| Plan Review Stops For Permit 08070674 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-29 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-08-29 |
Time |
14:51 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-27 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-08-27 |
Time |
11:47 |
Sent To |
PC |
|
| Notes |
| 2008-08-27 11:49:59 | RESIDENTIAL(R3) PARTIAL DEMOLITION, BUILDING REVIEW | | | SECOND CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1-DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY THE | | | ARCHITECT RESPONSIBLE OF THE PLANS (AMES BENNETT & | | | ASSOCIATES) AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. | | | (REPEAT COMMENT). | | | | | | NOTE:ONE COPY OF PLANS WILL BE RETAINED IN THIS | | | OFFICE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-11 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-08-11 |
Time |
16:35 |
Sent To |
PC |
|
| Notes |
| 2008-08-11 16:57:33 | RESIDENTIAL (R3) PARTIAL DEMOLITION, BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1-ALL DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY | | | THE ARCHITECTSHOWN ON THE TITLE BLOCK AS REQUIRED BY | | | CHAPTER 481 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-26 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-26 |
Time |
10:26 |
Sent To |
P |
|
| Notes |
| 2008-08-26 10:38:34 | | | | | | | | | | PROVISO | | | | | | PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR | | | REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE | | | REMOVED FOR DEMOLITION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-29 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-29 |
Time |
12:31 |
Sent To |
Z |
|
| Notes |
| 2008-07-29 12:52:52 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} SHEET A101-THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK | | | APPEARS ON THE PLANS, MUST SIGN AND SEAL THE PLAN PER | | | 481.221(1)(B)FS. | | | | | | 2} SHEET A104-THE PERSON TAKING RESPONSIBILITY FOR THE | | | DESIGN MUST PRINT AND SIGN THEIR NAME TO SAME, ALL | | | SHEETS, PER 106.1.3.FBC. | | | | | | 3} THERE ARE TWO BUILDINGS SHOWN ON THE PLANS, THE | | | APPLICATION DESCRIPTION OF THE PROJECT DOES NOT MENTION | | | TWO BUILDINGS. PLEASE CLARIFY THE INTENT OF THIS | | | APPLICATION.105.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-28 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-28 |
Time |
15:50 |
Sent To |
P |
|
| Notes |
| 2008-08-28 15:51:17 | TO "PLUMB" MIKE P. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-21 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-21 |
Time |
09:15 |
Sent To |
E |
|
| Notes |
| 2008-08-21 09:16:05 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-04 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-04 |
Time |
08:56 |
Sent To |
P |
|
| Notes |
| 2008-08-04 08:56:53 | TO "SFR" "P" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-11 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-24 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2008-07-24 11:13:56 | TO "SFR "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2008-07-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-25 |
Time |
09:38 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-07-25 |
Time |
09:38 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-29 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-29 |
Time |
14:01 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-26 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-26 |
Time |
14:20 |
Sent To |
B |
|
| Notes |
| 2008-08-26 16:15:03 | PLUMBING PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WEL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | | COMMENTS. | | | NOTE: THERE WAS NO COMMENT RESPONSE FROM THE | | | DESIGNER. | | | | | | | | | 1. "OK" COMMENT ADDRESSED | | | | | | 2. SHEET A101: THE ARCHITECTURAL FIRM WHOSE TITLE | | | BLOCK APPEARS ON THE PLANS MUST SIGN AND SEAL THE PLAN. | | | PER FS 481.221(1)(B). | | | | | | **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE | | | COMMENT WAS NOT ADDRESSED. MPERRY DESIGN, INC CAN NOT | | | TAKE RESPOSIBILITY FOR THE DESIGN WHEN AN ARCHITECTURAL | | | FIRM IS INDICATED ON THE TITLE BLOCK. THE RESUBMITTED | | | SHEET A101 STILL HAS AN ARCHITECTURAL FIRM ON THE TITLE | | | BLOCK AND PER FS 481.221(1)(B) THE ARCHITECTURAL FIRM | | | INDICATED ON THE PLAN SHEET TITLE BLOCK MUST SIGN, DATE | | | AND SEAL SAID PLAN SHEET. | | | | | | 3. "OK" COMMENT ADDRESSED. | | | | | | 4. PLEASE ADD THE FOLLOWING NOTE TO THE PLAN SHEETS | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS | | | SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND | | | AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR | | | TO COVERING DEMO WORK WITH FINNISH WALLS, CEILINGS, OR | | | POURED CONCRETE SLABS. | | | | | | **THE COMMENT WAS PARTIALLY ADDRESSED. PLEASE KNOW | | | THAT A PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS | | | REQUIRED OF THE PLUMBING DEMO WORK PRIOR TO COVERING | | | DEMO WORK WITH FINNISH WALLS, CEILINGS, OR POURED | | | CONCRETE SLABS.PER SECTION 704.5 DEAD ENDS AND (WP.P.B. | | | AS AMENDED) SECTION 109.3 REQUIRED INSPECTIONS. | | | | | | **THE FOLLOWING IS A NEW COMMENT** | | | | | | 5. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | | (4) TIMES THE FEE. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-04 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-04 |
Time |
11:03 |
Sent To |
B |
|
| Notes |
| 2008-08-04 11:18:36 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE PERMIT APPLICATION DOES NOT MATCH THE SUBMITTED | | | PLANS. THE SUBMITTED PLANS ARE INDICATINT THE PARTIAL | | | DEMOLITION OF TWO BUILDINGS CONSISTING OF A MAIN HOUSE | | | AND A GUEST HOUSE. PLEASE CORRELATE THE PERMIT | | | APPLICATION WITH THE PLANS. PER (W.P.B. AS AMENDED) | | | SECTION 105.1 REQUIRED. | | | | | | 2. SHEET A101: THE ARCHITECTURAL FIRM WHOSE TITLE | | | BLOCK APPEARS ON THE PLANS MUST SIGN AND SEAL THE PLAN. | | | PER FS 481.221(1)(B). | | | | | | 3. SHEET 104: THE PERSON TAKING RESPONSIBILITY FOR THE | | | DESIGN MUST PRINT AND SIGN (ORIGINAL SIGNATURE) THEIR | | | NAME TO PLAN SHEET. PER (W.P.B. AS AMENDED) SECTION | | | 106.1.3. | | | | | | 4. PLEASE ADD THE FOLLOWING NOTE TO THE PLAN SHEETS | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS | | | SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND | | | AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR | | | TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR | | | POURED CONCRETE SLABS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-03 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-08-03 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-08-03 |
Time |
13:06 |
Sent To |
I |
|
| Notes |
| 2008-08-03 13:07:30 | **ZONING REVIEW N/A.SCOPE OF WORK DOES NOT EXCEED 50% | | | RULE.** |
|
|