| 2008-08-12 11:14:04 | RESIDENTIAL (R3)ALTERATION/RENOVATION, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- THERE WERE REPORTS SUBMITTED SHOWING THAT THERE WAS |
| | A FIRE IN THE KITCHEN OF THE HOUSE.PLANS SUBMITTED |
| | NEED TO INDICATE ANY SCOPE OF WORKTHAT IS REQUIRED TO |
| | FIX THE FIRE DAMAGE TO THE STRUCTURE. SEC.101.3 OF |
| | 2004 FLORIDA EXISTING BUILDING CODE. |
| | |
| | 2- PLANS NEED TO CLEARLYSPECIFYCLASSIFICATION OF |
| | WORK AS REQUIRED BY SEC. 301.5OF 2004 FLORIDA |
| | EXISTING BUILDING CODE. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT.SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK UP. |
| | |
| | 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5120)TO CHECK IF |
| | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF IMPACT FEES ARE DUE. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | A) SPECIFY EAVE OVERHANG ON ITEM #5. |
| | B) CLARIFY HOW ARE YOU GETTING THE 0.3 INSULATION ON |
| | THE CONCRETE SLAB ON GRADE, ITEM #8A. ONLY WHEN |
| | INSULATION IS ADDED IS WHEN THE R-VALUE MAY BE TAKEN |
| | INTO CONSIDERATION. |
| | C) REVISEINSULATION R-VALUE FOR EXTERIOR WALL ITEM |
| | #9(A)2.R-19 INSULATION DOESN'T FIT ON 2X4 WALL. |
| | ***NOTE: REVISE INFORMATION ON TABLE 6C-1 ON THE BACK |
| | OF THE FORM TOO. R-11 IS THE INSULATION VALUE THAT |
| | GOES WITH 2X4 WALL.. |
| | D) CLARIFY IF ADDING THE INSULATION ON EXISTING |
| | ADJACENT MASONRY WALL ANDADJACENT FRAME WALL. |
| | OTHERWISE IF NO ADDINGTHE INSULATION , THEN LEAVE |
| | SPACE BLANK.THIS PRESCRIPTIVE FORM ONLY APPLIES TO |
| | NEW COMPONENTS BEING INSTALLED. |
| | E) IS THE A/C SYSTEM ON ITEM #11 NEW OR EXISTING?. |
| | |
| | |
| | 6- SHEET 1.1: |
| | A) DESIGN LOADS SHOWN ON DESIGN PARAMETERS BOX DON'T |
| | MATCH THE DESIGN LOADS SHOWN ON STRUCTURAL NOTE 2A. |
| | REVISE AS REQUIRED. |
| | B) UPDATE STRUCTURAL NOTE #12. SEE THE 2004 FLORIDA |
| | RESIDENTIAL CODE AND REFERENCE CORRECT CODE SECTION. |
| | SEC. 2306.1 APPLIES TO OTHER BUILDING OTHER THAN ONE |
| | AND TWO FAMILY RESIDENCES. |
| | C) REVISE AND CLARIFY STRUCTURAL NOTE #14:1 3/4" |
| | NAILING IS NOT ADEQUATE. ASTM C926 AND ASTM C1063 |
| | REQUIRES MIN. 1 3/4" NAIL PENETRATION INTO THE |
| | STRUCTURAL MEMBER. THEREFORE, NAILS NEED TO BE LONGER. |
| | REVISE AS REQUIRED. |
| | ALSO, CLARIFY WHAT'S 1/2" EXT. PLYWOOD VENT SYSTEM |
| | REQUIRED? |
| | D) REVISE CODE SPECIFIED O THE DESIGN PARAMETERS |
| | BOX. CORRECT CODEFOR ONE AND TWO FAMILY RESIDENCES IS |
| | THE 2004 FLORIDA RESIDENTIAL CODE. AND CORRECT SECTION |
| | FOR DESIGN LOADS IS SEC. R301. REVISE AS REQUIRED. |
| | |
| | 7- SHEET 2.1: |
| | A) TYPICAL WALL SECTION: |
| | (1) SPECIFY VENTILATION TO COMPLY WITH SEC. R806 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. CONFIRM OR ADD CONT. |
| | VENT. IS NOT ADEQUATE INFORMATION. |
| | (2) REVISE INSULATION VALUE. R-19 DOESN'T FIT ON 2X4 |
| | WALL. |
| | (3) CLARIFY IF ADDING A 4"X4" CONC. PIER, THEN HOW |
| | ARE YOU GETTING THE 8" FROM GRADE TO TOP OF PIER AS |
| | SHOWN ON THE SECTION. SEE COMMENTS ONWALL SECTION. |
| | |
| | (4) CLARIFY WHY THE 4" GALV. FLASH. IS BURIEDUNDER |
| | THE FINISH GRADE.SEE SEC. R704 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | (5) SPECIFY EXISTING FOOTING SIZE. THIS IS PART OF |
| | THE DESIGN.CONFIRM EXISTING FOOTING IS NOT ACCEPTABLE |
| | DESCRIPTION.SEE SEC.R403 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | (6) TYPICAL WALL SECTION CALLS FOR T-11 ON WALLS, |
| | WHILE DETAIL D/ 2/1 CALLS FOR 7/8" STUCCO. REVISE AS |
| | REQUIRED TO MATCH. |
| | (7) INFORMATION ON DETAILD / 2/1DOESN'T MATCH |
| | INFORMATION SHOWN ON TYPICAL WALL SECTION.SEE |
| | INFORMATION ABOUT MEMBRANE STRIP COVERING, ETC. AT |
| | BOTTOM OF DETAIL.REVISE AS REQUIRED TO MATCH. ALSO, |
| | CHECK DIMENSIONS. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) FRENCH DOORS AS SHOWN ON PLANS. |
| | B) SINGLE HUNG WINDOWS. |
| | D) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT |
| | GLAZING. |
| | ***NOTE: ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | FOR STORM SHUTTERS AND CLEARLY MARK ON SHUTTERS |
| | DRAWINGS SPECIFIC MOUNTING CONDITIONS AND ANCHOR TYPE |
| | AND SPACING TO BE USED. |
| | E) ALLSIMPSON STRUCTURAL CONNECTORS SHOWN ON |
| | PLANS. |
| | ***NOTE: PROVIDEONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTORIS SHOWN. |
| | |
| | 9- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| 2008-08-12 10:29:58 | NO RADON FEES. NEW KITCHEN WILL BE LOCATED ON EXISTING |
| | REAR PORCH. |