Plan Review Details - Permit 08070594
Plan Review Stops For Permit 08070594
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By btrobaug Date 2008-09-17 Time 15:19 Rev Time 0.00
Received By btrobaug Date 2008-09-17 Time 14:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-08-06 Cont ID  
Sent By btrobaug Date 2008-07-23 Time 11:13 Rev Time 0.00
Received By btrobaug Date 2008-07-23 Time 06:54 Sent To FIRE
Notes
2008-07-23 07:53:50 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-16 Cont ID  
Sent By mwennerg Date 2008-09-16 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2008-09-16 Time 13:39 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-13 Cont ID  
Sent By btrobaug Date 2008-08-13 Time 12:23 Rev Time 0.00
Received By mawillia Date 2008-08-13 Time 11:49 Sent To M
Notes
2008-08-13 12:23:23*****DENIED*****
  
  
 1.THE ADDRESS OF THE SCOPE OF WORK SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH DAY OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.AS PER LOCAL CODES, SMOKE DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 5.PROVIDE INFORMATION AND SPECS ON THE VESDA SYSTEM
 IN REFEENCE TO ITS FIRE ALARM CAPABILITY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 10:39 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 10:39 Sent To M
Notes
2008-11-21 10:40:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 16:19 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 16:19 Sent To FIRE
Notes
2008-08-26 16:20:06TO "FIRE" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 09:14 Rev Time 0.00
Received By tgordon Date 2008-07-22 Time 09:18 Sent To  
Notes
2008-07-22 09:18:53TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-02 Cont ID  
Sent By rregueir Date 2008-12-02 Time 18:42 Rev Time 0.00
Received By rregueir Date 2008-12-02 Time 18:42 Sent To PC
Notes
2008-12-02 18:42:41REVISED M1.2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By tgordon Date 2008-09-17 Time 11:29 Rev Time 1.45
Received By tgordon Date 2008-09-17 Time 11:29 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-14 Cont ID  
Sent By tgordon Date 2008-08-14 Time 08:17 Rev Time 1.15
Received By tgordon Date 2008-08-14 Time 08:17 Sent To  
Notes
2008-08-14 09:13:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. ENGINEERS
 PRINTED NAME AND LICENSE NUMBER, AND THE ENGINEERING
 BUSINESS C. OF A. NUMBER.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) THE JOB ADDRESS (325 GARDENIA ST.) MUST APPEAR IN
 THE TITLE BLOCK OF EACH PAGE OF THE PLANS, PER CITY WPB
 AMEND. 106.1.1.
  
 3) THE INFORMATION REGARDING THE VESDA PIPING SYSTEM
 MUST APPEAR ON THE MECHANICAL PLANS ALSO, AS THE
 MECHANICAL INSPECTOR MAY NOT BE LOOKING AT THE
 ELECTRICAL PLANS, PER 2004 FBC/M 602.2.1.
  
 4) PLEASE ALSO SHOW THE SIZE (O.D.) OF THE CPVC PIPE
 FOR THE VESDA PIPING SYSTEM ON THE MECHANICAL PLANS,
 PER 2004 FBC/M 602.2.1
  
 5) PLEASE SHOW COMPLIANCE WITH 2004 FBC/M 606.2.2
 COMMON SUPPLY, RETURN AIR AND SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE VESDA PIPING SYSTEM, PER 2004
 W.P.B. AMEND. 106.1.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]