Plan Review Details - Permit 08070674
Plan Review Stops For Permit 08070674
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-29 Cont ID  
Sent By jgomez Date 2008-08-29 Time 14:51 Rev Time 0.00
Received By jgomez Date 2008-08-29 Time 14:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-27 Cont ID  
Sent By jgomez Date 2008-08-27 Time 11:47 Rev Time 0.00
Received By jgomez Date 2008-08-27 Time 11:47 Sent To PC
Notes
2008-08-27 11:49:59RESIDENTIAL(R3) PARTIAL DEMOLITION, BUILDING REVIEW
 SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY THE
 ARCHITECT RESPONSIBLE OF THE PLANS (AMES BENNETT &
 ASSOCIATES) AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
 (REPEAT COMMENT).
  
 NOTE:ONE COPY OF PLANS WILL BE RETAINED IN THIS
 OFFICE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By jgomez Date 2008-08-11 Time 16:54 Rev Time 0.00
Received By jgomez Date 2008-08-11 Time 16:35 Sent To PC
Notes
2008-08-11 16:57:33RESIDENTIAL (R3) PARTIAL DEMOLITION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-ALL DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY
 THE ARCHITECTSHOWN ON THE TITLE BLOCK AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-26 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 10:35 Rev Time 0.00
Received By btrobaug Date 2008-08-26 Time 10:26 Sent To P
Notes
2008-08-26 10:38:34 
  
  
 PROVISO
  
 PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 12:52 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 12:31 Sent To Z
Notes
2008-07-29 12:52:52 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET A101-THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK
 APPEARS ON THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 2} SHEET A104-THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO SAME, ALL
 SHEETS, PER 106.1.3.FBC.
  
 3} THERE ARE TWO BUILDINGS SHOWN ON THE PLANS, THE
 APPLICATION DESCRIPTION OF THE PROJECT DOES NOT MENTION
 TWO BUILDINGS. PLEASE CLARIFY THE INTENT OF THIS
 APPLICATION.105.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 15:50 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 15:50 Sent To P
Notes
2008-08-28 15:51:17TO "PLUMB" MIKE P.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 09:15 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 09:15 Sent To E
Notes
2008-08-21 09:16:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 08:56 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 08:56 Sent To P
Notes
2008-08-04 08:56:53TO "SFR" "P"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-11 Cont ID  
Sent By jgomez Date 2008-08-11 Time 17:00 Rev Time 0.00
Received By jgomez Date 2008-07-24 Time 11:13 Sent To  
Notes
2008-07-24 11:13:56TO "SFR "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 09:38 Rev Time 0.20
Received By tgordon Date 2008-07-25 Time 09:38 Sent To Z
Notes
2008-07-25 09:38:55DEMO.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-08-29 Cont ID  
Sent By mperson Date 2008-08-29 Time 14:01 Rev Time 0.00
Received By mperson Date 2008-08-29 Time 14:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-26 Cont ID  
Sent By mperson Date 2008-08-26 Time 14:20 Rev Time 0.00
Received By mperson Date 2008-08-26 Time 14:20 Sent To B
Notes
2008-08-26 16:15:03PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WEL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WAS NO COMMENT RESPONSE FROM THE
 DESIGNER.
  
  
 1. "OK" COMMENT ADDRESSED
  
 2. SHEET A101: THE ARCHITECTURAL FIRM WHOSE TITLE
 BLOCK APPEARS ON THE PLANS MUST SIGN AND SEAL THE PLAN.
 PER FS 481.221(1)(B).
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 COMMENT WAS NOT ADDRESSED. MPERRY DESIGN, INC CAN NOT
 TAKE RESPOSIBILITY FOR THE DESIGN WHEN AN ARCHITECTURAL
 FIRM IS INDICATED ON THE TITLE BLOCK. THE RESUBMITTED
 SHEET A101 STILL HAS AN ARCHITECTURAL FIRM ON THE TITLE
 BLOCK AND PER FS 481.221(1)(B) THE ARCHITECTURAL FIRM
 INDICATED ON THE PLAN SHEET TITLE BLOCK MUST SIGN, DATE
 AND SEAL SAID PLAN SHEET.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. PLEASE ADD THE FOLLOWING NOTE TO THE PLAN SHEETS
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH WALLS, CEILINGS, OR
 POURED CONCRETE SLABS.
  
 **THE COMMENT WAS PARTIALLY ADDRESSED. PLEASE KNOW
 THAT A PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS
 REQUIRED OF THE PLUMBING DEMO WORK PRIOR TO COVERING
 DEMO WORK WITH FINNISH WALLS, CEILINGS, OR POURED
 CONCRETE SLABS.PER SECTION 704.5 DEAD ENDS AND (WP.P.B.
 AS AMENDED) SECTION 109.3 REQUIRED INSPECTIONS.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 5. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 (4) TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By mperson Date 2008-08-04 Time 11:03 Rev Time 0.00
Received By mperson Date 2008-08-04 Time 11:03 Sent To B
Notes
2008-08-04 11:18:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PERMIT APPLICATION DOES NOT MATCH THE SUBMITTED
 PLANS. THE SUBMITTED PLANS ARE INDICATINT THE PARTIAL
 DEMOLITION OF TWO BUILDINGS CONSISTING OF A MAIN HOUSE
 AND A GUEST HOUSE. PLEASE CORRELATE THE PERMIT
 APPLICATION WITH THE PLANS. PER (W.P.B. AS AMENDED)
 SECTION 105.1 REQUIRED.
  
 2. SHEET A101: THE ARCHITECTURAL FIRM WHOSE TITLE
 BLOCK APPEARS ON THE PLANS MUST SIGN AND SEAL THE PLAN.
 PER FS 481.221(1)(B).
  
 3. SHEET 104: THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN (ORIGINAL SIGNATURE) THEIR
 NAME TO PLAN SHEET. PER (W.P.B. AS AMENDED) SECTION
 106.1.3.
  
 4. PLEASE ADD THE FOLLOWING NOTE TO THE PLAN SHEETS
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 13:07 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 13:06 Sent To I
Notes
2008-08-03 13:07:30**ZONING REVIEW N/A.SCOPE OF WORK DOES NOT EXCEED 50%
 RULE.**