| 2008-07-24 09:01:09 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. NOTE: THE SUBMITTED GAS PLANS CAN NOT BE APPROVED |
| | DUE TO THE FACT THAT THERE IS ALREADY AN APPROVED GAS |
| | PLAN FOR THE COMMERCIAL GENERATOR ON GEN/COM PERMIT |
| | #07040466 THAT IS SIGNED AND SEALED BY AN ARCHITECT. |
| | PLEASE KNOW THAT YOUR SUBMITTED PLANS ARE DIFFERENT |
| | THAN THE APPROVED PLANS BEING THAT THE APPROVED PLANS |
| | ARE INSTALLING 1-1/2" SCHEDULE 40 METALLIC ABOVE GROUND |
| | AND YOUR PLANS ARE USING 2" PE PIPING UNDERGROUND. |
| | IN ORDER TO RECIEVE A GAS PERMIT FOR THIS JOB THE |
| | RESUBMITTED PERMIT APPLICATION SHOULD STATE IN THE |
| | "DESCRIBE PROJECT IN DETAIL" SECTION OF THE PERMIT |
| | APPLICATION THE FOLLOWING, "GAS PERMIT PER APPROVED |
| | GEN/COM PERMIT #07040466." PLEASE KNOW THAT ANY CHANGES |
| | FROM THE APPROVED SET OF PLANS WILL HAVE TO HAVE THE |
| | ORIGINAL DESIGN PROFESSIONAL LEONARD LAFOREST RA |
| | #AROO14784 SUBMIT A SIGNED, SEALED, AND DATED REVISED |
| | GAS ISOMETRIC RISER DIAGRAM. PER CHAPTER 481, FLORIDA |
| | STATUTES, PART 1 AND FAC 61G1-16.004. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |