Plan Review Details - Permit 08070580
| Plan Review Stops For Permit 08070580 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-06-01 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-06-01 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-11-18 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-11-18 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2008-11-18 13:06:33 | BUILDING REVIEW COMMENTS | | | | | | | | | | | | #3 FROM PREVIOUS REVIEW. SURVEYS HAVE NOT BEEN | | | PROVIDED. | | | | | | #5 FROM PREVIOUS REVIEW. ENERGY CALC'S ARE NOT SIGNED | | | AND DATED BY OWNER/AGENT. | | | | | | #6 FROM PREVIOUS REVIEW. COUNTY IMPACT FEES ARE STILL | | | DUE. | | | | | | #7 FROM PREVIOUS REVIEW. VERIFY EMERGENCY EGRESS | | | COMPLIANCE FOR BEDROOM OVER GARAGE. | | | | | | #8 FROM PREVIOUS REVIEW. THE TYPE OF CONSTRUCTION IS | | | INCORRECT, TYPE VI UNPROTECTED IS NOT RECOGNIZED WITHIN | | | THE 2004 FBC. | | | | | | #15 FROM PREVIOUS REVIEW. THE REQUIREMENT FOR HANDRAILS | | | AND GUARDS HAS NOT BEEN PROVIDED. | | | | | | #17 FROM PREVIOUS REVIEW. PROVIDE APPROVED SHOP | | | DRAWINGS FOR THE HOLLOW CORE PANELS AND THE | | | MANUFACTURED STAIRS. | | | | | | #18 FROM PREVIOUS REVIEW. PROVIDE GARAGE DOOR REPORT. | | | | | | #20 FROM PREVIOUS REVIEW. FRENCH DOOR SUBMITTAL IS | | | STILL INCOMPLETE. PROVIDE FULL PAGE ENGINEERING. | | | | | | #24 FROM PREVIOUS REVIEW. DEMONSTRATE THE 6" HOLE | | | PROVIDED MEETS THE REQUIREMENTS OF R806.1 AND R806.2. | | | | | | #25 FROM PREVIOUS REVIEW. ATTIC ACCESS IS ALSO REQUIRED | | | OVER GARAGE BEDROOM. | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-16 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-08-16 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-08-16 |
Time |
06:35 |
Sent To |
PC |
|
| Notes |
| 2008-08-16 08:53:29 | DENIED | | | | | | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | | | | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES | | | | | | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 160.78 FOR | | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW | | | | | | | | | 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE | | | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR | | | SETBACKS | | | | | | 4)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN | | | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. | | | | | | 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER | | | AND OWNER/AGENT PRIOR TO SUBMITTAL. PLEASE NOTE THAT | | | THE OWNER AGENT SECTION WAS NOT SIGNED AND SEVERAL | | | CORRECTION ARE REQUIRED TO COMPLY WITH DRAWINGS SUCH AS | | | FRAMED SECOND STORY WALLS, NO INSULATION SHOWN ON | | | RAISED FLOOR BELOW BALCONY IN MASTER BEDROOM OR | | | INSULATION VALUE FOR VAULTED CEILINGS (NOT UNDER | | | ATTIC) | | | | | | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. | | | | | | 7)VERIFY THAT BEDROOM WINDOW IN GUEST ROOM ABOVE | | | GARAGE MEET EMERGENCY EGRESS PER R310 FBC: MIN. NET | | | CLEAR OPENING OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET | | | CLEAR OPENING ALL OTHER FLOORS OF 5.7 SQ.FT. IN BOTH | | | CASES THE MIN.NET CLEAR HEIGHT SHALL BE 24" AND THE NET | | | CLEAR WIDTH SHALL BE 20" | | | | | | 8)VERIFY THE DESIGN CRITERIA THAT WILL BE USED, | | | ENGINEERING CALC SHEETS PROVIDED DIFFER FROM THOSE ON | | | THE DRAWINGS A-1.1 AND S-1.1 AND S-1.2 FOR WIND SPEED, | | | SOIL BEARING CAPACITY , ROOF/TRUSS LOADS ETC. ONCE THE | | | DESIGN CRITERIA IS SET BE SURE THAT THE DOOR AND WINDOW | | | PRESSURES ARE AS REQUIRED. | | | | | | 9)TIE BEAM #3 ON S-1.1 IS NOT SHOWN IN THE BEAM | | | SCHEDULE | | | | | | 10)PLEASE VERIFY HANGER USED FOR 3 PLY GIRDER TRUSS | | | AT GARAGE FLOOR FRAMING, SECTION B ON S-1.7 SHOWS A | | | SINGLE WIDE HANGER THD28 | | | | | | 11)CONFIRM LOCATION OF GIRDER TRUSS IN GARAGEWITH | | | LAYOUT OF STAIRS TO SECOND FLOOR, SHOW OPENING LAYOUT | | | | | | 12)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT | | | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR | | | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD | | | | | | 13)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF | | | FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES. | | | 12" BELOW UNDISTURBED SOIL, SHEETS S-1.7 AND S-1.8 SHOW | | | 8" | | | | | | 14)PROVIDE BEARING/ATTACHMENT DETAIL FOR HOLLOW CORE | | | PANELS AT BALCONYAND EXISTING GARAGE WALLAND AT | | | FIREPLACE, SEE S-1.1 | | | | | | 15)HANDRAILS AND GUARDS TO SHOW THAT ATTACHMENT WILL | | | MEET THE REQUIREMENTS OF 1607.7.1.1 FBC FOR | | | CONCENTRATED LOADS ANDFURTHER REQUIREMENTS IN | | | SECTIONS R311 & 312 FBC RES. | | | | | | 16)PROVIDE ELEVATIONS FOR NEW GARAGE FLOOR/BEAMS | | | | | | 17) PROVIDE REVIEWED AND APPROVED SHOP DRAWINGS FOR | | | HOLLOW CORE PANELS AND MANUFACTURED STAIRS | | | | | | 18)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. NO | | | PRODUCT APPROVAL WAS SUBMITTED FOR THE GARAGE DOOR | | | | | | 19)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | | | | 20)THE PRODUCT APPROVAL NOA FOR THE FRENCH DOORS IS | | | INCOMPLETE, PLEASE SEE THAT THE INFORMATION AT THE TOPS | | | OF THE DRAWINGS HAS BEEN CUT OFF, THIS INFORMATION IS | | | REQUIRED FOR ATTACHMENT INSPECTION. | | | | | | 21)PER LEVEL 3 ALTERATION IN EXISTING BUILDING CODE | | | ACCESSIBILITY REQUIREMENTS SHALL MEET CHAPTER 11 FBC | | | FOR RESIDENTIAL CONSTRUCTION PROVIDE AT MINIMUM 1 | | | ACCESSIBLE BATHROOM PER R322.1.1 FBC 29" CLEAR WITH | | | DOOR OPEN 90 DEGREES | | | | | | 22)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER | | | R313.1.1 FBC RES. | | | | | | 23)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER | | | R803.2.3.1 FBC RES. FASTENERS TO BE 4" O/CIN ZONE 3 | | | FOR WIND DESIGN SPEEDS OVER 130 MPH | | | | | | 24)PROVIDE VENTILATION REQUIREMENTS ON DRAWINGS PER | | | R806.1 AND R806.2 FBC RES. | | | | | | 25)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS | | | REQUIRED PER R807.1 FBC RES. | | | | | | 26)SUBMIT A COPY OF THE RECORDED NOTICE OF | | | COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT | | | | | | 27)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS | | | WITH REVISIONS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY | | | FOR REFERENCE. | | | | | | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006&2007 | | | AMENDMENTS | | | FBC* = WEST PALM BEACH ADMINISTRATIVE | | | AMENDMENTS TO FBC | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | FBC RES. = FLORIDA BUILDING CODE | | | RESIDENTIAL 2004 W/2006&2007 AMENDMENTS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-15 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-15 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-11-13 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-11-13 |
Time |
07:55 |
Sent To |
M |
|
| Notes |
