Plan Review Details - Permit 08070697
Plan Review Stops For Permit 08070697
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By jgomez Date 2008-08-12 Time 10:29 Rev Time 0.00
Received By jgomez Date 2008-08-12 Time 07:38 Sent To P
Notes
2008-08-12 11:14:04RESIDENTIAL (R3)ALTERATION/RENOVATION, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- THERE WERE REPORTS SUBMITTED SHOWING THAT THERE WAS
 A FIRE IN THE KITCHEN OF THE HOUSE.PLANS SUBMITTED
 NEED TO INDICATE ANY SCOPE OF WORKTHAT IS REQUIRED TO
 FIX THE FIRE DAMAGE TO THE STRUCTURE. SEC.101.3 OF
 2004 FLORIDA EXISTING BUILDING CODE.
  
 2- PLANS NEED TO CLEARLYSPECIFYCLASSIFICATION OF
 WORK AS REQUIRED BY SEC. 301.5OF 2004 FLORIDA
 EXISTING BUILDING CODE.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT.SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK UP.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5120)TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF IMPACT FEES ARE DUE.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) SPECIFY EAVE OVERHANG ON ITEM #5.
 B) CLARIFY HOW ARE YOU GETTING THE 0.3 INSULATION ON
 THE CONCRETE SLAB ON GRADE, ITEM #8A. ONLY WHEN
 INSULATION IS ADDED IS WHEN THE R-VALUE MAY BE TAKEN
 INTO CONSIDERATION.
 C) REVISEINSULATION R-VALUE FOR EXTERIOR WALL ITEM
 #9(A)2.R-19 INSULATION DOESN'T FIT ON 2X4 WALL.
 ***NOTE: REVISE INFORMATION ON TABLE 6C-1 ON THE BACK
 OF THE FORM TOO. R-11 IS THE INSULATION VALUE THAT
 GOES WITH 2X4 WALL..
 D) CLARIFY IF ADDING THE INSULATION ON EXISTING
 ADJACENT MASONRY WALL ANDADJACENT FRAME WALL.
 OTHERWISE IF NO ADDINGTHE INSULATION , THEN LEAVE
 SPACE BLANK.THIS PRESCRIPTIVE FORM ONLY APPLIES TO
 NEW COMPONENTS BEING INSTALLED.
 E) IS THE A/C SYSTEM ON ITEM #11 NEW OR EXISTING?.
  
  
 6- SHEET 1.1:
 A) DESIGN LOADS SHOWN ON DESIGN PARAMETERS BOX DON'T
 MATCH THE DESIGN LOADS SHOWN ON STRUCTURAL NOTE 2A.
 REVISE AS REQUIRED.
 B) UPDATE STRUCTURAL NOTE #12. SEE THE 2004 FLORIDA
 RESIDENTIAL CODE AND REFERENCE CORRECT CODE SECTION.
 SEC. 2306.1 APPLIES TO OTHER BUILDING OTHER THAN ONE
 AND TWO FAMILY RESIDENCES.
 C) REVISE AND CLARIFY STRUCTURAL NOTE #14:1 3/4"
 NAILING IS NOT ADEQUATE. ASTM C926 AND ASTM C1063
 REQUIRES MIN. 1 3/4" NAIL PENETRATION INTO THE
 STRUCTURAL MEMBER. THEREFORE, NAILS NEED TO BE LONGER.
 REVISE AS REQUIRED.
 ALSO, CLARIFY WHAT'S 1/2" EXT. PLYWOOD VENT SYSTEM
 REQUIRED?
 D) REVISE CODE SPECIFIED O THE DESIGN PARAMETERS
 BOX. CORRECT CODEFOR ONE AND TWO FAMILY RESIDENCES IS
 THE 2004 FLORIDA RESIDENTIAL CODE. AND CORRECT SECTION
 FOR DESIGN LOADS IS SEC. R301. REVISE AS REQUIRED.
  
 7- SHEET 2.1:
 A) TYPICAL WALL SECTION:
 (1) SPECIFY VENTILATION TO COMPLY WITH SEC. R806 OF
 2004 FLORIDA RESIDENTIAL CODE. CONFIRM OR ADD CONT.
 VENT. IS NOT ADEQUATE INFORMATION.
 (2) REVISE INSULATION VALUE. R-19 DOESN'T FIT ON 2X4
 WALL.
 (3) CLARIFY IF ADDING A 4"X4" CONC. PIER, THEN HOW
 ARE YOU GETTING THE 8" FROM GRADE TO TOP OF PIER AS
 SHOWN ON THE SECTION. SEE COMMENTS ONWALL SECTION.
  
