Plan Review Details - Permit 08070580
Plan Review Stops For Permit 08070580
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-01 Cont ID  
Sent By lmartine Date 2009-06-01 Time 16:50 Rev Time 0.00
Received By lmartine Date 2009-06-01 Time 16:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By lmartine Date 2008-11-18 Time 13:07 Rev Time 0.00
Received By lmartine Date 2008-11-18 Time 12:02 Sent To  
Notes
2008-11-18 13:06:33BUILDING REVIEW COMMENTS
  
  
  
 #3 FROM PREVIOUS REVIEW. SURVEYS HAVE NOT BEEN
 PROVIDED.
  
 #5 FROM PREVIOUS REVIEW. ENERGY CALC'S ARE NOT SIGNED
 AND DATED BY OWNER/AGENT.
  
 #6 FROM PREVIOUS REVIEW. COUNTY IMPACT FEES ARE STILL
 DUE.
  
 #7 FROM PREVIOUS REVIEW. VERIFY EMERGENCY EGRESS
 COMPLIANCE FOR BEDROOM OVER GARAGE.
  
 #8 FROM PREVIOUS REVIEW. THE TYPE OF CONSTRUCTION IS
 INCORRECT, TYPE VI UNPROTECTED IS NOT RECOGNIZED WITHIN
 THE 2004 FBC.
  
 #15 FROM PREVIOUS REVIEW. THE REQUIREMENT FOR HANDRAILS
 AND GUARDS HAS NOT BEEN PROVIDED.
  
 #17 FROM PREVIOUS REVIEW. PROVIDE APPROVED SHOP
 DRAWINGS FOR THE HOLLOW CORE PANELS AND THE
 MANUFACTURED STAIRS.
  
 #18 FROM PREVIOUS REVIEW. PROVIDE GARAGE DOOR REPORT.
  
 #20 FROM PREVIOUS REVIEW. FRENCH DOOR SUBMITTAL IS
 STILL INCOMPLETE. PROVIDE FULL PAGE ENGINEERING.
  
 #24 FROM PREVIOUS REVIEW. DEMONSTRATE THE 6" HOLE
 PROVIDED MEETS THE REQUIREMENTS OF R806.1 AND R806.2.
  
 #25 FROM PREVIOUS REVIEW. ATTIC ACCESS IS ALSO REQUIRED
 OVER GARAGE BEDROOM.
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-16 Cont ID  
Sent By amorse Date 2008-08-16 Time 06:35 Rev Time 0.00
Received By amorse Date 2008-08-16 Time 06:35 Sent To PC
Notes
2008-08-16 08:53:29DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 160.78 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
  
 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 4)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL. PLEASE NOTE THAT
 THE OWNER AGENT SECTION WAS NOT SIGNED AND SEVERAL
 CORRECTION ARE REQUIRED TO COMPLY WITH DRAWINGS SUCH AS
 FRAMED SECOND STORY WALLS, NO INSULATION SHOWN ON
 RAISED FLOOR BELOW BALCONY IN MASTER BEDROOM OR
 INSULATION VALUE FOR VAULTED CEILINGS (NOT UNDER
 ATTIC)
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 7)VERIFY THAT BEDROOM WINDOW IN GUEST ROOM ABOVE
 GARAGE MEET EMERGENCY EGRESS PER R310 FBC: MIN. NET
 CLEAR OPENING OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET
 CLEAR OPENING ALL OTHER FLOORS OF 5.7 SQ.FT. IN BOTH
 CASES THE MIN.NET CLEAR HEIGHT SHALL BE 24" AND THE NET
 CLEAR WIDTH SHALL BE 20"
  
 8)VERIFY THE DESIGN CRITERIA THAT WILL BE USED,
 ENGINEERING CALC SHEETS PROVIDED DIFFER FROM THOSE ON
 THE DRAWINGS A-1.1 AND S-1.1 AND S-1.2 FOR WIND SPEED,
 SOIL BEARING CAPACITY , ROOF/TRUSS LOADS ETC. ONCE THE
 DESIGN CRITERIA IS SET BE SURE THAT THE DOOR AND WINDOW
 PRESSURES ARE AS REQUIRED.
  
 9)TIE BEAM #3 ON S-1.1 IS NOT SHOWN IN THE BEAM
 SCHEDULE
  
 10)PLEASE VERIFY HANGER USED FOR 3 PLY GIRDER TRUSS
 AT GARAGE FLOOR FRAMING, SECTION B ON S-1.7 SHOWS A
 SINGLE WIDE HANGER THD28
  
 11)CONFIRM LOCATION OF GIRDER TRUSS IN GARAGEWITH
 LAYOUT OF STAIRS TO SECOND FLOOR, SHOW OPENING LAYOUT
  
 12)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 13)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF
 FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES.
 12" BELOW UNDISTURBED SOIL, SHEETS S-1.7 AND S-1.8 SHOW
 8"
  
 14)PROVIDE BEARING/ATTACHMENT DETAIL FOR HOLLOW CORE
 PANELS AT BALCONYAND EXISTING GARAGE WALLAND AT
 FIREPLACE, SEE S-1.1
  
 15)HANDRAILS AND GUARDS TO SHOW THAT ATTACHMENT WILL
 MEET THE REQUIREMENTS OF 1607.7.1.1 FBC FOR
 CONCENTRATED LOADS ANDFURTHER REQUIREMENTS IN
 SECTIONS R311 & 312 FBC RES.
  
 16)PROVIDE ELEVATIONS FOR NEW GARAGE FLOOR/BEAMS
  
 17) PROVIDE REVIEWED AND APPROVED SHOP DRAWINGS FOR
 HOLLOW CORE PANELS AND MANUFACTURED STAIRS
  
 18)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. NO
 PRODUCT APPROVAL WAS SUBMITTED FOR THE GARAGE DOOR
  
 19)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 20)THE PRODUCT APPROVAL NOA FOR THE FRENCH DOORS IS
 INCOMPLETE, PLEASE SEE THAT THE INFORMATION AT THE TOPS
 OF THE DRAWINGS HAS BEEN CUT OFF, THIS INFORMATION IS
 REQUIRED FOR ATTACHMENT INSPECTION.
  
 21)PER LEVEL 3 ALTERATION IN EXISTING BUILDING CODE
 ACCESSIBILITY REQUIREMENTS SHALL MEET CHAPTER 11 FBC
 FOR RESIDENTIAL CONSTRUCTION PROVIDE AT MINIMUM 1
 ACCESSIBLE BATHROOM PER R322.1.1 FBC 29" CLEAR WITH
 DOOR OPEN 90 DEGREES
  
 22)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 23)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. FASTENERS TO BE 4" O/CIN ZONE 3
 FOR WIND DESIGN SPEEDS OVER 130 MPH
  
 24)PROVIDE VENTILATION REQUIREMENTS ON DRAWINGS PER
 R806.1 AND R806.2 FBC RES.
  
 25)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 26)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 27)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 WITH REVISIONS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY
 FOR REFERENCE.
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006&2007
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006&2007 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-15 Cont ID  
Sent By btrobaug Date 2009-04-15 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2009-04-15 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-13 Cont ID  
Sent By btrobaug Date 2008-11-13 Time 13:23 Rev Time 0.00
Received By btrobaug Date 2008-11-13 Time 07:55 Sent To M
Notes
2008-11-13 11:11:55 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE
 NOTED.
  
 THESE ARE COMMENTS FROM THE PREVIOUS REVIEW THAT WERE
 NOT CORRECTLY RESPONDED TO.***INDICATES FURTHER
 EXPLANATION OF PREVIOUS COMMENT
  
 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED
 SEPARATE***.THE GENERATOR IS STILL SHOWN ON THE RISER
 DIAGRAM AND ON THE MECHANICAL SHEETS. REMOVE FROM
 PLANS, DESIGNATE AS FUTURE OR PROVIDE ALL DOCUMENTATION
 AND PLANS FOR A RESIDENTIAL GENERATOR PERMIT IF IT IS
 TO BE PART OF THIS PERMIT.
  
 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE
 IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE
 ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT
 CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED.
 THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005*** THE CALCULATION
 GIVEN IS INCORRECT PER 220.83. THE AMPERAGE WOULD BE
 212 AMPS AFTER DEMANDS. THE EXISTING SERVICE IS 200
 AMPS..
  
 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM
 FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER
 INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE
 PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A
 REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN
 THE FUTURE***THE PANEL SCHEDULE LISTS THE FEEDER FOR
 PANEL "B" AS 40 AMP (NOT LARGE ENOUGH FOR THE
 CALCULATED LOAD FOR THAT PANEL), AND 60 AMPS FOR PANEL
 "C". CORRELATE THE RISER INFORMATIONN WITH THE PANEL
 INFORMATIO..
  
 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-2/0 AND 1
 #6 CONDUCTORS FEEDING PANEL "A" , "B" AND PANEL "C" IS
 IN VIOLATION OF ANNEX "C" TABLES, 2005 NEC***.THIS
 ISSUE STILL REMAINS ON THE PLAN, NO CHANGE.
  
 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE
 SCHEDULE PER 408.4*** NOW LABELED CORRECTLY BU ON A 15
 AMP CIRCUIT IN VIOLATION OF.210.11(C)(3)--20 AMP
 CIRCUIT.
  
 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA
 ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD
 CALCS. 220.83(B).*** NO CHANGE , STILL NOT LISTED IN
 THE SCHEDULES.
  
 ALL COMMENTS RELATE TO SHEET E-2.0.
  
 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY
 OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF
 THE GARAGE BY THE STAIR WILL MEET THE INTENT***WAS NOT
 ADDED, STILL IN VIOLATION..
  
 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C
 CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL
 SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICALLY*** NO
 NOTE ADDED, NO DISCONNECTS LOCATED ON THE PLAN.
  
 ALL COMMENTS REFER TO SHEET E-2.1
  
 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES*** NOT ADDRESSED..
  
  
 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS
 REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING
 UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH
 A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE
 ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE
 CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE
 NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE
 210.12 NEC.***THE CIRCUITS ASSIGN TO THE SMOKE ALARMS
 ARE MULTIPLE. ALL INTERCONNECTED ALARMS ARE TO BE ON
 THE SAME CIRCUIT PER MANUFACTURERS INSTRUCTIONS AND TO
 PREVENT SHORT CIRCUITS.
  
 NEW COMMENTS GENERATED BY PLAN CHANGES
  
 26} SHEET E-1.0, CIRCUIT A4, PANEL "A" SHOULD BE
 LABELED "BATH CIRCUIT".
  
 27} PANEL "B", CIRCUITS #B8,B10, AND B12 MUST BE 20 AMP
 PER 210.11(C)(1) AND 210.11(C)(3).
  
 28 } PANEL "C" CIRCUIT C8 MUST BE LABELED BATH CIRCUIT
 AND BE 20 AMPS PER 210.11(C)(3)
  
 SHEET E-2.0
  
 29} THE LOCATION OF AHU #1 VIOLATES THE CLEARANCE
 REQUIREMENTS OF 3' FOR THE PANELS. 110.26
  
 RESPOND TO ALL COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By btrobaug Date 2008-08-08 Time 07:49 Rev Time 0.00
Received By btrobaug Date 2008-08-07 Time 09:39 Sent To P
Notes
2008-08-07 12:08:08 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE
 NOTED.
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED. SEE GENERAL DESIGN CRITERIA ON SHEET A-1.1
 AND ELECTRICAL NOTES #1 AND 11 SHEET E-1.0
  
 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED
 SEPARATE.
  
 3} THE SMOKE DETECTOR CONNECTION DETAIL CONNECTS THEM
 TO A KITCHEN OR BATH LIGHT CIRCUIT, SEE NOTE #27 THIS
 SHEET (E-1.0) AND 210.12, 2005 NEC.
  
 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE
 IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE
 ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT
 CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED.
 THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS, ARTICLE 215.5 NEC 2005.
  
 5} NEW PANEL "C" IS NOT LISTED AS BEING FED IN PANEL
 "A" SCHEDULE, E-1.0.
  
 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM
 FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER
 INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE
 PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A
 REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN
 THE FUTURE.
  
 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-32/0 AND 1
 #6 CONDUCTORS FEEDING PANEL "A" AND PANEL "C" IS IN
 VIOLATION OF ANNEX "C" TABLES, 2005 NEC.
  
 8} THE 40 AMP OCP FOR THE 9500 WATT AIR HANDLERS 3 AND
 4, DOES NOT COMPLY WITH 424.3(B) (125%). 9500/240=39
 AMPS X 125%=49 AMPS.
  
 9} THERE ARE ONLY 3 A/C SYSTEMS ON THE MECHANICAL PLANS
 AND FOUR ON THE ELECTRICAL, CORRELATE SAME.ALSO SEE THE
 MECHANICAL SHEETS LIST THE HEAT AT 10K, THE ELECTRICAL
 SCHEDULES AT 9.5K. CORRELATE THESE PLANS.
  
 10} THE SUB PANEL FEED FROM PANEL "A" TO "B" LISTS
 NUMBER #8 CONDUCTORS ON A 60 AMP BREAKER IN VIOLATION
 OF 310.16. NOTE THE LOAD @ 14KW IS 59 AMPS.
  
 11} THE SMALL APPLIANCE CIRCUIT #A8 IS NOT SHOWN ON THE
 FLOOR PLAN CIRCUIT #A26 SEEMS TO BE THE ONLY SMALL
 APPLIANCE CIRCUIT SERVING THE KITCHEN, SEE 210.52(B)(1)
 FOR MINIMUM REQUIREMENTS.
  
 12} THERE IS AN EXISTING POOL ON SHEET A-2.0, THERE IS
 NO POOL EQUIPMENT LISTED IN THE PANEL SCHEDULES OR IN
 THE LOAD CALCS.
  
 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE
 SCHEDULE PER 408.4.
  
 14} CIRCUIT A4 EXTENDING OUT OF THE BATHROOM INTO THE
 CLOSET, SHEET E-2.1, IS IN VIOLATION OF 210.11(C)(3).
  
 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA
 ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD
 CALCS. 220.83(B).
  
 16} CIRCUITS B11 AND C11CARRY OVER TO INCLUDE GENERAL
 LIGHTING CIRCUITS ALONG WITH AIR HANDLERS. PLEASE
 RENUMBER CIRCUITS.408.4.
  
 17} INDICATE THE NUMBER OF CIRCUITS IN EACH OF THE
 PANELS LISTED AS PART OF THEIR RATING, 408.4 NEC,
 106.3.5.4(8) FBC.
  
 18} PANEL"B" LISTS 2 CONDUCTORS ON CIRCUITS B3, 5, 7, 9
 AND 11, PANEL "C" LISTS TWO CONDUCTORS ON CIRCUITS
 C3,5,7,9 AND 11 AND ONE BREAKER (C1) FOR A 240 CIRCUIT.
 SEE 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 B8 SHOULD BE LISTED AS BATH CIRCUIT.
  
 ALL COMMENTS RELATE TO SHEET E-2.0.
  
 19} THE RECEPTACLE AT THE SINK IN THE "DOG AREA" MUST
 BE GFI PER 210.8(A)(7).
  
 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY
 OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF
 THE GARAGE BY THE STAIR WILL MEET THE INTENT.
  
 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C
 CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL
 SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICAL
  
 ALL COMMENTS REFER TO SHEET E-2.1
  
 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 23} PER 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A
 SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE
 SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN
 ACCORDANCE WITH 210.23(A)(1) AND (A)(2).***CIRCUIT C8
 FEEDING THE BATH IN THE UNIT ABOVE THE GARAGE ALSO
 FEEDS THE SMOKE ALARMS AND A RECEPTACLE IN THE KITCHEN
 IN VIOLATION OF THIS ARTICLE.
  
 24} ALTHOUGH COMMENT #8 OF THE ZONING REVIEW DISALLOWS
 THE 240 VOLT OUTLET, THE FBCR VIEWS THIS AREA AS A
 KITCHEN BY DEFINITION IN CHAPTER #2. PER THE NEC
 ARTICLE 210.11(C)(1) TWO SMALL APPLIANCE CIRCUITS ARE
 REQUIRED. INDICATE COMPLIANCE ON THE PLAN AND IN THE
 PANEL SCHEDULE PER 408.4, AS A ZONING VARIANCE MAY BE
 ALLOWED IN THE FUTURE.
  
 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS
 REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING
 UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH
 A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE
 ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE
 CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE
 NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE
 210.12 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By kstevens Date 2009-04-16 Time 08:50 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 16:55 Sent To  
Notes
2009-04-16 08:52:00 
  
  
 PASSED/PROVISO:
 MANUF. SPECIFICATIONS REQUIRED FOR ALL GAS APPLIANCES
 AT TIME OF GAS INSPECTION. RANGE/OVEN SHALL SHOW
 LISTING/APPROVAL FOR RESIDENTIAL USE.
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-11-17 Cont ID  
Sent By kstevens Date 2008-11-17 Time 13:06 Rev Time 0.00
Received By kstevens Date 2008-11-17 Time 13:06 Sent To B1
Notes
2008-11-17 13:20:33DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A
 SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE RISER DIAGRAM APPEARS TO
 THE UNDER THE SLAB, WHICH IS NOT APPROVED PER SECTION
 404.11. ALL PIPING UNDER THE SLAB, (TO ISLAND
 APPLIANCES), SHALL BE SLEEVED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****RESPONSE NOTED, SCHEDULE 40 METALLIC PIPE INDICATED
 SHALL BE PROTECTED PER SECTIONS 404.8, 404.8.1 &
 404.8.2. PLEASE SHOW COMPLIANCE.
  
 C. OK
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEET
 SUBMITTED FOR THE TANKLESS WATER HEATERS INDICATE THE
 BTU LOAD AS 145,000 BTU'S. THIS WILL BE VERIFIED BY THE
 FIELD INSPECTOR. IF BOTH WATER HEATERS ARE 145,000
 BTU'S THEN THE PIPE SIZING MAY BE REQUIRED TO BE
 CHANGED FOR NEW LOAD. TABLE 402.4(2).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE ADDITION OF ALL CUT SECTION
 LENGTHS SUBMITTED ADDS UP TO 138 FEET. PLEASE CORRECT
 INFORMATION IN "GAS NOTES" SHT P-2.0.
  
 F. OK
 G. N/A
 H. N/A
  
 I. PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING
 REQUIREMENTS.
 (INFORMATIONAL)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By kstevens Date 2008-08-12 Time 07:25 Rev Time 0.00
Received By kstevens Date 2008-08-12 Time 07:25 Sent To B
Notes
2008-08-12 07:34:49DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A
 SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING
 REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-02-23 Cont ID  
Sent By btrobaug Date 2010-02-23 Time 08:53 Rev Time 0.00
Received By btrobaug Date 2010-02-23 Time 08:52 Sent To B
Notes
2010-02-23 08:54:49TO LUIS DESK, REVISION # 10020464./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 16:57 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 16:57 Sent To  
Notes
2009-04-06 16:57:56TO "R17"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 10:31 Sent To  
Notes
2008-11-05 10:41:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-16 Time   Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 13:38 Sent To  
Notes
2008-07-21 13:42:30TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-23 Cont ID  
Sent By rregueir Date 2009-04-23 Time 15:31 Rev Time 0.00
Received By rregueir Date 2009-04-23 Time 14:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-14 Cont ID  
Sent By tgordon Date 2008-11-14 Time 14:13 Rev Time 2.30
Received By tgordon Date 2008-11-14 Time 14:13 Sent To P
Notes
2008-11-14 14:22:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS FOR MAIN HOUSE, LINE 12C IS
 SHOWING A/C SYSTEM 4 AS 17 SEER, PLANS ARE SHOWING A/C
 SYSTEM AS 13 SEER. PLEASE CORRECT ENERGY CAL'S. PER
 2004 FBC13-103.3 AND 13-607.1.ABC.3.1.1.
  
 2) ENERGY CALCULATIONS FOR APT. ABOVE NEW GARAGE, LINE
 12A SHOW THE A/C SYSTEM AS 14 SEER, SEE ATTACHED COPY
 OF ARI CERTIFICATE SHOWS THE SYSTEM IS A 13 SEER,
 PLEASE CORRECT ENERGY CAL'S. PER 2004 FBC 13-103.3 AND
 13-607.1.ABC.3.1.1.
  
 3) ENERGY CALCULATIONS FOR THE APT. ABOVE NEW GARAGE
 NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-103.3.
  
 4) PLEASE SHOW WHICH GAS TANKLESS WATER HEATER MODEL IS
 BEING INSTALLED (INDOOR) (OUTDOOR) (DIRECT VENT). BE
 ADVISED IF NOT THE DIRECT VENT MODEL THEN COMBUSTION
 AIR WILL NEED TO BE PROVIDED FOR AND SHOWN ON
 MECHANICAL PLANS. PER 2004 FBC/R G2407 AND G2407.5.1.
  
 5) SEE PLAN M-1.0, PLEASE SIZE THE SUPPLY AIR DUCT FROM
 A.H.U. #1, R-6 INS. BOX TO THE LIVING ROOM (HOOK TO
 EXISTING TRUNK LINE). PER 2004 FBC/R M1601.1.
  
 6) SEE PLAN M-2.0 APT. ABOVE NEW GARAGE, THE 4X8 RETURN
 AIR TRANSFER GRILL TO THE BEDROOM IS UNDER SIZED. PER
 2004 FBC/R M1602.1 BALANCED RETURN AIR MAY BE ACHIEVED
 BY.
  
 (B) TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
  
 (C) HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-06 Cont ID  
Sent By tgordon Date 2008-08-06 Time 11:18 Rev Time 2.00
Received By tgordon Date 2008-08-06 Time 11:18 Sent To E
Notes
2008-08-06 11:24:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SUBMIT ENERGY CALCULATIONS AND COOLING LOAD
 CALCULATIONS FOR THE SECOND FLOOR ABOVE THE GARAGE. PER
 2004 FBC 13-101.2.5.1 RESIDENCES IN WHICH TWO BUILDINGS
 ARE PERMITTED TOGETHER THAT ARE NOT CONNECTED BY
 CONDITIONED SPACE SHALL BE CONSIDERED SEPARATE
 RESIDENCES FOR THE PURPOSES OF COMPLIANCE WITH THIS
 CODE IF THE FOLLOWING CONDITIONS APPLY:
 1. THE SECONDARY BUILDING HAS ITS OWN BATHROOM AND
 KITCHENETTE OR BAR; AND
 2. THE SECONDARY BUILDING IS HEATED AND/OR COOLED BY
 A SEPARATE HEATING AND/OR COOLING SYSTEM.
  
 2) ENERGY CALCULATIONS LINE 12 SHOWS TWO 14 SEER A/C
 SYSTEMS, AS THE SYSTEMS ARE EXISTING (USED) YOU NEED TO
 COMPLY WITH 2004 FBC 13-101.4.2.1 ASSUMPTIONS FOR
 EXISTING BUILDING EFFICIENCIES.
 THE FOLLOWING RESTRICTIONS APPLY IF THE ENTIRE BUILDING
 IS USED TO DEMONSTRATE CODE COMPLIANCE:
 4. EQUIPMENT EFFICIENCIES SHALL BE DEMONSTRATED,
 EITHER FROM MANUFACTURER?S LITERATURE OR CERTIFIED
 EQUIPMENT DIRECTORIES, OR BY THE PROCEDURE PROVIDED IN
 SECTION 407.1.ABC.3 OR SECTION 607.1.ABC.3 BASED ON
 SYSTEM CAPACITY AND TOTAL ON-SITE ENERGY INPUT.
 EQUIPMENT TO BE ADDED SHALL MEET THE APPLICABLE MINIMUM
 EQUIPMENT EFFICIENCY FROM TABLES 407.1.ABC.3.2A THROUGH
 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1
 .ABC.3.2G FOR COMMERCIAL OCCUPANCIES AND FROM TABLES
 607.1.ABC.3.2A THROUGH 607.1.ABC.3.2D AND
 608.1.ABC.3.2E THROUGH 608.1.ABC.3.2F FOR RESIDENTIAL
 OCCUPANCIES. EXISTING EQUIPMENT EFFICIENCIES NOT
 MEETING THE VALUES GIVEN IN TABLES 407.1.ABC.3.2A
 THROUGH 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1
 .ABC.3.2G FOR COMMERCIAL OCCUPANCIES SHALL UTILIZE THE
 COOLING OR HEATING SYSTEM MULTIPLIERS PROVIDED BY
 FLA/COM. EXISTING RESIDENTIAL EQUIPMENT NOT MEETING THE
 EFFICIENCIES IN TABLES 607.1.ABC.3.2A THROUGH
 607.1.ABC.3.2D AND 608.1.ABC.3.2E THROUGH
 608.1.ABC.3.2F SHALL UTILIZE THE COOLING OR HEATING
 SYSTEM MULTIPLIERS PROVIDED IN TABLES 6-16 TO 6-17 OF
 APPENDIX C TO THIS CHAPTER. RESIDENTIAL DUCTS WITH LESS
 THAN R-4.2 INSULATION SHALL USE THE MULTIPLIERS
 PROVIDED IN TABLES 6-18 TO 6-20 IN APPENDIX 13-C TO
 THIS CHAPTER.
  
 3)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C PLAN
 M-3.0 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR
 13-607.1.ABC.3.1.1.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 5) AREA CALCULATIONS ON PLAN A-2.0 FOR UNDER AIR NEW
 AND EXISTING DO NOT ADD UP, PLEASE RECHECK AND
 CORRECT.
  
 6) ARCHITECTURAL AND ELECTRICAL PLANS SHOW A NEW AIR
 HANDLER IN THE GARAGE NEXT TO THE MAIN KITCHEN AND A
 NEW CONDENSER UNIT UNDER THE STAIRS. AS THIS DOES NOT
 COINCIDE WITH THE MECHANICAL PLANS AND ENERGY
 CALCULATIONS, WHETHER NEW OR EXISTING PLEASE REMOVE,
 SEE 2004 FBC 13-607.1.ABC.1.2.
  
 7) PROVIDE FOR RETURN AIR TO BEDROOM #2 AND THE STUDY
 ON PLAN M-2.0, PER 2004 FBC/R M1602.4.
  
 8) RETURN AIR WILL NOT GET FROM THE MASTER BEDROOM TO
 THE AIR HANDLER IF THE POCKET DOOR ARE CLOSED AT THE
 MASTER BEDROOM OR THE POCKET DOORS AT THE HALL, PLEASE
 CORRECT PER 2004 FBC/R M1602.4.
  
 9) NO PLANS WERE SUBMITTED FOR THE THIRD FLOOR. PLEASE
 SUBMIT PLANS FOR THE THIRD FLOOR AS DUCTS ARE GOING TO
 IT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-16 Cont ID  
Sent By kstevens Date 2009-04-16 Time 08:47 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 16:55 Sent To  
Notes
2009-04-16 08:49:51 
  
 PASSED/PROVISO:
 REVISION REQUIRED, NEW M/B W/C NOT VENTED & SHOWER IN
 BATH #2 NOT VENTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-17 Cont ID  
Sent By kstevens Date 2008-11-17 Time 13:06 Rev Time 0.00
Received By kstevens Date 2008-11-17 Time 13:06 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 14:05 Rev Time 0.00
Received By kstevens Date 2008-08-11 Time 14:05 Sent To B1
Notes
2008-08-11 15:59:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 MECHANICAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. SHT A-2.3 SHOW COMPLIANCE WITH SECTIONS P305.9,
 PROTECTION OF COMPONETS OF PLUMBING SYSTEM, (WATER
 HEATER), AND M303.4 PROTECTION FROM DAMAGE, (WASH
 MACHINE - A/C UNIT). INDICATE METHOD FOR BOTH.
  
 2. ALL SHEETS WITH WAYNE FERRELL TITLE BLOCK. THE
 ADDRESS INDICATED ON THE TITLE BLOCK FOR THE ARCHITECT,
 (825 S.E. 8TH STREET DEERFIELD BEACH), DOES NOT REFLECT
 THE ADDRESS OF RECORD ON THE FLORIDA DBPR WEBSITE. (801
 S.E. 12TH AVE. DEERFIELD BEACH). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW. FAC 61G1-16.004(1) & FS 481.219.
  
 3. SHT P-1.0 PLUMBING NOTES #10. AIR CHAMBERS ARE NOT
 APPROVED. SECTION 604.9. PLEASE DELETE FROM REFERENCE.
  
 4. SHT P-1.0 NEW WATER HEATER DETAIL. A FULL OPEN VALVE
 IS REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER.
 SECTION 606.1(7). PLEASE INDICATE IN DETAIL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2009-05-01 Cont ID  
Sent By jroach Date 2009-05-01 Time 10:49 Rev Time 0.00
Received By jroach Date 2009-05-01 Time 10:49 Sent To  
Notes
2009-05-01 10:50:31ZONING PLAN REVIEW
  
 PERMIT NO.: 08070580
 ADDRESS: 203 ALPINE ROAD
 CONTRACTOR/CONTACT: TED BERGHAUS
 TELEPHONE NO.: 718.3997
 SCOPE OF REVIEW: SINGLE FAMILY RESIDENCE
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 PRIOR TO FINAL INSPECTION, A LANDSCAPE PLAN WILL NEED
 TO BE SUBMITTED AS PART OF THE PERMIT APPLICATION,
 INDICATING THAT THE PROPERTY IS IN COMPLIANCE WITH
 ARTICLE XIV OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS. THE PROPERTY IS REQUIRED TO BE IN
 COMPLIANCE WITH THESE PROVISIONS AS THE VALUE OF THE
 IMPROVEMENTS EXCEEDS 50% OF THE VALUE OF THE STRUCTURE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 PHONE: (561) 822-1435
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-04-27 Cont ID  
Sent By jroach Date 2009-04-27 Time 09:59 Rev Time 0.00
Received By jroach Date 2009-04-27 Time 09:59 Sent To  
Notes
2009-04-27 10:13:55ZONING PLAN REVIEW
  
 PERMIT NO.: 08070580
 ADDRESS: 203 ALPINE ROAD
 CONTRACTOR/CONTACT: TED BERGHAUS
 TELEPHONE NO.: 718.3997
 SCOPE OF REVIEW: SINGLE FAMILY RESIDENCE
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED
 FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY
 FENCING. THIS FORM MAY BE OBTAINED IN CONSTRUCTION
 SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S
 PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO
 BE REVIEWED AND APPROVED. ONCE APPROVED BY PUBLIC
 UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING
 PERMIT APPLICATION. (REPEAT COMMENT)
  
 IMPORTANT: PRIOR TO FINAL INSPECTION, A LANDSCAPE PLAN
 WILL NEED TO BE SUBMITTED AS PART OF THE PERMIT
 APPLICATION, INDICATING THAT THE PROPERTY IS IN
 COMPLIANCE WITH ARTICLE XIV OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS. THE PROPERTY IS REQUIRED
 TO BE IN COMPLIANCE WITH THESE PROVISIONS AS THE VALUE
 OF THE IMPROVEMENTS EXCEEDS 50% OF THE VALUE OF THE
 STRUCTURE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 PHONE: (561) 822-1435
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By jroach Date 2008-11-06 Time 19:34 Rev Time 0.00
Received By jroach Date 2008-11-06 Time 19:34 Sent To  
Notes
2008-11-06 19:42:35***FAILED***
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO THE
 ISSUANCE OF A PERMIT. UPON RESUBMITTAL, A WRITTEN
 RESPONSE SHALL BE PROVIDED FOR EACH COMMENT, INDICATING
 HOW IT HAS BEEN ADDRESSED.
  
 1) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL
 BE SUBMITTED WITH THE PERMIT PACKAGE. (REPEAT COMMENT)
  
 2) ALTHOUGH THE NOTE WAS CORRECTED ON SHEET A-3.0B
 REGARDING THE HEIGHT OF THE PRIVACY WALL, THE WALL THAT
 IS DRAWN IN THE ELEVATION CONTINUES TO BE SIX (6) FEET
 IN HEIGHT. THE MAXIMUM HEIGHT ALLOWED BY ZBA CASE NO.
 3222 WAS FIVE (5) FEET. PLEASE ENSURE THAT ALL NOTES,
 PLANS, AND DETAILS CORRESPOND AND ADJUST THE HEIGHT OF
 THE WALL TO SHOW A MAXIMUM OF FIVE (5) FEET.
  
 3) IN REGARD TO DETAIL #4 ON SHEET A-2.0, WHICH WAS
 ADDED REFERENCING THE SECTION OF THE PRIVACY WALL,
 PLEASE PROVIDE DIMENSIONS THAT CORRESPOND WITH THE SITE
 PLAN, ELEVATIONS, ETC. BE SURE THE WALL DOES NOT EXCEED
 FIVE (5) FEET ON THE EXTERIOR FACE AND FOUR (4) FEET ON
 THE INTERIOR FACE.
  
