Plan Review Details - Permit 08070649
Plan Review Stops For Permit 08070649
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By jgomez Date 2008-08-05 Time 16:48 Rev Time 0.00
Received By jgomez Date 2008-08-05 Time 16:46 Sent To PC
Notes
2008-08-05 16:56:36RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY 2300 N JOG RD (561)233-5120 TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF
 IMPACT FEES PAID RECEIPT IF FEES ARE DUE.
  
 3-A) ACCORDING TO SEC. R301.2.1.4(3) OF 2004 FLORIDA
 RESIDENTIAL CODE THE BUILDINGIS LOCATED IN EXPOSURE
 CATEGORY "C". REVISE DESIGN INFORMATION ON SHEET 1 OF
 10 AND 10 OF 10 AS REQUIRED.
  
 B)CLARIFY HOW IS THE BUILDING DESIGNED AS ENCLOSED
 IF SOFFIT ON STUDIO AREA IS OPEN AND IF COVERED PORCH
 IS OPEN ON THREESIDES.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004TO VERIFY COMPLIANCE WITH DESIGN LOADS OF
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 5- SPECIFYOPENINGS DESIGN PRESSURES AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 NOTE:COORDINATE WITH ITEM #3 ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FRENCH DOORS AS SHOWN ON PLANS.PROVIDE COMPLETE
 PRODUCT APPROVAL REPORT.FLORIDA PRODUCT APPROVAL
 FL7133 SUBMITTED IS MISSING THE TECHNICAL DRAWINGS
 SHOWING THE APPROVED DOORS.
  
 B) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING.
 ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
  
 C) SINGLE HUNG WINDOWS. PROVIDE COMPLETE PRODUCT
 APPROVAL REPORT. PRODUCT APPROVAL FL239-R11
 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
  
 D) HORIZONTAL SLIDER WINDOWS. PROVIDE COMPLETE
 PRODUCT APPROVAL REPORT.PRODUCT APPROVAL FL242-R7
 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
  
 E) ROOF SHINGLES.
  
 F) PRECAST LINTELSSPECIFIED ON PLANS AND DETAILS.
  
 G) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NOTE:PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED
 TO SUBMITCOMPLETE REPORT.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- OWES $16.72 FOR RADON FEES.
  
 9- SURVEY SUBMITTED HAS INCORRECT FLOOD ZONE AND PANEL
 NUMBER.CORRECT INFORMATION IS FLOOD ZONE "B" AND
 CORRECT MAP IS 120192 - 0125 BDATED 10/15/82.
 REVISE AS REQUIRED.
  
 10- SHEET 1 OF 10:SQUARE FOOTAGE DATA DOESN'TADD
 UP. 960 PLUS 711 IS EQUAL TO 1671, NOT 1673. REVISE AS
 REQUIRED.
  
 11- SHEET 2 OF 10:IF WINDOWSLOCATED NEXT TO FRENCH
 DOORS ON EASTWALL OF STUDIO DON'T HAVE IMPACT GLASS,
 THEN THEY NEEDHAVE SAFETY GLAZING AS REQUIRED BY SEC.
 R308.4(6) OF 2004 FLORIDA RESIDENTIAL CODE.SPECIFY ON
 PLANS AS REQUIRED.
  
 12- SHEET 6 OF 10:A) SPECIFY SPACING FOR 2X 10
 RAFTERS ON COVERED PATIO AREA.
  
 B) SPECIFY ROOF PITCH.
  
 C) SPECIFY CALCULATED UPLIFT LOADS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE TO VERIFY
 COMPLIANCE WITH SPECIFIED CONNECTOR (ONE H1 SIMPSON
 CONNECTION BETWEEN RAFTER AND (3)2X12 BEAM IN OPEN
 COVERED PATIO AREA.AND ONLY ONE H1 SIMPSON CONNECTOR
 BETWEEN RAFTER AND DOUBLE 2X PLATE ON ENCLOSED STUDIO
 AREA.)
  
 D) PROVIDE COMPLETE FRAMING DETAIL AT GABLE ENDS
 SHOWING COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.HOW ARE THE LOADS TRANSFERRED TO THE
 GABLE END WALL?.
  
 13-SHEET 8 OF 10:CLARIFY/REVISE SIZE OF T & G ROOF
 SHEATHING.DETAIL ON COVERED PATIO SECTION SAYS 5/4" T
 & G SHEATHING, WHILE DETAIL ON COVERED PATIO WALL
 SECTION SAYS 3/4" X 6" T & G SHEATHING.
  
 14- SHEET 9OF 10:REVISE LINTEL SCHEDULE TO MATCH
 PLANS.MISSING L-3 AND SIZE OF L-2 IS INCORRECT.
  
 15- SHEET 10 OF 10:
 A) UPDATE GENERAL STRUCTURAL NOTE # 4(A). SPECIFY
 CURRENT CODE. VERSION.
  
 B) UPDATE YEAR REFERENCE FOR MASONRY NOTE#1. SEE
 CHAPTER43 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 CURRENT YEAR TO BE USED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 12:09 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 11:07 Sent To Z
Notes
2008-07-29 12:09:46 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN ELECTRODE
 ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR
 FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH,
 CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE
 BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT
 LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING
 OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT
 SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED
 TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR
 OTHER EFFECTIVE MEANS.**INDICATE COMPLIANCE ON THE
 PLAN.
  
 2} } PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 INCLUDING THE METER ENCLOSURE, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.SEE 230.70(A)(1)
 REGARDING LOCATION WITH RELATION TO THE FIRST MEANS OF
 DISCONNECT.
  
 3} THE METER SHOWN ON THE RISER IS SHOWN AS 150 AMP,
 THE PANEL IS SHOWN AS A 200 AMP MCP.THE #1 SERVICE
 CONDUCTORS ARE RATED FOR 150 AMPS PER 310.15(B)(6), AND
 ARE IN VIOLATION OF OF THAT ARTICLE AND 240.6 BY
 TERMINATING IN 200AMP OCP.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 5} 210.70(A)(2)(B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT. ***LOCATE
 SAME ON PLANS.
  
 NOTE: THE 2007 REVISIONS TO THE 2004 FBC HAS BEEN
 ADOPTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 09:01 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 09:01 Sent To B
Notes
2008-08-04 09:02:13TO "SFR" "B"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By jgomez Date 2008-08-05 Time 16:56 Rev Time 0.00
Received By jgomez Date 2008-07-23 Time 11:27 Sent To  
Notes
2008-07-23 11:27:46TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 09:20 Rev Time 0.20
Received By tgordon Date 2008-07-25 Time 09:20 Sent To Z
Notes
2008-07-25 09:20:59NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 13:04 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 13:03 Sent To I
Notes
2008-08-03 13:03:41**ZONING FAILED**
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE IRONHORSE ESTATE DESIGN CRITERIA,
 THE REAR SETBACK IS A MINIMUM OF 35 FEET TO THE
 BUILDING.PLEASE REVISE SITE PLAN TO COMPLY WITH THIS
 PROVISION.I HAVE INCLUDED A COPY OF THE DESIGN
 GUIDELINES, SEE ATTACHED.
  
 3. EXTERIOR COLORS SHALL BE APPROVED INDIVIDUALLY, IF
 APPLICABLE, PLEASE PROVIDE A LETTER FROM THE IRONHORSE
 HOME OWNER?S ASSOCIATION INDICATING APPROVAL OF THE
 EXTERIOR COLORS OF THE ADDITION.
  
 4. INDICATE ON THE SURVEY THE SETBACK DIMENSIONS OF THE
 PROPOSED ADDITION TO ALL PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT