLEASE SEE 11-4.28.3(4). PLANS NOTE THE STROBE
 75 FLASH RATE. THIS SHOULD BE 75CD/ OR CANDELA. THE
 FLASH RATE IS DIFFERENT.
  
 6) NOTE: PLEASE BE SURE THE SUITE OR UNIT NUMBER IS
 LISTED ON THE TITLE BLOCKS OF EACH SHEET. THIS CAN BE
 PRINTED ON ANY SHEETS WHICH DO NOT NEED TO BE REVISED.
 FAC 61G1-16.004, 61G15-23.002, FBC 106.5.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 11:26 Sent To  
Notes
2008-11-10 11:26:45 
  
  
 ** DENIED 2ND REVIEW **
  
  
  
 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF
 OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED
 BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A
 *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE
 BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT
 BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL
 REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: THE PLANS STILL INDICATE EXISTING RETAIL
 HOWEVER THIS IS NOT POSSIBLE AS THE BUILDING CONTAINS
 *SHELL* SPACES FOR FUTURE. THE PLANS NEED TO BE
 ADJUSTED ACCORDINGLY.
 FBC 301.1
 FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD
 PLANS.
  
 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS ARE NOT COMPLETE AT THIS TIME. PLEASE SEE
 THE FIXTURE LEGEND NOW SUBMITTED IS NOT YET COMPLETE.
 AN EXAMPLE IS THE *Q* FIXTURE. THIS ONE EXAMPLE IS
 GIVEN AS A BENEFIT.
 PLEASE SEE SECTIONS OF CODE BELOW WHICH WERE GIVEN ON
 PREVIOUS REVIEW. PLEASE SEE TRACK LIGHTING IN THE FBC.
 THE CODE REQUIRES ANY LINE VOLTAGE FIXTURES TO BE
 FIGURED AT THE MAXIMUM VA PER FIXTURE OR 30VA PER
 LINEAR FT OF TRACK WHICH EVER IS GREATER. IF THESE ARE
 LOW VOLTAGE TYPES THEN THE VA IS BASED ON THE MAXIMUM
 VA OF THE TRANSFORMER. THE FIXTURE LEGEND AS SUBMITTED
 HAS A N/A NEXT TO FIXTURE AND ASSOCIATED EQUIPMENT.
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: THE RISER SHOWS WHAT APPEARS TO BE THE
 DISCONNECT AND TRANSFORMER WHICH WOULD BE LOCATED IN
 THE STORAGE CLOSET ON MEZZANINE LEVEL WHICH IS NOT
 PERMITTED.
 THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON
 MEZZANINE LEVEL AND ONLY SHOWS THE PANEL.
 PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL
 ACCORDINGLY TO RISER AND PANEL IDENTIFICATION.
 PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC
 THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET
 WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE
 MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD.
 PLEASE ADJUST, RE-LOCATE ETC.
  
 6) NOTE: FROM PREVIOUS REVIEW:
 PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND
 HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3.
  
 7) NOTE: PLEASE SEE 410.5, 410.6 ETC AS THE TYPE *Q*
 FIXTURE MAY NOT BE LOCATED NEAR COMBUSTIBLES.
  
 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN
 AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS
 ONLY A NOTICE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By dpalmer Date 2008-08-08 Time 09:42 Rev Time 0.00
Received By dpalmer Date 2008-08-08 Time 09:42 Sent To  
Notes
2008-08-08 09:42:44 
 ** DENIED REVIEW **
  
  
  
 1) NOTE: THE BASE BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT
 PERMITTED BEFORE THE C OF O OF BASE BUILDING ARE TO
 CONTAIN A *SHOP DRAWING* REVIEW STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD ON EACH
 RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR
 BUILD OUT BEFORE THE C OF O IS ISSUED ON BASE BUILDING
 WILL REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS IN
 PHOTO-METRICS ON STAIRS PER NFPA-101 2003, 7.8.1.3,
 7.9.2.1, .2.2.
  
 4) NOTE: PLEASE INDICATE ALL LIGHTING CONTROLS REQUIRED
 PER FBC 13-415.1.ABC.1.1,.1.2 AND .1.3.
 THE SYMBOL LEGEND DOES INDICATE SOME OCCUPANCY SENSOR
 TYPE DEVICES HOWEVER NONE OF THIS DEVICE S IS ON PLANS.
 IN FACT THE PLANS ONLY INDICATE STANDARD SWITCHING
 DEVICES WHICH ARE NOT PERMITTED.
 PLEASE PROVIDE ALL MAXIMUM TIMES ON ALL DEVICES.
 PLEASE BE SURE TO SEE NFPA-101 7.8.1.2.2 AND FBC
 1006.1.2 AS ANY OCCUPANCY SENSOR FOR ANY EGRESS
 LIGHTING SHALL BE * FAIL SAFE ON*.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE SUBMIT THE FIXTURE SCHEDULE/LEGEND.
 PLEASE SEE THE SECTIONS OF THE CODE ABOVE. THE WATTAGE
 TO BE USED IS BASED ON THE FIXTURE WATTAGE NOT THE LAMP
 WATTAGE AS STATED ON PLANS.
 PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH A
 FIXTURE LEGEND ETC SOME OF THESE ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DETERMINED AT THIS TIME.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP PER
 13-413.1.ABC.1.2 FOR CU.
  
 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR ALL
 CIRCUITS TO SPECIFIC AREAS AND LOCATIONS.
 408.4
  
 8) NOTE: PLEASE COORDINATE ALL CIRCUITS. PLEASE SEE ONE
 FOR EXAMPLE AS L-10 IS INDICATED ON PANEL SCHEDULE AS
 *MEZZANINE* YET THIS IS ALSO SHOWN ON PLANS TO THE
 REFRIGERATOR.
 NO DEDICATED CIRCUIT SHOWN FOR REFRIGERATOR.
 PLEASE SEE SOME OTHER CIRCUITS SHOWING A QUESTION MARK
 NEXT TO THE PANEL DESIGNATION ON PLAN.
 408.4, 240.4, ETC
  
 9) NOTE: PLEASE VERIFY RISER AS THE GUTTER IS INDICATED
 AS RAIN TIGHT? PLEASE ALSO INDICATE THE SIZE/AMPERAGE
 OF THE GUTTER PROVIDED.
 PLEASE INDICATE A FLOATING NEUTRAL ON THE NEW METER AS
 THE MAIN FOR TENANT SHOWN WILL BE AFTER A MEANS OF
 DISCONNECT FOR SERVICE.
 250.24, 250.6
  
 10) NOTE: PLEASE SEE 600.5 AS THE LOAD FOR A SIGN
 CIRCUIT IS REQUIRED TO BE FIGURED AT 1200VA. THIS WOULD
 BE 10AMPS ON THE CIRCUIT.
 **
  
 11) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW
 RECEPTACLES.
 PLEASE ALSO SEE 220.43
  
 12) NOTE: PLEASE INCLUDE LOADS FOR TRACK LIGHTING PER
 220.43
  
 13) NOTE: BASE BUILD OUT PLANS SHALL INCLUDE DEVICES TO
 COMPLY WITH THE FIRE CODES, SUCH AS NFPA-1, NFPA-72 AND
 FBC 2004 W/2007 REVISIONS.
 PLEASE SEE FBC 11-4.28 (ALL) AND INDICATE REQUIRED
 DEVICES ACCORDINGLY
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET ON
 DESIGN SHEETS THERE MAY VERY WELL BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-05-05 Cont ID  
Sent By mawillia Date 2009-05-05 Time 15:11 Rev Time 0.00
Received By mawillia Date 2009-05-05 Time 14:26 Sent To  
Notes
2009-05-05 15:11:07*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET A.1 (OF THE SUBMITTED PLAN SET)
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-26 Cont ID  
Sent By mwennerg Date 2008-12-26 Time 14:02 Rev Time 0.00
Received By mwennerg Date 2008-12-26 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-12-10 Cont ID  
Sent By mawillia Date 2008-12-10 Time 12:04 Rev Time 0.00
Received By mawillia Date 2008-12-10 Time 11:34 Sent To  
Notes
2008-12-10 12:03:29*****UNSAT*****
  
 PLEASE BE ADVISED THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN SATISFIED; HOWEVER THE APPROPIATE SHEETS TO BE
 FIRE-STAMPED WHEN THE MATTER WITH THE SHOP DRAWING
 STAMP (SEE BUILDING AND ELECTRICAL EXAMINERS' COMMENT)
 HAS BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 11:38 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 11:38 Sent To  
Notes
2008-11-12 11:43:59***DENIED***
  
 1) ON SHEET A.3- CAPTION 1, CLARIFY AS TO WHETHER THE
 ADDRESS VERBAGE IS FOR BUILDING OR THE SUITE. A.3 CAN
 NOT BE FOUND WITH INITIAL SUBMITTAL.
  
 2) SHOW LAYOUT OF THE SPRINKLER HEADS FOR THE FLOOR
 SPACE. THESE HEADS MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN. NO ATTACHED ENGINEERED SPRINKLER DRAWINGS
 FOUND WITH THIS SUBMITTAL.
  
 PLANS DON'T SEEM TO CORRELATE WITH RESPONSE LETTER.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By mawillia Date 2008-08-13 Time 13:59 Rev Time 0.00
Received By mawillia Date 2008-08-13 Time 13:51 Sent To  
Notes
2008-08-13 13:59:40*****DENIED*****
  
 PLEASE BE ADVISED THAT THEBASE BUILDING DOES NOT HAVE A
 CERTIFICATE OF OCCUPANCY
  
 1. ON SHEET A.3 - CAPTION 1, CLARIFY AS TO WHETHER THE
 ADDRESS VERBAGE IS FOR THE BUILDING OR THE SUITE.
  
 2. SHOW A LAYOUT OF THE SPRINKLER HEADS FOR THE FLOOR
 SPACE. THESE HEADS MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 08:19 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 08:19 Sent To  
Notes
2009-07-01 08:20:13SENT TO D.PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 14:17 Sent To  
Notes
2009-04-29 14:17:34TO B-13

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 15:44 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 15:44 Sent To  
Notes
2008-12-19 15:45:04TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-01 Cont ID  
Sent By adarroug Date 2008-12-01 Time 15:25 Rev Time 0.00
Received By adarroug Date 2008-12-01 Time 15:25 Sent To  
Notes
2008-12-01 15:25:44TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 14:50 Sent To  
Notes
2008-11-03 14:56:48TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-08-20 Time 14:46 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 11:56 Sent To  
Notes
2008-08-05 09:23:58TO "BOB"#18
2008-07-28 11:57:16WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-07-14 Cont ID  
Sent By rregueir Date 2009-07-14 Time 16:47 Rev Time 0.00
Received By rregueir Date 2009-07-14 Time 16:47 Sent To PC
Notes
2009-07-14 16:47:32REVISED M1 DELTA 6

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-05-12 Cont ID  
Sent By rregueir Date 2009-05-12 Time 14:13 Rev Time 0.00
Received By rregueir Date 2009-05-12 Time 14:01 Sent To PC
Notes
2009-05-12 14:14:15PAGE M-1 REVISION #5

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-12-29 Cont ID  
Sent By rregueir Date 2008-12-29 Time 10:39 Rev Time 0.00
Received By rregueir Date 2008-12-29 Time 10:38 Sent To  
Notes
2008-12-29 10:39:28OK FOR LMARTINEZ TO STAMP MECH SHEETS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-12-12 Cont ID  
Sent By rregueir Date 2008-12-12 Time 16:37 Rev Time 0.00
Received By rregueir Date 2008-12-11 Time 19:28 Sent To  
Notes
2008-12-12 16:37:11REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. **PARTIALLY ADDRESSED** PLEASE PLACE SHOP DRAWING
 REVIEW STAMPS ON FRONT OF PAGES FOR RECORDS RETENTION
 PURPOSES. THSES PLANS WILL BE DIGITIZED FOR ARCHIVING
 AND STAMPS ON BACKS OF PAGES WILL NOT BE RECORDED.
 ALSO, PAGE M1 CONTAINS A SHOP DRAWING REVIEW STAMP
 DATED 10/25/08 BUT THE PLANS INDICATE THEY WERE REVISED
 ON 11/25/08 (SAME GOES FOR ENGINEER'S SEAL AND
 SIGNATURE). HOW IS THIS POSSIBLE? PLEASE CORRECT DATES
 ON PLANS TO CORRESPOND WITH ACTUAL REVISION DATES.
  
 2. OK
  
 3. **NOT ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL: IN NO
 CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT
 IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5 INCHES
 WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. OK
  
 5. OK
  
 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS
 NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN
 LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH
 ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 7. OK
  
 8. **NOT ADDRESSED** PAGE A.1 SHOWS A SINGLE DOOR IN
 MECHANICAL ROOM 204. PAGE M1 FLOOR PLAN SHOWS A
 LOUVERED DOUBLE-DOOR AT THIS LOCATION. WHICH IS
 CORRECT? NO DOOR SCHEDULE COULD BE FOUND IN THE
 ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF DOOR IS TO BE
 USED AT THIS LOCATION. PLEASE SHOW THE DOOR TYPES TO
 VERIFY THAT A LOUVERED DOOR IS BEING PROVIDED FOR
 RETURN AIR. ALSO, THE TYPE OF DOOR SHALL MEET THE
 REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH FBCM
 602.2.1.
  
 9. SEE ABOVE.
  
 10. OK
  
 11. OK
  
 **NEW** THESE PLANS HAVE FAILED REVIEW FOR CODE
 COMPLIANCE 3 TIMES. EACH TIME COMMENTS 3, 6 AND 8 ABOVE
 HAVE BEEN REPEATED AND HAVE NOT BEEN ADDRESSED OR
 CORRECTED ON PLANS. AS A RESULT, A FINE OF FOUR TIMES
 THE PLAN REVIEW FEE IS BEING IMPOSED ON THIS PERMIT
 APPLICATION IN ACCORDANCE WITH FS 553.80(2)(B). THE
 CITY OF WEST PALM BEACH ATTRIBUTES 30% OF PERMIT FEES
 TO PLAN REVIEW. THE PERMIT FEE IS $800. THIRTY PERCENT
 OF THAT FEE (THE PLAN REVIEW FEE) IS $240. THE TOTAL
 AMOUNT DUE PRIOR TO RESUBMISSION OF PLANS FOR PERMIT IS
 $960.00.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 16:03 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 15:53 Sent To PC
Notes
2008-11-15 15:56:30REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. OK
  
 3. **PARTIALLY ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL:
 IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT
 THAT IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5
 INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. OK
  
 5. OK
  
 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS
 NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN
 LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH
 ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 7. OK
  
 8. **NOT ADDRESSED** PAGE A.1 SHOWS A SINGLE DOOR IN
 MECHANICAL ROOM 204. PAGE M1 FLOOR PLAN SHOWS A
 LOUVERED DOUBLE-DOOR AT THIS LOCATION. WHICH IS
 CORRECT? NO DOOR SCHEDULE COULD BE FOUND IN THE
 ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF DOOR IS TO BE
 USED AT THIS LOCATION. PLEASE SHOW THE DOOR TYPES TO
 VERIFY THAT A LOUVERED DOOR IS BEING PROVIDED FOR
 RETURN AIR. ALSO, THE TYPE OF DOOR SHALL MEET THE
 REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH FBCM
 602.2.1.
  
 9. SEE ABOVE.
  
 10. OK
  
 11. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-20 Cont ID  
Sent By rregueir Date 2008-08-20 Time 14:18 Rev Time 0.00
Received By rregueir Date 2008-08-20 Time 11:41 Sent To PC
Notes
2008-08-20 14:18:18REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. PROVIDE COOLING LOAD CALCULATIONS FOR THIS SPACE IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 3. PAGE M1 DUCT TAKEOFF DETAIL: HORIZONTAL DUCT SHALL
 BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FEET AND
 HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT
 MANUFACTURER?S RECOMMENDATIONS AND SHALL BE OF
 SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL
 DUCT DIAMETER. IN NO CASE SHALL THE MATERIAL SUPPORTING
 FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH IT BE LESS
 THAN 1? INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. LOCATION OF CONDENSATE DISPOSAL NOT SHOWN ON PLANS.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 5. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 6. PAGE M1 PLUMBING NOTE #18: THIS NOTE CALLS FOR PVC O
 BE USED FOR THE CONDENSATE DRAIN LINE. PVC MAY NOT BE
 USED IN THE MECHANICAL ROOM WHICH ALSO SERVES AS A
 RETURN AIR PLENUM. MATERIALS EXPOSED WITHIN PLENUMS
 SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 PER FBCM 602.2.1.
  
 7. PAGE M1: NO INFORMATION WAS PROVIDED ON PLANS
 REGARDING THE CFM OF THE TOILET ROOM EXHAUST FAN.
 PROVIDE A FAN SCHEDULE WITH MAKE, MODEL, VOLTS, AMPS
 AND EXHAUST RATE EXPRESSED IN CFM. EXHAUST RATE SHALL
 BE IN COMPLIANCE WITH FBCM 403.4 AND ASHRAE 62.1-2004
 TABLE 6-4.
  
 8. PAGE A.1 SHOWS A SINGLE DOOR IN MECHANICAL ROOM 204.
 PAGE M1 FLOOR PLAN SHOWS A LOUVERED DOUBLE-DOOR AT THIS
 LOCATION. WHICH IS CORRECT? NO DOOR SCHEDULE COULD BE
 FOUND IN THE ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF
 DOOR IS TO BE USED AT THIS LOCATION. PLEASE SHOW THE
 DOOR TYPES TO VERIFY THAT A LOUVERED DOOR IS BEING
 PROVIDED FOR RETURN AIR. ALSO, THE TYPE OF DOOR SHALL
 MEET THE REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH
 FBCM 602.2.1.
  
 9. PAGE M1 CALLS FOR A LOUVERED DOOR FOR RETURN AIR
 ABOVE THE DOOR IN MECHANICAL ROOM 204. NO SUCH DOOR IS
 SHOWN ON ARCHITECTURAL PLANS. SHOW THE LOCATION AND
 SIZE OF THE RETURN OPENING ON THE MECHANICAL PLANS. AIR
 DISTRIBUTION SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 PROVIDE THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE
 WITH FBCM 603.1. ALSO, BALANCED RETURN IS REQUIRED IN
 ACCORDANCE WITH FBCM 601.4.
  
 10. THE OUTSIDE AIR INTAKE DUCT SHALL BE PROVIDED WITH
 AUTOMATIC SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBCB 13-409.1.ACB 3.3.
  
 11. THE OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH
 ASHRAE 62.1-2004 SECTION 6.2. EXAMPLE: THE OCCUPANCY
 SHOULD BE BASED ON A RETAIL OCCUPANCY ON TABLE 6-1.
 BASED ON THIS OCCUPANCY AND THE SIZE OF THE SPACE GIVEN
 ON THE PLANS, A MINIMUM VENTILATION RATE OF 227 CFM IS
 REQUIRED IN ACCORDANCE WITH FBCM 403.4 AND ASHRAE
 62.1-2004 SECTION 6.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 16:13 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 16:13 Sent To  
Notes
2009-07-14 16:14:26REVISION #6 REPLACED REVISION #5 NO CHANGE NOTED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-05-06 Cont ID  
Sent By kstevens Date 2009-05-06 Time 09:44 Rev Time 0.00
Received By kstevens Date 2009-05-05 Time 16:54 Sent To  
Notes
2009-05-06 09:45:37REVISION OK -- SHT M1

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-30 Cont ID  
Sent By lwagner Date 2008-12-30 Time 10:55 Rev Time 0.00
Received By lwagner Date 2008-12-30 Time 10:06 Sent To  
Notes
2008-12-30 10:53:14PLUMBING REVIEW OK. CALLED STEPHEN ROY TO GET OK TO
 CHANGE LAV. HEIGHT ON SHEET A.4 FROM 2'-11" TO 2'- 10"
 . HE IS CHANGING HIS OFFICE SET TO MATCH.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By mperson Date 2008-11-05 Time 13:32 Rev Time 1.00
Received By mperson Date 2008-11-05 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By mperson Date 2008-08-08 Time 14:46 Rev Time 0.00
Received By mperson Date 2008-08-08 Time 14:46 Sent To  
Notes
2008-08-08 15:01:10PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1 KITCHEN ELEVATIONS DETAIL #1: PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR THE BREAK ROOM
 SINK ON THE ELEVATION DETAIL COMPLIANT WITH THE
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. CLEARLY INDICATE THIS ON SHEET A.1 FIRST FLOOR
 TENANT BUILD-OUT PLAN DETAIL #2.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEET A.4 KEY NOTES #8, #9 AND SHEET M1 PLUMBING
 FIXTURE SCHEDULE MARK 1, 2 ARE INDICATING DIFFERENT
 MODEL FIXTURES FOR THE WATER CLOSET, LAVATORIES AND THE
 LAVATORY FAUCETS. PLEASE KNOW THAT AN ONLINE SEARCH FOR
 THE INDICATED AMERICAN STANDARD FIXTURE MODELS CAME UP
 "NO RECORDS TO DISPLAY FOR THOSE FIXTURES. PLEASE
 CORRECT, CORRELATE, AND PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIXTURES. PER FBC-2004 PLUMBING SECTION
 401.1 SCOPE.
  
 3. SHEET M1 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING PER THE FBC-2004 PLUMBING SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE OF THE LAVATORY AND
 DRINKING FOUNTAIN WATER-SEAL TRAPS. PLEASE KNOW THAT IF
 TRAPS ARE 1-1/4"CLEANOUTS WILL BE REQUIRED AT THE
 BASE OF THEIR STACKS. PER SECTION 701.1 SCOPE AND
 SECTION 708.3.4. BASE OF STACK.
  
 B} CLEARLY INDICATE THE SIZE OF THE WATER SEAL TRAP
 FOR THE SINK. PER SECTION 701.1 SCOPE.
  
 4. SHEET M1 HVAC & PLUMBING: CLEARLY INDICATE ON THE
 RESUBMITTED PLANS WHERE THE CONDENSATE TIE-IN DRAIN
 PIPING TERMINATION POINT IS. DOES IT TIE INTO AN
 EXISTING SYSTEM? PLEASE KNOW THAT THE CONDENSATE SHALL
 NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS
 TO CAUSE A NUISANCE. PER SECTION 314.2.1 CONDENSATE
 DISPOSAL.
  
 5. THE PROPOSED BUILD-OUT OF SUITE 106 IS IN A BASE
 BUILDING THAT DOES NOT YET HAVE A CERTIFICATE OF
 OCCUPANCY, SO THE BASE BUILDING DESIGN PROFESSIONALS
 WILL BE REQUIRED TO PROVIDE A SHOP DRAWING REVIEW STAMP
 ON ANY BUILD-OUT PLANS THAT ARE PREPARED BY DIFFERENT
 DESIGNERS. PER FS 481, 481.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
 .

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By mflis Date 2008-08-05 Time 15:32 Rev Time 0.00
Received By mflis Date 2008-08-05 Time 15:32 Sent To  
Notes
2008-08-05 15:33:09ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR BUILD-OUT ONLY
 ** SIGNAGE TO BE SUBMITTED UNDER SEPARATE PERMIT **
 SALES OFFICE FOR DEVELOPMENT
  
 MATT FLIS - 822-1445