Plan Review Details - Permit 08070709
Plan Review Stops For Permit 08070709
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-25 Cont ID  
Sent By lmartine Date 2009-07-25 Time 11:13 Rev Time 0.00
Received By lmartine Date 2009-07-25 Time 11:13 Sent To  
Notes
2009-07-25 11:29:41REVISION #4

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-02-24 Cont ID  
Sent By mjacobs Date 2009-02-24 Time 15:49 Rev Time 0.00
Received By mjacobs Date 2009-02-24 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-22 Cont ID  
Sent By mjacobs Date 2009-01-22 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2009-01-22 Time 16:30 Sent To  
Notes
2009-01-22 16:30:56 
 BUILDING PLAN REVIEW
 PERMIT: 08070709
 ADD: 480 HIBISCUS ST. #104
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-22-09
 REVIEW: 3RD
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
  
 **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS
 OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY
 MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICENT CLARITY. 106.1.1**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE
 SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC
 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE
 MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF
 THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED
 WHEN CALCULATING THE OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 4) FBC 505.1 MEZZANINES ARE REQUIRED TO HAVE A CEILING
 HEIGHT OF NOT LESS THAN 7 FEET AND THE CEILING BELOW
 MUST ALSO BE AT LEAST 7 FEET. PROVIDE A FRONT ELEVATION
 OF THE MEZZANINE SHOWING THESE REQUIREMENTS.
  
 5) OK
 6) OK
 7) OK
 8) OK
  
 **THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. HANDWRITING AND WHITE-OUT ON
 THE PLANS IS NOT ACCEPTABLE. THE ARCHITECT IS NOT AWARE
 OF THE INFORMATION WRITTEN ON THE DRAWINGS. THE REVIEW
 STAMP IS SUFFICIENT INFORMATION. THE HANDWRITING
 INFORMATION NEEDS TO BE REMOVED FROM THE DRAWINGS.
 PLEASE SEE EACH SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561) 805-6726
 FAX (561)805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-19 Cont ID  
Sent By mjacobs Date 2008-11-19 Time 10:42 Rev Time 0.00
Received By mjacobs Date 2008-11-19 Time 10:42 Sent To  
Notes
2008-11-19 10:42:31BUILDING PLAN REVIEW
 PERMIT: 08070709
 ADD: 480 HIBISCUS ST. #104
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS
 OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY
 MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICENT CLARITY. 106.1.1**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE
 SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC
 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE
 MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF
 THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED
 WHEN CALCULATING THE OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
  
 **AFTER FURTHER INVESTIGATION, I FOUND OUT THIS IS A
 NEW BUILDING THAT HAS NOT BEING OCCUPIED. THEREFORE, NO
 ALTERATION LEVEL IS REQUIRED.**
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; BECAUSE THE SPACE HAS NEVER BEEN
 OCCUPIED, THIS WILL BE CONSIDERED AS NEW CONSTRUCTION
 SO, NO ALTERATION LEVEL IS REQUIRED.
  
 6) OK
 7) OK
  
 **NO VERTICAL ACCESSIBILITY SHALL BE PROVIDED IF THE
 REQUIREMENTS ARE MET**
 8) 11-4.1.3(5) (3) OCCUPIABLE SPACES AND ROOMS THAT ARE
 NOT OPEN TO THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE
 PERSONS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT
 CONTROL ROOMS AND PROJECTION BOOTHS. HOWEVER AS
 PROVIDED IN SECTION 553.509, FLORIDA STATUTES,
 BUILDINGS, STRUCTURES, AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADAAG.
 THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS CODE. SHEET
 A.1 INDICATES WHAT APPEARS TO BE A CONFERENCE ROOM AT
 THE MEZZANINE LEVEL WITH MORE THAN FIVE PERSONS, WHICH
 WILL REQUIRE VERTICAL ACCESSIBILITY .
  
 NOTE: PLEASE INDICATE THE TYPE AND MAKE OF THE
 MECHANICAL ROOM DOOR. IS THE DOOR A NON-COMBUSTIBLE
 DOOR? ADDITIONAL INFORMATION IS REQUIRED 106.1.2.
  
 A) A FINISH SCHEDULE WAS NOT PROVIDED FOR THE ROOMS OR
 DOORS. FBC 1210.02 WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. SHOW
 COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-18 Cont ID  
Sent By mjacobs Date 2008-08-18 Time 09:05 Rev Time 0.00
Received By mjacobs Date 2008-08-15 Time 16:39 Sent To  
Notes
2008-08-18 09:05:07BUILDING PLAN REVIEW
 PERMIT: 08070709
 ADD: 480 HIBISCUS ST. #104
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD.
  
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
  
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; BECAUSE THE SPACE HAS NEVER BEEN
 OCCUPIED, THIS WILL BE CONSIDERED AS NEW CONSTRUCTION
 SO, NO ALTERATION LEVEL IS REQUIRED.
  
 7) FBC 1013.3 (EXCEPTION #5) SHOW THE COMMON PATH OF
 EGRESS TRAVEL WHICH SHALL BE 100 FEET IN BUILDINGS WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED THROUGHOUT.
  
 8) FBC 1009.5 ALL STAIRS SHALL BE BUILT OF MATERIALS
 CONSISTENT WITH THE CONSTRUCTION TYPE OF THE BUILDING
 WHICH IS TYPE IB. ONLY THE HANDRAILS CAN BE CONSTRUCTED
 OF WOOD.
  
 9) DUE TO THE FACT THAT THIS FACILITY USE IS
 MERCANTILE,WHICH IS OPEN TO THE PUBLIC THE REQUIREMENTS
 OF THIS SECTION SHALL BE MET.11-4.1.2 NEW CONSTRUCTION:
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS
 CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-07-08 Cont ID  
Sent By btrobaug Date 2009-07-08 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2009-07-08 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-03-03 Cont ID  
Sent By btrobaug Date 2009-03-03 Time 12:40 Rev Time 0.00
Received By btrobaug Date 2009-03-03 Time 12:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-01-23 Cont ID  
Sent By btrobaug Date 2009-01-23 Time 11:30 Rev Time 0.00
Received By btrobaug Date 2009-01-23 Time 10:23 Sent To  
Notes
2009-01-23 10:58:44 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NOTE THAT HAND DRAWN CHANGES/NOTES TO THE PLAN ARE
 NOT ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE
 BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481,
 AS APPLICABLE.SHEET A.0
  
 ALL COMMENTS ARE FOR SHEET E.1
  
 2} THE FEED FROM THE DISCONNECT AT THE METER AND THE
 TRANSFORMER DISCONNECT DOES NOT INCLUDE AN EQUIPMENT
 GROUND. INDICATE IF THIS IS A METAL CONDUIT IF NOT
 INSTALL THE EQUIPMENT GROUND PER 250.122. ALSO INDICATE
 CONDUIT AND WIRE SIZE,TYPE AND NUMBER OF CONDUCTORS
 FROM THE 70 AMP TRANSFORMER DISCONNECT TO THE
 TRANSFORMER.
  
 3} INDICATE THE NUMBER OF CONDUCTORS FROM THE PANEL TO
 THE AIR HANDLER DISCONNECT AND IF GROUNDED.215.5 NEC.
  
 4} INDICATE THE NUMBER OF CONDUCTORS FROM THE PANEL TO
 THE CONDENSER DISCONNECT AND IF GROUNDED.215.5 NEC.
  
 5} THE LPD PER SQUARE FT IS SHOWN AS 2.1. THE CORRECT
 LPD FOR RETAIL IS 1.5 PER13-415.2.C.1 FBC. THE ALLOWED
 DENSITIES ARE COMPLIANT, THE CALCULATION SHOULD
 INDICATE 1.5 W/SQFT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-17 Cont ID  
Sent By dpalmer Date 2008-11-17 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2008-11-17 Time 10:02 Sent To  
Notes
2008-11-17 10:02:22** FAILED **
  
  
 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF
 OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED
 BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A
 *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE
 BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT
 BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL
 REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: THE PLANS STILL INDICATE EXISTING RETAIL
 HOWEVER THIS IS NOT POSSIBLE AS THE BUILDING CONTAINS
 *SHELL* SPACES FOR FUTURE. THE PLANS NEED TO BE
 ADJUSTED ACCORDINGLY.
 FBC 301.1
 FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD
 PLANS.
  
 4) NOTE: PLEASE SEE THE SUBMITTED LIGHTING AND LIGHTING
 CALCULATIONS FOR PERFORMANCE LEVELS STILL NEED TO BE
 ADDRESSED. THE LIGHTING SHOWN ON SHEET A.2 IS
 COMPLETELY DIFFERENT FROM THE LIGHTING SHOWN ON
 ELECTRICAL PLANS. IN FACT THERE ARE DIFFERENT FIXTURES,
 DIFFERENT WATTAGES ETC.
 PLEASE SEE ELECTRICAL PLANS WHICH INDICATE A FIXTURE B
 YET THE ARCHITECTURAL PLANS INDICATE A FIXTURE C. EACH
 OF THESE HAVE A SUBSTANTIAL DIFFERENCE IN THE ACTUAL
 WATTAGE OF THE FIXTURES.
 PLEASE COORDINATE ALL OF THESE ITEMS.
 THE DESIGN WATTAGE TOTAL IS SHOWN AS 1448WATTS. THIS IS
 NOT POSSIBLE BASED ON THE SUBMITTED PLANS. FIXTURE *A*
 ALONE EXCEEDS THE DESIGN WATTAGE SHOWN. THE NUMBER OF
 *A* FIXTURES ON THE E-1 AND E-2 ARE GREATER THAN THE
 TOTAL WATTAGE. THIS DOES NOT INCLUDE THE WATTAGE FOR
 OTHER FIXTURES SUCH AS *C* ETC.
 NOT ALL AREAS ARE RETAIL.
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: THE RISER INDICATES A DISCONNECT AND
 TRANSFORMER WHICH WOULD BE LOCATED IN THE STORAGE
 CLOSET ON MEZZANINE LEVEL WHICH IS NOT PERMITTED.
 THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON
 MEZZANINE LEVEL AND ONLY SHOWS THE PANEL.
 PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL
 ACCORDINGLY TO RISER AND PANEL IDENTIFICATION.
 PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC
 THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET
 WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE
 MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD.
 PLEASE ADJUST, RE-LOCATE ETC.
  
 6) NOTE: FROM PREVIOUS REVIEW:
 PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND
 HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3.
  
 7) NOTE: PLEASE SEE THE PANEL SCHEDULE NEEDS TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. USING
 *RECEPTACLES* OR *LIGHTING* IS NOT SPECIFIC. PLEASE SEE
 THE 2005 NEC CHANGE IN THE HANDBOOK UNDER 408.4 AS THIS
 WAS SPECIFICALLY REVISED.
  
 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN
 AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS
 ONLY A NOTICE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By dpalmer Date 2008-08-08 Time 09:08 Rev Time 0.00
Received By dpalmer Date 2008-08-08 Time 09:08 Sent To  
Notes
2008-08-08 09:08:43 
 ** DENIED REVIEW **
  
  
  
 1) NOTE: THE BASE BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT
 PERMITTED BEFORE THE C OF O OF BASE BUILDING ARE TO
 CONTAIN A *SHOP DRAWING* REVIEW STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD ON EACH
 RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR
 BUILD OUT BEFORE THE C OF O IS ISSUED ON BASE BUILDING
 WILL REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS. 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS IN
 PHOTO-METRICS ON STAIRS PER NFPA-101 2003, 7.8.1.3,
 7.9.2.1, .2.2.
  
 4) NOTE: PLEASE INDICATE ALL LIGHTING CONTROLS REQUIRED
 PER FBC 13-415.1.ABC.1.1,.1.2 AND .1.3.
 THE SYMBOL LEGEND DOES INDICATE SOME OCCUPANCY SENSOR
 TYPE DEVICES HOWEVER NONE OF THIS DEVICE S IS ON PLANS.
 IN FACT THE PLANS ONLY INDICATE STANDARD SWITCHING
 DEVICES WHICH ARE NOT PERMITTED.
 PLEASE PROVIDE ALL MAXIMUM TIMES ON ALL DEVICES. PLEASE
 BE SURE TO SEE NFPA-101 7.8.1.2.2 AND FBC 1006.1.2 AS
 ANY OCCUPANCY SENSOR FOR ANY EGRESS LIGHTING SHALL BE *
 FAIL SAFE ON*.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE SUBMIT THE FIXTURE SCHEDULE/LEGEND.
 PLEASE SEE THE SECTIONS OF THE CODE ABOVE. THE WATTAGE
 TO BE USED IS BASED ON THE FIXTURE WATTAGE NOT THE LAMP
 WATTAGE AS STATED ON PLANS.
 PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH A
 FIXTURE LEGEND ETC SOME OF THESE ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DETERMINED AT THIS TIME.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP PER
 13-413.1.ABC.1.2 FOR CU.
  
 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR ALL
 CIRCUITS TO SPECIFIC AREAS AND LOCATIONS.
 408.4
  
 8) NOTE: PLEASE ALSO CORRELATE SOME ITEMS ON PANEL WITH
 RISER.
 FOR EXAMPLE:
 PLEASE SEE RISER FOR CONDUCTORS TO CONDENSING UNIT.
 PANEL SHOWS #8 AND RISER SHOWS#6.
 WITH COMMENT ON VOLTAGE DROP AS NOTED ABOVE AND NOT
 KNOWING THE EXACT LOCATION OF THE CONDENSING UNIT THE
 CONDUCTORS CAN NOT BE DETERMINED TO MEET CODE AT THIS
 TIME.
 310.16, 240.4, FBC 13-413.1.ABC.1,
  
 9) NOTE: PLEASE VERIFY RISER AS THE GUTTER IS INDICATED
 AS RAIN TIGHT? PLEASE ALSO INDICATE THE SIZE/AMPERAGE
 OF THE GUTTER PROVIDED.
 PLEASE INDICATE A FLOATING NEUTRAL ON THE NEW METER AS
 THE MAIN FOR TENANT SHOWN WILL BE AFTER A MEANS OF
 DISCONNECT FOR SERVICE.
 250.24, 250.6
  
 10) NOTE: PLEASE SEE 600.5 AS THE LOAD FOR A SIGN
 CIRCUIT IS REQUIRED TO BE FIGURED AT 1200VA. THIS WOULD
 BE 10AMPS ON THE CIRCUIT.
  
 11) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW
 RECEPTACLES.
 PLEASE ALSO SEE 220.43
  
 12) NOTE: BASE BUILD OUT PLANS SHALL INCLUDE DEVICES TO
 COMPLY WITH THE FIRE CODES, SUCH AS NFPA-1, NFPA-72 AND
 FBC 2004 W/2007 REVISIONS.
 PLEASE SEE FBC 11-4.28 (ALL) AND INDICATE REQUIRED
 DEVICES ACCORDINGLY
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET ON
 DESIGN SHEETS THERE MAY VERY WELL BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-07-24 Cont ID  
Sent By mawillia Date 2009-07-24 Time 15:21 Rev Time 0.00
Received By mawillia Date 2009-07-24 Time 15:11 Sent To  
Notes
2009-07-24 15:21:21***** REVISION, DATED MAY 09, APPROVED*****
  
 REVISED PLAN SHEETS A.1, A.3, AND E1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-02-26 Cont ID  
Sent By mawillia Date 2009-02-26 Time 11:51 Rev Time 0.00
Received By mawillia Date 2009-02-26 Time 11:36 Sent To  
Notes
2009-02-26 11:47:51*****APPROVED*****
  
 PLAN SHEETS A.1, A.3, AND E1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-01-23 Cont ID  
Sent By mwennerg Date 2009-01-23 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2009-01-23 Time 13:30 Sent To  
Notes
2009-01-23 13:31:01***DENIED***
  
 1) OK
  
 2) SHOW A LAYOUT OF SPRINKLER HEADS FOR THE FLOOR SPACE
 WHICH MAY BE SHOWN ON THE REFLECTED CEILING PLAN. NO
 ATTACHED SPRINKLER DRAWINGS WERE FOUND WITH THIS
 SUBMITTAL.
  
 3) HANDWRITTEN NOTES ON THE PLANS ARE NOT ACCEPTABLE.
 SEE OTHER REVIEW COMMENTS. SHEET A.0
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-17 Cont ID  
Sent By mawillia Date 2008-11-17 Time 11:04 Rev Time 0.00
Received By mawillia Date 2008-11-17 Time 10:49 Sent To  
Notes
2008-11-17 11:04:07*****DENIED*****
  
 PLEASE BE ADVISED THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY
  
 1. ON SHEET A-0 CAPTION 2 INDICATES THAT THE SCOPE OF
 WORK IS INTERIOR BUILDOUT OF AN EXISTING RETAIL SPACE.
 HOW CAN THIS BE BASED UPON THE ABOVE CAPITALIZED
 ADVISEMENT?
  
 2. SHOW A LAYOUT OF THE SPRINKLER HEADS FOR THE FLOOR
 SPACE. THESE HEADS MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN. THIS COMMENT WAS NOT ADDRESSED FROM THE
 PREVIOUS FIRE PLAN REVIEW
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By mawillia Date 2008-08-13 Time 13:18 Rev Time 0.00
Received By mawillia Date 2008-08-13 Time 12:37 Sent To  
Notes
2008-08-13 13:16:36*****DENIED*****
  
 PLEASE BE ADVISED THAT THEBASE BUILDING DOES NOT HAVE A
 CERTIFICATE OF OCCUPANCY
  
 1. ON SHEET A.1 - CAPTION 1, CLARIFY AS TO WHETHER THE
 ADDRESS VERBAGE IS FOR THE BUILDING OR THE SUITE. WHY
 IS "103" SHOWN IN THE VERBAGE INSTEAD OF 104.
  
 2. SHOW A LAYOUT OF THE SPRINKLER HEADS FOR THE FLOOR
 SPACE. THESE HEADS MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-06-19 Cont ID  
Sent By btrobaug Date 2009-06-19 Time 14:03 Rev Time 0.00
Received By btrobaug Date 2009-06-19 Time 13:53 Sent To  
Notes
2009-06-19 14:03:32C-12

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 10:07 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 10:07 Sent To  
Notes
2009-02-24 10:08:42TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 11:02 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 11:02 Sent To  
Notes
2009-01-20 11:02:28TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 09:22 Sent To  
Notes
2008-11-12 09:24:42TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-08-18 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 10:15 Sent To  
Notes
2008-08-04 15:22:25TO "BOB"#11
2008-07-28 10:21:59WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 13:38 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 13:06 Sent To  
Notes
2009-07-20 13:38:42REVISED M1 DELTA 5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-29 Cont ID  
Sent By rregueir Date 2009-01-29 Time 19:05 Rev Time 0.00
Received By rregueir Date 2009-01-29 Time 19:03 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 16:32 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 16:31 Sent To  
Notes
2008-11-15 16:32:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. OK
  
 3. **PARTIALLY ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL:
 IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT
 THAT IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5
 INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. OK
  
 5. OK
  
 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS
 NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN
 LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH
 ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 7. OK
  
 8. **NOT ADDRESSED** NO INFORMATION COULD BE FOUND
 REGARDING THE TYPE OF DOOR TO BE USED ON MECHANICAL
 ROOM 104. IS THIS DOOR WOOD OR OF NON-COMBUSTIBLE
 MATERIAL? SEE COMMENT #6 ABOVE FOR THE REQUIREMENTS FOR
 MATERIALS EXPOSED IN PLENUMS. PROVIDE THE MISSING
 INFORMATION ON THE PLANS.
  
 9. SEE ABOVE.
  
 10. OK
  
 11. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-18 Cont ID  
Sent By rregueir Date 2008-08-18 Time 16:26 Rev Time 0.00
Received By rregueir Date 2008-08-18 Time 13:10 Sent To PC
Notes
2008-08-18 16:26:42REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED UNDER THE FOLLOWING CODES:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. PROVIDE COOLING LOAD CALCULATIONS FOR THIS SPACE IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 3. PAGE M1 DUCT TAKEOFF DETAIL: HORIZONTAL DUCT SHALL
 BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FEET AND
 HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT
 MANUFACTURER?S RECOMMENDATIONS AND SHALL BE OF
 SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL
 DUCT DIAMETER. IN NO CASE SHALL THE MATERIAL SUPPORTING
 FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH IT BE LESS
 THAN 1? INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. LOCATION OF CONDENSATE DISPOSAL NOT SHOWN ON PLANS.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 5. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 6. PAGE M1 PLUMBING NOTE #18: THIS NOTE CALLS FOR PVC O
 BE USED FOR THE CONDENSATE DRAIN LINE. PVC MAY NOT BE
 USED IN THE MECHANICAL ROOM WHICH ALSO SERVES AS A
 RETURN AIR PLENUM. MATERIALS EXPOSED WITHIN PLENUMS
 SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 PER FBCM 602.2.1.
  
 7. PAGE M1: NO INFORMATION WAS PROVIDED ON PLANS
 REGARDING THE CFM OF THE TOILET ROOM EXHAUST FAN.
 PROVIDE A FAN SCHEDULE WITH MAKE, MODEL, VOLTS, AMPS
 AND EXHAUST RATE EXPRESSED IN CFM. EXHAUST RATE SHALL
 BE IN COMPLIANCE WITH FBCM 403.4 AND ASHRAE 62.1-2004
 TABLE 6-4.
  
 8. NO INFORMATION COULD BE FOUND REGARDING THE TYPE OF
 DOOR TO BE USED ON MECHANICAL ROOM 104. IS THIS DOOR
 WOOD OR OF NON-COMBUSTIBLE MATERIAL? SEE COMMENT #6
 ABOVE FOR THE REQUIREMENTS FOR MATERIALS EXPOSED IN
 PLENUMS. PROVIDE THE MISSING INFORMATION ON THE PLANS.
  
 9. PAGE A.1 CALLS FOR A LOUVERED PANEL FOR RETURN AIR
 ABOVE THE DOOR IN MECHANICAL ROOM 104. NO SIZE IS GIVEN
 ON FLOOR PLANS OR THE AIR DEVICE SCHEDULE. SHOW THE
 LOCATION AND SIZE OF THE RETURN OPENING ON THE
 MECHANICAL PLANS. AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO PROVIDE THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
 ALSO, BALANCED RETURN IS REQUIRED IN ACCORDANCE WITH
 FBCM 601.4.
  
 10. THE OUTSIDE AIR INTAKE DUCT SHALL BE PROVIDED WITH
 AUTOMATIC SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBCB 13-409.1.ACB 3.3.
  
 11. THE OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH
 ASHRAE 62.1-2004 SECTION 6.2. EXAMPLE: THE OCCUPANCY
 SHOULD BE BASED ON A RETAIL OCCUPANCY ON TABLE 6-1.
 BASED ON THIS OCCUPANCY AND THE SIZE OF THE SPACE GIVEN
 ON THE PLANS, A MINIMUM VENTILATION RATE OF 227 CFM IS
 REQUIRED IN ACCORDANCE WITH FBCM 403.4 AND ASHRAE
 62.1-2004 SECTION 6.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 09:54 Rev Time 0.00
Received By kstevens Date 2009-07-06 Time 09:54 Sent To  
Notes
2009-07-06 09:55:09REVISION OK -- SHT M1

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 11:45 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 11:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By kstevens Date 2008-11-24 Time 11:51 Rev Time 0.00
Received By kstevens Date 2008-11-24 Time 11:51 Sent To  
Notes
2008-11-24 11:52:14PLUMBING PLAN REVIEW:
 DENIED:
  