| 2008-11-13 11:11:55 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE | | | NOTED. | | | | | | THESE ARE COMMENTS FROM THE PREVIOUS REVIEW THAT WERE | | | NOT CORRECTLY RESPONDED TO.***INDICATES FURTHER | | | EXPLANATION OF PREVIOUS COMMENT | | | | | | 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED | | | SEPARATE***.THE GENERATOR IS STILL SHOWN ON THE RISER | | | DIAGRAM AND ON THE MECHANICAL SHEETS. REMOVE FROM | | | PLANS, DESIGNATE AS FUTURE OR PROVIDE ALL DOCUMENTATION | | | AND PLANS FOR A RESIDENTIAL GENERATOR PERMIT IF IT IS | | | TO BE PART OF THIS PERMIT. | | | | | | 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE | | | IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE | | | ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT | | | CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED. | | | THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED | | | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS | | | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND | | | FACTORS, ARTICLE 215.5 NEC 2005*** THE CALCULATION | | | GIVEN IS INCORRECT PER 220.83. THE AMPERAGE WOULD BE | | | 212 AMPS AFTER DEMANDS. THE EXISTING SERVICE IS 200 | | | AMPS.. | | | | | | 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM | | | FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER | | | INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE | | | PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A | | | REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN | | | THE FUTURE***THE PANEL SCHEDULE LISTS THE FEEDER FOR | | | PANEL "B" AS 40 AMP (NOT LARGE ENOUGH FOR THE | | | CALCULATED LOAD FOR THAT PANEL), AND 60 AMPS FOR PANEL | | | "C". CORRELATE THE RISER INFORMATIONN WITH THE PANEL | | | INFORMATIO.. | | | | | | 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-2/0 AND 1 | | | #6 CONDUCTORS FEEDING PANEL "A" , "B" AND PANEL "C" IS | | | IN VIOLATION OF ANNEX "C" TABLES, 2005 NEC***.THIS | | | ISSUE STILL REMAINS ON THE PLAN, NO CHANGE. | | | | | | 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE | | | SCHEDULE PER 408.4*** NOW LABELED CORRECTLY BU ON A 15 | | | AMP CIRCUIT IN VIOLATION OF.210.11(C)(3)--20 AMP | | | CIRCUIT. | | | | | | 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA | | | ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD | | | CALCS. 220.83(B).*** NO CHANGE , STILL NOT LISTED IN | | | THE SCHEDULES. | | | | | | ALL COMMENTS RELATE TO SHEET E-2.0. | | | | | | 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY | | | OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF | | | THE GARAGE BY THE STAIR WILL MEET THE INTENT***WAS NOT | | | ADDED, STILL IN VIOLATION.. | | | | | | 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C | | | CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE | | | REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL | | | SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICALLY*** NO | | | NOTE ADDED, NO DISCONNECTS LOCATED ON THE PLAN. | | | | | | ALL COMMENTS REFER TO SHEET E-2.1 | | | | | | 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE | | | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, | | | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE | | | LOCATIONS OF THE SOUNDING DEVICES*** NOT ADDRESSED.. | | | | | | | | | 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS | | | REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING | | | UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH | | | A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE | | | ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE | | | CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE | | | NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE | | | 210.12 NEC.***THE CIRCUITS ASSIGN TO THE SMOKE ALARMS | | | ARE MULTIPLE. ALL INTERCONNECTED ALARMS ARE TO BE ON | | | THE SAME CIRCUIT PER MANUFACTURERS INSTRUCTIONS AND TO | | | PREVENT SHORT CIRCUITS. | | | | | | NEW COMMENTS GENERATED BY PLAN CHANGES | | | | | | 26} SHEET E-1.0, CIRCUIT A4, PANEL "A" SHOULD BE | | | LABELED "BATH CIRCUIT". | | | | | | 27} PANEL "B", CIRCUITS #B8,B10, AND B12 MUST BE 20 AMP | | | PER 210.11(C)(1) AND 210.11(C)(3). | | | | | | 28 } PANEL "C" CIRCUIT C8 MUST BE LABELED BATH CIRCUIT | | | AND BE 20 AMPS PER 210.11(C)(3) | | | | | | SHEET E-2.0 | | | | | | 29} THE LOCATION OF AHU #1 VIOLATES THE CLEARANCE | | | REQUIREMENTS OF 3' FOR THE PANELS. 110.26 | | | | | | RESPOND TO ALL COMMENTS IN WRITING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-08 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-07 |
Time |
09:39 |
Sent To |
P |
|
| Notes |
| 2008-08-07 12:08:08 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ALL COMMENTS RELATE TO SHEET E-1.0, UNLESS OTHERWISE | | | NOTED. | | | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. SEE GENERAL DESIGN CRITERIA ON SHEET A-1.1 | | | AND ELECTRICAL NOTES #1 AND 11 SHEET E-1.0 | | | | | | 2} THE GENERATOR SHOWN ON SHEET E-1.0 MUST BE PERMITTED | | | SEPARATE. | | | | | | 3} THE SMOKE DETECTOR CONNECTION DETAIL CONNECTS THEM | | | TO A KITCHEN OR BATH LIGHT CIRCUIT, SEE NOTE #27 THIS | | | SHEET (E-1.0) AND 210.12, 2005 NEC. | | | | | | 4} PROVIDE LOAD CALCULATIONS PER 220.83(B) TO DETERMINE | | | IF THE EXISTING SERVICE HAS SUFFICIENT CAPACITY FOR THE | | | ADDED LOADS. THE "DEMAND CALCULATION" (E-1.0) IS NOT | | | CORRECT AS H.V.A.C UNITS #3 AND 4 HAVE BEEN OMITTED. | | | THE CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED | | | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS | | | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND | | | FACTORS, ARTICLE 215.5 NEC 2005. | | | | | | 5} NEW PANEL "C" IS NOT LISTED AS BEING FED IN PANEL | | | "A" SCHEDULE, E-1.0. | | | | | | 6} VERIFY THE 2/0 FEEDERS SHOWN ON THE RISER DIAGRAM | | | FEEDING A 50 AMP PANEL (C) IS WHAT THE DESIGNER | | | INTENDED. ALTHOUGH NOT A VIOLATION, IF PART OF THE | | | PERMITTED SET OF PLANS THEY MUST BE INSTALLED, OR A | | | REVISION WILL BE MUST BE SUBMITTED TO MAKE A CHANGE IN | | | THE FUTURE. | | | | | | 7} THE 1" CONDUIT (SHEET E-1.0 RISER) WITH 3-32/0 AND 1 | | | #6 CONDUCTORS FEEDING PANEL "A" AND PANEL "C" IS IN | | | VIOLATION OF ANNEX "C" TABLES, 2005 NEC. | | | | | | 8} THE 40 AMP OCP FOR THE 9500 WATT AIR HANDLERS 3 AND | | | 4, DOES NOT COMPLY WITH 424.3(B) (125%). 9500/240=39 | | | AMPS X 125%=49 AMPS. | | | | | | 9} THERE ARE ONLY 3 A/C SYSTEMS ON THE MECHANICAL PLANS | | | AND FOUR ON THE ELECTRICAL, CORRELATE SAME.ALSO SEE THE | | | MECHANICAL SHEETS LIST THE HEAT AT 10K, THE ELECTRICAL | | | SCHEDULES AT 9.5K. CORRELATE THESE PLANS. | | | | | | 10} THE SUB PANEL FEED FROM PANEL "A" TO "B" LISTS | | | NUMBER #8 CONDUCTORS ON A 60 AMP BREAKER IN VIOLATION | | | OF 310.16. NOTE THE LOAD @ 14KW IS 59 AMPS. | | | | | | 11} THE SMALL APPLIANCE CIRCUIT #A8 IS NOT SHOWN ON THE | | | FLOOR PLAN CIRCUIT #A26 SEEMS TO BE THE ONLY SMALL | | | APPLIANCE CIRCUIT SERVING THE KITCHEN, SEE 210.52(B)(1) | | | FOR MINIMUM REQUIREMENTS. | | | | | | 12} THERE IS AN EXISTING POOL ON SHEET A-2.0, THERE IS | | | NO POOL EQUIPMENT LISTED IN THE PANEL SCHEDULES OR IN | | | THE LOAD CALCS. | | | | | | 13} CIRCUIT B8 SHOULD BE LABELED BATH CIRCUIT IN THE | | | SCHEDULE PER 408.4. | | | | | | 14} CIRCUIT A4 EXTENDING OUT OF THE BATHROOM INTO THE | | | CLOSET, SHEET E-2.1, IS IN VIOLATION OF 210.11(C)(3). | | | | | | 15} THE FREEZER, MICROWAVES (TWO EACH) ICEMAKER AND SPA | | | ARE NOT LISTED IN THE PANEL SCHEDULE OR IN THE LOAD | | | CALCS. 220.83(B). | | | | | | 16} CIRCUITS B11 AND C11CARRY OVER TO INCLUDE GENERAL | | | LIGHTING CIRCUITS ALONG WITH AIR HANDLERS. PLEASE | | | RENUMBER CIRCUITS.408.4. | | | | | | 17} INDICATE THE NUMBER OF CIRCUITS IN EACH OF THE | | | PANELS LISTED AS PART OF THEIR RATING, 408.4 NEC, | | | 106.3.5.4(8) FBC. | | | | | | 18} PANEL"B" LISTS 2 CONDUCTORS ON CIRCUITS B3, 5, 7, 9 | | | AND 11, PANEL "C" LISTS TWO CONDUCTORS ON CIRCUITS | | | C3,5,7,9 AND 11 AND ONE BREAKER (C1) FOR A 240 CIRCUIT. | | | SEE 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. | | | B8 SHOULD BE LISTED AS BATH CIRCUIT. | | | | | | ALL COMMENTS RELATE TO SHEET E-2.0. | | | | | | 19} THE RECEPTACLE AT THE SINK IN THE "DOG AREA" MUST | | | BE GFI PER 210.8(A)(7). | | | | | | 20} A SMOKE ALARM IS REQUIRED ON EACH ADDITIONAL STORY | | | OF THE DWELLING, PER 313.1(A) FBCR. THE FIRST FLOOR OF | | | THE GARAGE BY THE STAIR WILL MEET THE INTENT. | | | | | | 21} THE LOCATION OF THE DISCONNECTS FOR THE A/C | | | CONDENSERS DO NOT COMPLY WITH 110.26 CLEARANCE | | | REQUIREMENTS. A NOTE TO COMPLY WITH THAT ARTICLE WILL | | | SUFFICE AS THE LOCATION SHOWN IS DIAGRAMMATICAL | | | | | | ALL COMMENTS REFER TO SHEET E-2.1 | | | | | | 22} THE SMOKE DEVICES ARE LABELED "DETECTORS", SEE THE | | | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, | | | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE | | | LOCATIONS OF THE SOUNDING DEVICES. | | | | | | 23} PER 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN | | | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY | | | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE | | | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM | | | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER | | | OUTLETS. | | | EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A | | | SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE | | | SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN | | | ACCORDANCE WITH 210.23(A)(1) AND (A)(2).***CIRCUIT C8 | | | FEEDING THE BATH IN THE UNIT ABOVE THE GARAGE ALSO | | | FEEDS THE SMOKE ALARMS AND A RECEPTACLE IN THE KITCHEN | | | IN VIOLATION OF THIS ARTICLE. | | | | | | 24} ALTHOUGH COMMENT #8 OF THE ZONING REVIEW DISALLOWS | | | THE 240 VOLT OUTLET, THE FBCR VIEWS THIS AREA AS A | | | KITCHEN BY DEFINITION IN CHAPTER #2. PER THE NEC | | | ARTICLE 210.11(C)(1) TWO SMALL APPLIANCE CIRCUITS ARE | | | REQUIRED. INDICATE COMPLIANCE ON THE PLAN AND IN THE | | | PANEL SCHEDULE PER 408.4, AS A ZONING VARIANCE MAY BE | | | ALLOWED IN THE FUTURE. | | | | | | 25} PER 313.1 FBCR "WHEN MORE THAN ONE SMOKE ALARM IS | | | REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING | | | UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH | | | A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE | | | ALL OF THE ALARMS IN THE INDIVIDUAL UNIT." INDICATE THE | | | CIRCUIT NUMBER AT ALL SMOKE DEVICES TO HELP ELIMINATE | | | NO CONFUSION IN THE FIELD AT INSTALLATION. ALSO SEE | | | 210.12 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-16 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-15 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2009-04-16 08:52:00 | | | | | | | | | | PASSED/PROVISO: | | | MANUF. SPECIFICATIONS REQUIRED FOR ALL GAS APPLIANCES | | | AT TIME OF GAS INSPECTION. RANGE/OVEN SHALL SHOW | | | LISTING/APPROVAL FOR RESIDENTIAL USE. | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-17 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-17 |
Time |
13:06 |
Sent To |
B1 |
|
| Notes |
