Plan Review Details - Permit 08070652
Plan Review Stops For Permit 08070652
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-28 Cont ID  
Sent By rmcdouga Date 2008-08-28 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2008-08-28 Time 16:45 Sent To  
Notes
2008-08-28 16:45:57OK PER REVIEW BY LUIS MARTINEZ.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-06 Cont ID  
Sent By shill Date 2008-08-06 Time 09:55 Rev Time 0.00
Received By shill Date 2008-08-06 Time 09:55 Sent To FIRE
Notes
2008-08-06 10:26:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.INCORPORATE HANDWRITTEN CHANGES INTO THE PLAN.
  
 2.DECLARE OCCUPANCY CLASSIFICATION FBC CHAPTER 3.
  
 3.SHOW USE OF THIS AREA.A TABLE TOP IS SHOWN; IS
 THIS DINING AREA?SHOW PROPSED SEATING FBC11-5, NOTE
 WHETHER THIS IS FIXED SEATING OR NON FIXED SEATING.
  
 4.SHOW THE DIMENSION BETWEEN COLUMNS, AND THE
 DIMENSION FROM EDGE OF TABLE TOP TO WALL.
  
 5.DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 6.DECLARE GOVERNING CODE INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 7.THE STEEL COLUMNS ARE SHOWN AS "REMOVABLE".WHAT
 DOES THIS MEAN?ARE THE STEEL COLUMNS TO BE REMOVED
 AND REPLACED BY PRECAST, OR WILL THE PRECAST GO AROUND
 THE EXISTING STEEL COLUMNS?ARE THEY STRUCTURAL?WHY
 WOULD A STRUCTURAL ELEMENT BE "REMOVABLE"?
  
 8.DECLARE DESIGN LOAD CRITERIA, DEAD AND LIVE LOADS.
  
  
 9.WHAT DO THE LINES REPRESENT?IS THIS A ROOF
 FRAMING PLAN?PROVIDE INFORMATION REGARDING THE
 SUBSTRATE AT TOP AND BOTTOM.IF YOU USE A 4" SELF
 TAPPING SCREW (PLAN STATES SELF TAPING, DO YOU MEAN
 SELF TAPPING?), HOW WILL THIS AFFECT THE ROOF DECK?
  
 10. PROVIDE A DETAIL FOR THE PRECAST CONCRETE COLUMN
 AND THE ATTACHMENT DETAIL, TOP AND BOTTOM.SEE ALSO
 OTHER COMMENTS.
  
 11. PROVIDE A SURVEY OF THIS PROPERTY.BASED ON THE
 ENGINEER'S PLAN, THIS PROJECT ENCROACHES THE PROPERTY
 LINE.SEE FBC32.SHOW DIMENSION OF ENCROACHMENT.
  
 12. PROVIDE AN ELEVATION WITH ALL DIMENSIONS.
  
 13. PROVIDE A STRUCTURAL DETAIL OF THE EXISTING PROJECT
 AREA.
  
 14. THE SITE PLAN DOES NOT MATCH THE ELECTRICAL LAYOUT
 PLAN.GRAPHICALLY THE 3.97 DIMENSION IS SHOWN AS
 APPROXIMATELY 1/4 OF THE TOTAL WIDTH, BUT THE TOTAL
 WIDTH IS SHOWN AS 7'10".
  
 15.ARE ANY EXIT DOOR ON THE EXISTING COMMERCIAL
 BUILDING LEADING INTO THE PROPOSED PROJECT AREA?

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-08-05 Cont ID  
Sent By btrobaug Date 2008-08-05 Time 09:14 Rev Time 0.00
Received By btrobaug Date 2008-08-05 Time 09:14 Sent To B
Notes
2008-08-05 09:15:00 
  
 TO MISC. #3./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 09:19 Sent To E
Notes
2008-08-04 09:19:17TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-06 Cont ID  
Sent By shill Date 2008-08-06 Time 10:26 Rev Time 0.00
Received By shill Date 2008-07-28 Time 09:17 Sent To  
Notes
2008-07-28 09:21:19TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 10:47 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 10:47 Sent To I
Notes
***NONE***