Plan Review Details - Permit 08070648
Plan Review Stops For Permit 08070648
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-12-11 Cont ID  
Sent By shill Date 2008-12-11 Time 16:02 Rev Time 0.00
Received By shill Date 2008-12-11 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-11-24 Cont ID  
Sent By shill Date 2008-11-24 Time 14:24 Rev Time  
Received By shill Date 2008-11-24 Time 14:16 Sent To  
Notes
2008-11-24 14:19:40***CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE DESIGN PRESSURES USED FOR OPENINGS 5, 6 ARE FOR
 -40 AND LESS, BUT THE DESIGN PRESSURE REQUIRED IS OVER
 40PSF. NOTE THAT THIS IS EXPOSURE C, SO ALL PRESSURES
 WILL BE GREATER THAN 40PSF.
  
 2. OPENING 4 SPECIFIES 2 TOP, 40.08 PSF, BLOCK.
 CONTRACTOR USED THE COLUMN FOR LESS THAN -40PSF,
 CONCRETE SUBSTRATE. PLEASE REVISE.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-11-12 Cont ID  
Sent By shill Date 2008-11-12 Time 11:36 Rev Time 0.00
Received By shill Date 2008-11-12 Time 11:36 Sent To  
Notes
2008-11-12 11:39:28***CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT APPEARS THAT ANCHOR SPACING INTO CONCRETE WAS
 USED, PAGE 10. HOWEVER, "CONCRETE FILLED BLOCK"
 REQUIRES USE OF THE "MASONRY" COLUMN AS THIS DOES NOT
 HAVE THE SAME STRENGTH AS FORMED AND POURED CONCRETE.
 PLEASE REVISE ANCHOR SCHEDULE ACCORDINGLY. EXAMPLES
 WERE PROVIDED IN PREVIOUS REVIEWS.
  
 FOR EXAMPLE, OPENING 4, 1 (TOP) WOULD NOT BE ALLOWED
 (DIFFERENT CONNECTION DETAIL REQUIRED). 9 (BOTTOM)
 WOULD REQUIRE 7" SPACING, NOT 12" AS SPECIFIED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-10-17 Cont ID  
Sent By shill Date 2008-10-17 Time 15:29 Rev Time 0.00
Received By shill Date 2008-10-17 Time 15:29 Sent To  
Notes
2008-10-17 15:35:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS BUILDING IS LOCATED IN EXPOSURE C, SEE FBC
 R301.2.1.4.
  
 2. ALTHOUGH DESIGN PRESSURES ARE GREATER THAN -40PSF,
 IT APPEARS THAT THE CHART FOR -40PSF HAS BEEN USED TO
 SPECIFY ANCHOR SPACING. PLEASE SEE CHARTS ON SHEET 10
 (NOT SHEET 9). FOR INSTANCE, SEE OPENING 4. FOR A
 PRESSURE OF -40.08, CONNECTION TYPE 2, TOP, INTO
 BLOCKIS NOT ALLOWED. CONNECTION TYPE 11 BOTTOM REQUIRES
 4 1/2" ANCHOR SPACING; 11" SPECIFIED. PLEASE REVISE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-10-02 Cont ID  
Sent By shill Date 2008-10-02 Time 10:18 Rev Time 0.00
Received By shill Date 2008-10-02 Time 10:18 Sent To  
Notes
2008-10-02 10:21:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. +-40PSF HAS BEEN HIGHLIGHTED ON THE PRODUCT
 APPROVALS (FOR INSTANCE, SEE SHEET 9 OF THE STORM PANEL
 PA). HOWEVER, THE INSTALLATION SCHEDULE STATES THAT
 DESIGN PRESSURE IS +-60PSF FOR SOME OPENINGS; +-90PSF
 FOR OTHERS. THE DISCREPANCY IN DESIGN PRESSURE HAS
 RESULTED IN OTHER COMMENTS. INFORMATION HIGHLIGHTED ON
 THE PRODUCT APPROVALS SHOULD BE CONSISTENT WITH THE
 INSTALLATION SCHEDULE AND THE JOB. FBC R 301.
  