 ****FROM PREVIOUS REVIEW:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.3 KEY NOTES #8, #9 AND SHEET M1 PLUMBING
 FIXTURE SCHEDULE MARK 1, 2 ARE INDICATING DIFFERENT
 MODEL FIXTURES FOR THE WATER CLOSET, LAVATORIES AND THE
 LAVATORY FAUCETS. PLEASE KNOW THAT AN ONLINE SEARCH FOR
 THE INDICATED AMERICAN STANDARD FIXTURE MODELS CAME UP
 "NO RECORDS TO DISPLAY FOR THOSE FIXTURES". PLEASE
 CORRECT, CORRELATE, AND PROVIDE MANUFACTURE SPEC SHEETS
 FOR FIXTURES. PER FBC-2004 PLUMBING SECTION 401.1
 SCOPE.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED. (LEVER
 OPERATED FAUCETS ARE SPECIFIED) ?
  
 2. SHEET M1 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLLOWING PER THE FBC-2004 PLUMBING SECTIONS.
  
 A} OK
  
 3. OK
  
 4. THE PROPOSED BUILD-OUT OF SUITE 106 IS IN A BASE
 BUILDING THAT DOES NOT YET HAVE A CERTIFICATE OF
 OCCUPANCY. SO THE BUILDING DESIGN PROFESSIONALS WILL BE
 REQUIRED TO PROVIDE A SHOP DRAWING REVIEW STAMP ON ANY
 BUILD-OUT PLANS THAT ARE PREPARED BY DIFFERENT
 DESIGNERS. PER SS 481.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By mperson Date 2008-08-08 Time 13:56 Rev Time 0.00
Received By mperson Date 2008-08-08 Time 13:56 Sent To  
Notes
2008-08-08 14:02:19PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.3 KEY NOTES #8, #9 AND SHEET M1 PLUMBING
 FIXTURE SCHEDULE MARK 1, 2 ARE INDICATING DIFFERENT
 MODEL FIXTURES FOR THE WATER CLOSET, LAVATORIES AND THE
 LAVATORY FAUCETS. PLEASE KNOW THAT AN ONLINE SEARCH FOR
 THE INDICATED AMERICAN STANDARD FIXTURE MODELS CAME UP
 "NO RECORDS TO DISPLAY FOR THOSE FIXTURES. PLEASE
 CORRECT, CORRELATE, AND PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIXTURES. PER FBC-2004 PLUMBING SECTION
 401.1 SCOPE.
  
 2. SHEET M1 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING PER THE FBC-2004 PLUMBING SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE OF THE LAVATORY AND
 DRINKING FOUNTAIN WATER-SEAL TRAPS. PLEASE KNOW THAT IF
 TRAPS ARE 1-1/4"CLEANOUTS WILL BE REQUIRED AT THE
 BASE OF THEIR STACKS. PER SECTION 701.1 SCOPE AND
 SECTION 708.3.4. BASE OF STACK.
  
 3. SHEET M1 HVAC & PLUMBING: CLEARLY INDICATE ON THE
 RESUBMITTED PLANS WHERE THE CONDENSATE TIE-IN DRAIN
 PIPING TERMINATION POINT IS. DOES IT TIE INTO AN
 EXISTING SYSTEM? PLEASE KNOW THAT THE CONDENSATE SHALL
 NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS
 TO CAUSE A NUISANCE. PER SECTION 314.2.1 CONDENSATE
 DISPOSAL.
  
 4. THE PROPOSED BUILD-OUT OF SUITE 106 IS IN A BASE
 BUILDING THAT DOES NOT YET HAVE A CERTIFICATE OF
 OCCUPANCY, SO THE BASE BUILDING DESIGN PROFESSIONALS
 WILL BE REQUIRED TO PROVIDE A SHOP DRAWING REVIEW STAMP
 ON ANY BUILD-OUT PLANS THAT ARE PREPARED BY DIFFERENT
 DESIGNERS. PER FS 481, 481.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]