| 2008-11-17 13:20:33 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE | | | FOLLOWING INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. THE RISER DIAGRAM APPEARS TO | | | THE UNDER THE SLAB, WHICH IS NOT APPROVED PER SECTION | | | 404.11. ALL PIPING UNDER THE SLAB, (TO ISLAND | | | APPLIANCES), SHALL BE SLEEVED. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****RESPONSE NOTED, SCHEDULE 40 METALLIC PIPE INDICATED | | | SHALL BE PROTECTED PER SECTIONS 404.8, 404.8.1 & | | | 404.8.2. PLEASE SHOW COMPLIANCE. | | | | | | C. OK | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEET | | | SUBMITTED FOR THE TANKLESS WATER HEATERS INDICATE THE | | | BTU LOAD AS 145,000 BTU'S. THIS WILL BE VERIFIED BY THE | | | FIELD INSPECTOR. IF BOTH WATER HEATERS ARE 145,000 | | | BTU'S THEN THE PIPE SIZING MAY BE REQUIRED TO BE | | | CHANGED FOR NEW LOAD. TABLE 402.4(2). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, BUT THE ADDITION OF ALL CUT SECTION | | | LENGTHS SUBMITTED ADDS UP TO 138 FEET. PLEASE CORRECT | | | INFORMATION IN "GAS NOTES" SHT P-2.0. | | | | | | F. OK | | | G. N/A | | | H. N/A | | | | | | I. PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING | | | REQUIREMENTS. | | | (INFORMATIONAL) | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-12 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-12 |
Time |
07:25 |
Sent To |
B |
|
| Notes |
| 2008-08-12 07:34:49 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT A-2.3 INDICATES A GAS COOKTOP/DOUBLE OVEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE | | | FOLLOWING INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | G. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | H. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | I. PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING AS WELL AS MEETS THE LISTING | | | REQUIREMENTS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2010-02-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-02-23 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-02-23 |
Time |
08:52 |
Sent To |
B |
|
| Notes |
| 2010-02-23 08:54:49 | TO LUIS DESK, REVISION # 10020464./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-06 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-06 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2009-04-06 16:57:56 | TO "R17" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-05 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-05 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2008-11-05 10:41:07 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-08-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-21 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2008-07-21 13:42:30 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-04-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-23 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-23 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-11-14 |
Time |
14:13 |
Rev Time |
2.30 |
| Received By |
tgordon |
Date |
2008-11-14 |
Time |
14:13 |
Sent To |
P |
|
| Notes |
| 2008-11-14 14:22:45 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) ENERGY CALCULATIONS FOR MAIN HOUSE, LINE 12C IS | | | SHOWING A/C SYSTEM 4 AS 17 SEER, PLANS ARE SHOWING A/C | | | SYSTEM AS 13 SEER. PLEASE CORRECT ENERGY CAL'S. PER | | | 2004 FBC13-103.3 AND 13-607.1.ABC.3.1.1. | | | | | | 2) ENERGY CALCULATIONS FOR APT. ABOVE NEW GARAGE, LINE | | | 12A SHOW THE A/C SYSTEM AS 14 SEER, SEE ATTACHED COPY | | | OF ARI CERTIFICATE SHOWS THE SYSTEM IS A 13 SEER, | | | PLEASE CORRECT ENERGY CAL'S. PER 2004 FBC 13-103.3 AND | | | 13-607.1.ABC.3.1.1. | | | | | | 3) ENERGY CALCULATIONS FOR THE APT. ABOVE NEW GARAGE | | | NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-103.3. | | | | | | 4) PLEASE SHOW WHICH GAS TANKLESS WATER HEATER MODEL IS | | | BEING INSTALLED (INDOOR) (OUTDOOR) (DIRECT VENT). BE | | | ADVISED IF NOT THE DIRECT VENT MODEL THEN COMBUSTION | | | AIR WILL NEED TO BE PROVIDED FOR AND SHOWN ON | | | MECHANICAL