 2. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL
 PRODUCT APPROVAL; SHUTTER CONNECTION MOUNTING TYPE 2
 TOP, TAPCON, MASONRY (BLOCK), 60 PSF CANNOT BE USED.
 THIS APPLIES TO OTHER OPENINGS.
  
 3. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL PA;
 MOUNTING TYPE 11 BOTTOM, BLOCK, -60PSF REQUIRES 4"
 ANCHOR SPACING.
  
 4. SHEET 10, ACCORDION PRODUCT APPROVAL, WALL MOUNT 3
 IS HIGHLIGHTED BUT INSTALLATION SCHEDULE SPECIFIES "C",
 OPENING 7. WHAT IS C? THIS SHOULD CORRELATE WITH THE
 ANCHOR CHARTS.
  
 5. OPENING 7, WALL MOUNT 3 (HIGHLIGHTED ON THE PRODUCT
 APPROVAL), -90PSF REQUIRES 4" ANCHOR SPACING, SEE SHEET
 10.
  
 6. ALL COMMENTS APPLY TO OTHER OPENINGS; THESE SPECIFIC
 OPENINGS WERE PROVIDED AS AN EXAMPLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-29 Cont ID  
Sent By shill Date 2008-08-29 Time 10:31 Rev Time 0.00
Received By shill Date 2008-08-29 Time 10:31 Sent To  
Notes
2008-08-29 10:46:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE ALL OPENINGS. NA WAS WRITTEN IN THE COLUMN FOR
 SHUTTER CONNECTION MOUNTING TYPE. THIS SHOULD CORRELATE
 WITH THE ANCHOR CHARTS; FOR INSTANCE, ACCORDION, PAGE
 10, MOUNTING TYPE WOULD BE A THROUGH L FOR ACCORDIONS,
 AND (AN EXAMPLE) 1 TOP, 1 BOTTOM FOR STORM PANELS (SEE
 SHEET 9).
  
 2. MOUNTING TYPE A WAS HIGHLIGHTED ON THE ACCORDION
 SHUTTER PRODUCT APPROVAL; THIS REQUIRES A CONCRETE
 SUBSTRATE, NOT BLOCK.
  
 3. A 2" EDGE DISTANCE REQUIRES A .50 FACTOR, SEE PAGE
 11 OF ACCORDION PRODUCT APPROVAL, PAGE 9 OF PANEL
 PRODUCT APPROVAL.
  
 4. SEE OPENINGS 4, 5, 6. YOU'VE HIGHLIGHTED THE COLUMN
 FOR CONCRETE ON THE PRODUCT APPROVAL, 12" ANCHOR
 SPACING, BUT INSTALLATION SCHEDULE STATES THIS IS
 BLOCK. YOU MUST USE THE MASONRY COLUMN FOR BLOCK.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By shill Date 2008-08-11 Time 16:37 Rev Time 0.00
Received By shill Date 2008-08-11 Time 16:37 Sent To  
Notes
2008-08-11 16:38:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 _XX_2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 ____3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____4.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____5.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 2
 ABOVE.
  
 ____6.REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE
 FOR EXPOSURE B.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-11-20 Cont ID  
Sent By adarroug Date 2008-11-20 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-11-20 Time 10:45 Sent To B
Notes
2008-11-20 10:46:08TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 14:14 Sent To B
Notes
2008-11-03 14:15:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 09:22 Sent To B
Notes
2008-10-17 09:23:28TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 10:54 Sent To B
Notes
2008-09-25 10:55:17TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 11:47 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 11:47 Sent To B
Notes
2008-08-21 11:48:18TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-11 Time 11:47 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 10:43 Sent To  
Notes
2008-07-23 10:45:18TO "MISC" BOX#1