 4 AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED
 FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY
 FENCING. THIS FORM MAY BE OBTAINED IN CONSTRUCTION
 SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S
 PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO
 BE REVIEWED AND APPROVED. ONCE APPROVED BY PUBLIC
 UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING
 PERMIT APPLICATION. (REPEAT COMMENT)
  
 5) REGARDING THE LIVING AREA ABOVE THE GARAGE...THE
 REFRIGERATOR SHALL ONLY BE AN UNDERCOUNTER
 REFRIGERATOR; AND JUST AS AN FYI, NO RENTAL LICENSE
 WILL BE ISSUED FOR THIS AS A SEPARATE DWELLING UNIT IS
 NOT PERMITTED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By jroach Date 2008-08-05 Time 09:55 Rev Time 0.00
Received By jroach Date 2008-08-05 Time 09:55 Sent To  
Notes
2008-08-05 11:21:52***FAILED***
  
 THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO THE
 ISSUANCE OF A PERMIT.UPON RESUBMITTAL, A WRITTEN
 RESPONSE SHALL BE PROVIDED FOR EACH COMMENT, INDICATING
 HOW IT HAS BEEN ADDRESSED.
  
 1) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL
 BE SUBMITTED WITH THE PERMIT PACKAGE.
  
 2) THE VISIBILITY TRIANGLE SHALL BE SHOWN AND
 DIMENSIONED ON THE SITE PLAN.(SECTION 94-305(E) AND
 FIGURE X-1)
  
 3) BUILDING HEIGHT SHALL BE MEASURED FROM GRADE.
 PLEASE ADJUST THE DIMENSIONS ON THE ELEVATIONS
 ACCORDINGLY.ADDITIONALLY, ENSURE THAT DIMENSIONS ARE
 PROVIDED TO THE MEAN POINT ON ALL PITCHED ROOFS AND TO
 THE ROOF DECK ON ALL FLAT ROOFS. (SECTION 94-611)
  
 4) ON SHEET A-3.0B, THE NOTE REGARDING THE PRIVACY WALL
 INDICATES 4 FEET WITH AN ADDITIONAL 2 FEET OF CONCRETE
 BLOCK (OVERALL HEIGHT OF 6 FEET).THE NOTE ON THE SITE
 PLAN INDICATES THAT THE WALL IS TO BE APPROXIMATELY 5
 FEET (ALLOWING FOR 4 FEET WHEN MEASURED ON THE INTERIOR
 FACE OF THE WALL).THE VARIANCE ISSUED BY ZBA CASE NO.
 3222 PROVIDED FOR THE 5 FEET, NOT THE 6 FEET SHOWN ON
 THE ELEVATIONS.(SEE FINAL ORDER FOR ZBA CASE NO.
 3222)
  
 5) SHEET A-2.3 INDICATES A NEW FENCE NEXT TO THE
 GARAGE.THIS IS NOT SHOWN ON THE SITE PLAN.PLEASE
 ENSURE THAT ALL PLANS ARE CONSISTENT AND REFLECT THE
 SAME SCOPE OF WORK.
  
 6) SHEET A-2.0 REFERENCES A SECTION OF THE PRIVACY
 WALL, INDICATING THAT IT IS DETAIL #4 ON SHEET
 S-1.5....NO DETAIL OF THE PRIVACY WALL EXISTS ON THIS
 SHEET.PLEASE PROVIDE A CROSS SECTION AND DETAIL OF
 THE PRIVACY WALL, WITH DIMENSIONS, AND NOTE IT
 CORRECTLY ON THE SITE PLAN.
  
 7) AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED
 FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY
 FENCING.THIS FORM MAY BE OBTAINED IN CONSTRUCTION
 SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S
 PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO
 BE REVIEWED AND APPROVED.ONCE APPROVED BY PUBLIC
 UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING
 PERMIT APPLICATION.
  
 8) SHEET E-2.1 SHOWS THE INSTALLATION OF A 220V OUTLET
 IN THE LIVING AREA ABOVE THE GARAGE.NO 220V OUTLETS
 SHALL BE PERMITTED.THE PROPERTY IS LOCATED IN AN SF7
 ZONING DISTRICT, WHICH DOES NOT ALLOW FOR THE
 CONSTRUCTION OF ACCESSORY DWELLING UNITS.THE SPACE
 ABOVE THE GARAGE CANNOT BE CONSTRUCTED SO AS TO CREATE
 A DWELLING UNIT, AS DEFINED IN SECTION 94-611 OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
 PLEASE REFER TO SUCH DEFINITION AND AMEND THE PLANS
 ACCORDINGLY.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.