Plan Review Details - Permit 08070646
Plan Review Stops For Permit 08070646
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-31 Cont ID  
Sent By rbrown Date 2008-07-31 Time 18:16 Rev Time 0.00
Received By rbrown Date 2008-07-31 Time 18:16 Sent To  
Notes
2008-07-31 18:16:54PLANS REVIEWED AND STAMPED BY LUIS MARTINEZ ON 7/30/08.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-09-04 Cont ID  
Sent By btrobaug Date 2008-09-04 Time 16:32 Rev Time 0.00
Received By btrobaug Date 2008-09-04 Time 16:31 Sent To  
Notes
2008-09-04 16:32:00 
  
  
  
 PROVISO
  
 907.2.10.1.2 GROUPS R-2, R-3, R-4 AND I-1.
 SINGLE- OR MULTIPLE-STATION SMOKE ALARMS SHALL BE
 INSTALLED AND MAINTAINED IN GROUPS R-2, R-3, R-4 AND
 I-1, REGARDLESS OF OCCUPANT LOAD AT ALL OF THE
 FOLLOWING LOCATIONS:
 1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
 2. IN EACH ROOM USED FOR SLEEPING PURPOSES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-25 Cont ID  
Sent By btrobaug Date 2008-08-25 Time 16:30 Rev Time 0.00
Received By btrobaug Date 2008-08-25 Time 15:55 Sent To  
Notes
2008-08-25 16:30:04 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY. SEE FS 481.229(C) INDICATING WORK
 OVER $25000.00 REQUIRES AN ARCHITECT AND EXEMTIONS DO
 NOT APPLY
  
 2} PLEASE NOTE THAT HAND DRAWN CHANGES TO THE PLAN ARE
 NOT ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE
 BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481,
 AS APPLICABLE.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By btrobaug Date 2008-08-01 Time 11:38 Rev Time 0.00
Received By btrobaug Date 2008-08-01 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 09:16 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 09:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By mawillia Date 2008-08-05 Time 14:20 Rev Time 0.00
Received By mawillia Date 2008-08-05 Time 13:40 Sent To  
Notes
2008-08-05 14:19:55*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3THE REMOVAL OF AND/OR STOCKING OF BUILDING MATERIALS
 AND SUPPLIES SHALL NOT BE STORED IN THE EXIT AISLE
 CORRIDORS AS TO HINDER OR INTERFERE WITH ACCESS TO /
 EGRESS FROM OTHER TENANT SPACES ON THE FLOOR OR THE
 BUILDING..
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE THE INTERIOR FINISH MATERIAL FOR ANY
 NEW WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 6.SHOW THE LOCATION OF THE SMOKE ALARMS (SA) FOR THE
 PROPOSED FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 12:33 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 12:33 Sent To  
Notes
2008-09-03 12:36:29TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 16:15 Sent To  
Notes
2008-08-25 08:28:01TO BOB #2.
2008-08-18 16:16:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By mawillia Date 2008-08-05 Time 13:40 Rev Time 0.00
Received By mawillia Date 2008-07-23 Time 11:05 Sent To  
Notes
2008-07-28 09:05:24TO "BOB"#13
2008-07-23 11:12:28WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 14:45 Rev Time 0.30
Received By tgordon Date 2008-08-26 Time 14:45 Sent To  
Notes
2008-08-26 14:46:46*** PROVISO ***
 1)IN REGARDS TO THE A/C UNIT. PER 2004 FBC/R M1305.1
 APPLIANCE ACCESS FOR INSPECTION SERVICE, REPAIR AND
 REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION. THIRTY INCHES OF WORKING SPACE SHALL BE
 PROVIDED IN FRONT OF THE CONTROL SIDE TO SERVICE AN
 APPLIANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-28 Cont ID  
Sent By tgordon Date 2008-07-28 Time 12:14 Rev Time 0.30
Received By tgordon Date 2008-07-28 Time 12:14 Sent To  
Notes
2008-07-28 12:22:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) NOTICE: IN REGARDS TO THE A/C UNIT. PER 2004 FBC/R
 M1305.1 APPLIANCE ACCESS FOR INSPECTION SERVICE, REPAIR
 AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION. THIRTY INCHES OF WORKING SPACE SHALL BE
 PROVIDED IN FRONT OF THE CONTROL SIDE TO SERVICE AN
 APPLIANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-09-05 Cont ID  
Sent By mperson Date 2008-09-05 Time 08:19 Rev Time 0.00
Received By mperson Date 2008-09-05 Time 08:19 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-26 Cont ID  
Sent By mperson Date 2008-08-26 Time 10:27 Rev Time 0.00
Received By mperson Date 2008-08-26 Time 10:07 Sent To  
Notes
2008-08-26 10:26:36PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 3. THE SANITARY ISOMETRIC RISER DIAGRAMS REQUIRE THE
 FOLLOWING.
 NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA
 BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED
 NAME OF THE RESPONSIBLE PERSON WITH THE ORIGINAL
 SIGNATURE AND DATE ON SUCH INFORMATION. PER (W.P.B. AS
 AMENDED) SECTION *106.3.4.3. PLEASE KNOW THAT THE
 PLUMBING CONTRACTOR UNDER PROVISION OF FS 471.003(2)(H)
 AND FBCB 105.3.1.2 CAN BE THE DESIGNER AS LONG AS THEY
 ARE THE INSTALLER OF THE SYSTEM THEY DESIGN.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By mperson Date 2008-07-31 Time 10:58 Rev Time 0.00
Received By mperson Date 2008-07-31 Time 10:58 Sent To  
Notes
2008-07-31 11:09:40PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2. PROPOSED FLOOR PLAN BATH 1: PLEASE CLARIFY IF THE
 TUB IS BEING REPLACED WITH A SHOWER IN THIS BATH. THE
 FIXTURE BEING INDICATED ON THE PLANS IS A SHOWER. PER
 FBC-2004 PLUMBING SECTION 401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731