| 2008-08-14 09:13:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) INFORMATION MISSING FROM TITLE BLOCK. ENGINEERS |
| | PRINTED NAME AND LICENSE NUMBER, AND THE ENGINEERING |
| | BUSINESS C. OF A. NUMBER. |
| | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| | |
| | 2) THE JOB ADDRESS (325 GARDENIA ST.) MUST APPEAR IN |
| | THE TITLE BLOCK OF EACH PAGE OF THE PLANS, PER CITY WPB |
| | AMEND. 106.1.1. |
| | |
| | 3) THE INFORMATION REGARDING THE VESDA PIPING SYSTEM |
| | MUST APPEAR ON THE MECHANICAL PLANS ALSO, AS THE |
| | MECHANICAL INSPECTOR MAY NOT BE LOOKING AT THE |
| | ELECTRICAL PLANS, PER 2004 FBC/M 602.2.1. |
| | |
| | 4) PLEASE ALSO SHOW THE SIZE (O.D.) OF THE CPVC PIPE |
| | FOR THE VESDA PIPING SYSTEM ON THE MECHANICAL PLANS, |
| | PER 2004 FBC/M 602.2.1 |
| | |
| | 5) PLEASE SHOW COMPLIANCE WITH 2004 FBC/M 606.2.2 |
| | COMMON SUPPLY, RETURN AIR AND SUPPLY AIR SYSTEMS. |
| | WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY |
| | OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN |
| | CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE |
| | RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH |
| | SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. |
| | |
| | 6) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S FOR THE VESDA PIPING SYSTEM, PER 2004 |
| | W.P.B. AMEND. 106.1.2. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |