Plan Review Details - Permit 08070608
Plan Review Stops For Permit 08070608
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-11-06 Cont ID  
Sent By rmcdouga Date 2008-11-06 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2008-11-06 Time 14:31 Sent To  
Notes
2008-11-06 14:32:23ADDED STRUCTURAL REPAIR DETAIL AS REQUESTED BY
 INSPECTOR TO SHEET A1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-25 Cont ID  
Sent By rmcdouga Date 2008-08-25 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2008-08-25 Time 09:54 Sent To  
Notes
2008-08-25 09:54:22BUILDING PROVISO
  
 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 SHINGLES THAT HAVE BEEN APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 2) ADDITIONAL STRUCTURAL DRAWINGS OR CALCULATIONS MAY
 BE REQUIRED BY THE FIELD INSPECTOR AS THE JOB
 PROGRESSES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By rmcdouga Date 2008-07-29 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2008-07-29 Time 16:23 Sent To  
Notes
2008-07-29 14:45:182004 FBC W/2007 REVISIONS
 REPAIR FIRE DAMAGE/REPLACE WINDOWS
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE BUILDING DESIGN DATA ON SHEET CVR-1 SPECIFIES A
 1 STORY STRUCTURE AND PLANS ARE FOR A TWO STORY. PLEASE
 CORRECT. ALSO REVISE CODE REFERENCE TO THE 2004 FBC
 WITH 2007 REVISIONS.
  
 3) SPECIFY THE ROOF TRUSS/ RAFTER SPACING ON THE
 FRAMING PLAN ON SHEET A3. FBC R801.2
  
 4) PLEASE CLARIFY IF THE REPAIRED AREA OF THE ROOF IS
 ENGINEERED TRUSSES OR CONVENTIONAL ROOF FRAMING. THE
 DETAILS AND NOTES REFER TRUSSES AND COMMON FRAMING. IF
 CONVENTIONAL ROOF FRAMING SPECIFY THE RAFTER AND JOIST
 SPANS AND BEARING WALL LOCATIONS. SHOW COMPLIANCE WITH
 R801.2 REQUIREMENTS. ROOF AND CEILING CONSTRUCTION
 SHALL BE CAPABLE OF ACCOMMODATING ALL LOADS IMPOSED
 ACCORDING TO SECTION R301 AND OF TRANSMITTING THE
 RESULTING LOADS TO THE SUPPORTING STRUCTURAL ELEMENTS.
  
  
 5) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING
 FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6
 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING.
  
 6) THE MECHANICAL DRAWING M1 SPECIFIES THE AIR HANDLER
 HANGING FROM THE TRUSSES OR 2X4 RAFTERS. PROVIDE
 CALCULATIONS INDICATING THAT THE TRUSSES OR RAFTERS CAN
 SUPPORT THE AIR HANDLER. R801.2
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD AS
 REQUIRED BY RULE 9B-72 AND FBC 106.3.3* CITY
 AMENDMENTS.
  
 8) ADDITIONAL STRUCTURAL DRAWINGS OR CALCULATIONS MAY
 BE REQUIRED BY THE FIELD INSPECTOR AS THE JOB
 PROGRESSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 15:44 Sent To B
Notes
2008-08-21 15:58:40TO ROBBIE'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By btrobaug Date 2008-07-23 Time 16:18 Rev Time 0.00
Received By btrobaug Date 2008-07-23 Time 15:46 Sent To M
Notes
2008-07-23 16:17:40 
 NONCOMPLIANT
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.SHEET E1
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 11:12 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 11:12 Sent To B
Notes
2008-11-05 11:12:45TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 14:30 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 14:30 Sent To  
Notes
2008-08-15 09:43:18PLANS AT TOM G. DESK.
2008-08-08 14:31:06TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-29 Cont ID  
Sent By rmcdouga Date 2008-07-29 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2008-07-22 Time 11:31 Sent To  
Notes
2008-07-22 11:32:10TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-15 Cont ID  
Sent By tgordon Date 2008-08-15 Time 11:14 Rev Time 0.30
Received By tgordon Date 2008-08-15 Time 11:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By tgordon Date 2008-07-24 Time 09:38 Rev Time 0.40
Received By tgordon Date 2008-07-24 Time 09:38 Sent To P
Notes
2008-07-24 10:02:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN M-1 SHOWS THE AIR HANDLER UNIT ON
 TOP OF THE ATTIC ACCESS, THE UNIT MUST BE SERVICEABLE
 PER 2004 FBC/R M1305.1.3. PLEASE CORRECT.
  
 2) MECHANICAL PLAN SECOND FLOOR SHOWS NO DUCT (FLEX)
 GOING TO THE 14X14 R/A GRILL NEAR THE STAIRWAY. PLEASE
 CORRECT PER 2004 FBC/R M1602.4 AND FBC 106.1.1.
  
 3) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE
 MECHANICAL PLAN AND STATE IF NEW OR EXISTING, PER 2004
 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-07-29 Cont ID  
Sent By rmcdouga Date 2008-07-29 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2008-07-29 Time 16:29 Sent To  
Notes
2008-07-29 16:30:51NO PLUMBING PLANS SUBMITTED AND NO PLUMBING CONTRACTOR
 ON APPLICATION.