 (4) CLARIFY WHY THE 4" GALV. FLASH. IS BURIEDUNDER
 THE FINISH GRADE.SEE SEC. R704 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
 (5) SPECIFY EXISTING FOOTING SIZE. THIS IS PART OF
 THE DESIGN.CONFIRM EXISTING FOOTING IS NOT ACCEPTABLE
 DESCRIPTION.SEE SEC.R403 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 (6) TYPICAL WALL SECTION CALLS FOR T-11 ON WALLS,
 WHILE DETAIL D/ 2/1 CALLS FOR 7/8" STUCCO. REVISE AS
 REQUIRED TO MATCH.
 (7) INFORMATION ON DETAILD / 2/1DOESN'T MATCH
 INFORMATION SHOWN ON TYPICAL WALL SECTION.SEE
 INFORMATION ABOUT MEMBRANE STRIP COVERING, ETC. AT
 BOTTOM OF DETAIL.REVISE AS REQUIRED TO MATCH. ALSO,
 CHECK DIMENSIONS.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FRENCH DOORS AS SHOWN ON PLANS.
 B) SINGLE HUNG WINDOWS.
 D) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLAZING.
 ***NOTE: ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE
 FOR STORM SHUTTERS AND CLEARLY MARK ON SHUTTERS
 DRAWINGS SPECIFIC MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED.
 E) ALLSIMPSON STRUCTURAL CONNECTORS SHOWN ON
 PLANS.
 ***NOTE: PROVIDEONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTORIS SHOWN.
  
 9- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
2008-08-12 10:29:58NO RADON FEES. NEW KITCHEN WILL BE LOCATED ON EXISTING
 REAR PORCH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 14:34 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 14:03 Sent To Z
Notes
2008-07-29 14:34:05 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DESCRIPTION ON THE APPLICATION DOES NOT INCLUDE
 A NEW BATHROOM.REVISE THE APPLICATION TO INCLUDE ALL
 WORK TO BE COMPLETED UNDER THIS PERMIT. 105.1 FBC.
  
 2} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B)(1)
 RECEPTACLE OUTLETS SERVED IN THE KITCHEN, PANTRY,
 BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF A
 DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT.**ONLLY CIRCUIT 24, SHEET A-3
 COMPLIES, CIRCUIT 26 HAS LIGHTS ON THE SAME CIRCUIT AS
 THE RECEPTACLES.CIRCUIT #2 IS NOT SHOWN IN THE
 KITCHEN.
  
 3} NOTE #4 IN THE ELECTRICAL NOTES, SHEET A-3,
 REGARDING #12 COPPER CONDUCTORS MINIMUM IS IN CONFLICT
 WITH THE #14 WIRE ADDED IN CIRCUIT 28.
  
 4} THE LOAD CALCULATION ONLY LISTS ONE SMALL APPLIANCE
 CIRCUIT, TWO ARE LISTED ON THE PANEL SCHEDULE AND ARE
 RQUIRED PER 210.11(C)(1).
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.***
 INDICATE SAME ON PLANS, SHOW LOCATION OR NOTE THIS
 ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 15:54 Sent To B
Notes
2008-08-04 15:54:53TO "SFR" B"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-12 Cont ID  
Sent By mperson Date 2008-08-12 Time 15:37 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 14:18 Sent To PC
Notes
2008-07-24 14:18:13TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 09:52 Rev Time 0.30
Received By tgordon Date 2008-07-25 Time 09:52 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By mperson Date 2008-08-12 Time 15:04 Rev Time 0.00
Received By mperson Date 2008-08-12 Time 15:04 Sent To I
Notes
2008-08-12 15:30:50PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: PERMIT APPLICATION STATES "DESCRIBE PROJECT
 IN DETAIL (FAILURE TO DO SO MAY RESULT IN DELAYS)".
 PLEASE KNOW THAT THE NEW BATHROOM IS NOT ON THE PERMIT
 APPLICATION. PLEASE REVISE PERMIT APPLICATION TO
 REFLECT ALL PROPOSED WORK BEING DONE OR DELETE WORK
 FROM PLANS. PER (W.P.B.AS AMENDED) SECTION 105.1
 REQUIRED.
  
 2. SHEET A-3 SANITARY ISOMETRIC RISER DIAGRAM AND
 PLUMBING LAYOUT: DELETE THE HORIZONTAL DRY VENT
 UPSTREAM OF THE WATER CLOSET. THE BATHROOM GROUP IS
 COMPLIANT PER THE LAVATORY WET VENT. PER FBC-2004
 PLUMBING SECTION 905.3 VENT CONNECTION TO DRAINAGE
 SYSTEM.
  
 3. SHEET A-3 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THAT THE REQUIRED DRAIN FOR THE DISHWASHER
 SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. PER FBC-2004
 PLUMBING SECTION 802.1.6 DOMESTIC DISHWASHING MACHINES.
  
  
 4. SHEET A-3 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THE REQUIRED CLEANOUTS AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER AS BEING TWO-WAY
 CLEANOUTS. PER FBC-2004 PLUMBING SECTION 708.3.5
 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By mcruz Date 2008-08-04 Time 09:40 Rev Time 0.00
Received By mcruz Date 2008-08-04 Time 09:39 Sent To I
Notes
2008-08-04 09:40:36**ZONING FAILED**
  
 1.PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2.PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY?S LEGAL DESCRIPTION (THE SURVEY
 ONLY SHOWS A PARTIAL DESCRIPTION).INDICATE ON THE
 SURVEY THE SETBACK DIMENSIONS OF THE PROPOSED ADDITION
 TO ALL PROPERTY LINES.
  
 3.PROVIDE DIMENSION OF ROOF OVERHANG.NOTE:
 PURSUANT TO SECTION 305(B)(2), OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR)
 ROOF OVERHANGS SHALL EXTEND NO FURTHER THAN THREE (3)
 FEET INTO ANY SETBACK.
  