PLANS. PER 2004 FBC/R G2407 AND G2407.5.1. | | | | | | 5) SEE PLAN M-1.0, PLEASE SIZE THE SUPPLY AIR DUCT FROM | | | A.H.U. #1, R-6 INS. BOX TO THE LIVING ROOM (HOOK TO | | | EXISTING TRUNK LINE). PER 2004 FBC/R M1601.1. | | | | | | 6) SEE PLAN M-2.0 APT. ABOVE NEW GARAGE, THE 4X8 RETURN | | | AIR TRANSFER GRILL TO THE BEDROOM IS UNDER SIZED. PER | | | 2004 FBC/R M1602.1 BALANCED RETURN AIR MAY BE ACHIEVED | | | BY. | | | | | | (B) TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE | | | PROPER RETURN AIR BALANCE | | | | | | (C) HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-06 |
Time |
11:18 |
Rev Time |
2.00 |
| Received By |
tgordon |
Date |
2008-08-06 |
Time |
11:18 |
Sent To |
E |
|
| Notes |
| 2008-08-06 11:24:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) NEED TO SUBMIT ENERGY CALCULATIONS AND COOLING LOAD | | | CALCULATIONS FOR THE SECOND FLOOR ABOVE THE GARAGE. PER | | | 2004 FBC 13-101.2.5.1 RESIDENCES IN WHICH TWO BUILDINGS | | | ARE PERMITTED TOGETHER THAT ARE NOT CONNECTED BY | | | CONDITIONED SPACE SHALL BE CONSIDERED SEPARATE | | | RESIDENCES FOR THE PURPOSES OF COMPLIANCE WITH THIS | | | CODE IF THE FOLLOWING CONDITIONS APPLY: | | | 1. THE SECONDARY BUILDING HAS ITS OWN BATHROOM AND | | | KITCHENETTE OR BAR; AND | | | 2. THE SECONDARY BUILDING IS HEATED AND/OR COOLED BY | | | A SEPARATE HEATING AND/OR COOLING SYSTEM. | | | | | | 2) ENERGY CALCULATIONS LINE 12 SHOWS TWO 14 SEER A/C | | | SYSTEMS, AS THE SYSTEMS ARE EXISTING (USED) YOU NEED TO | | | COMPLY WITH 2004 FBC 13-101.4.2.1 ASSUMPTIONS FOR | | | EXISTING BUILDING EFFICIENCIES. | | | THE FOLLOWING RESTRICTIONS APPLY IF THE ENTIRE BUILDING | | | IS USED TO DEMONSTRATE CODE COMPLIANCE: | | | 4. EQUIPMENT EFFICIENCIES SHALL BE DEMONSTRATED, | | | EITHER FROM MANUFACTURER?S LITERATURE OR CERTIFIED | | | EQUIPMENT DIRECTORIES, OR BY THE PROCEDURE PROVIDED IN | | | SECTION 407.1.ABC.3 OR SECTION 607.1.ABC.3 BASED ON | | | SYSTEM CAPACITY AND TOTAL ON-SITE ENERGY INPUT. | | | EQUIPMENT TO BE ADDED SHALL MEET THE APPLICABLE MINIMUM | | | EQUIPMENT EFFICIENCY FROM TABLES 407.1.ABC.3.2A THROUGH | | | 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1 | | | .ABC.3.2G FOR COMMERCIAL OCCUPANCIES AND FROM TABLES | | | 607.1.ABC.3.2A THROUGH 607.1.ABC.3.2D AND | | | 608.1.ABC.3.2E THROUGH 608.1.ABC.3.2F FOR RESIDENTIAL | | | OCCUPANCIES. EXISTING EQUIPMENT EFFICIENCIES NOT | | | MEETING THE VALUES GIVEN IN TABLES 407.1.ABC.3.2A | | | THROUGH 407.1.ABC.3.2D AND 408.1.ABC.3.2E THROUGH 408.1 | | | .ABC.3.2G FOR COMMERCIAL OCCUPANCIES SHALL UTILIZE THE | | | COOLING OR HEATING SYSTEM MULTIPLIERS PROVIDED BY | | | FLA/COM. EXISTING RESIDENTIAL EQUIPMENT NOT MEETING THE | | | EFFICIENCIES IN TABLES 607.1.ABC.3.2A THROUGH | | | 607.1.ABC.3.2D AND 608.1.ABC.3.2E THROUGH | | | 608.1.ABC.3.2F SHALL UTILIZE THE COOLING OR HEATING | | | SYSTEM MULTIPLIERS PROVIDED IN TABLES 6-16 TO 6-17 OF | | | APPENDIX C TO THIS CHAPTER. RESIDENTIAL DUCTS WITH LESS | | | THAN R-4.2 INSULATION SHALL USE THE MULTIPLIERS | | | PROVIDED IN TABLES 6-18 TO 6-20 IN APPENDIX 13-C TO | | | THIS CHAPTER. | | | | | | 3)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C PLAN | | | M-3.0 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI | | | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI | | | CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR | | | 13-607.1.ABC.3.1.1. | | | | | | 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 5) AREA CALCULATIONS ON PLAN A-2.0 FOR UNDER AIR NEW | | | AND EXISTING DO NOT ADD UP, PLEASE RECHECK AND | | | CORRECT. | | | | | | 6) ARCHITECTURAL AND ELECTRICAL PLANS SHOW A NEW AIR | | | HANDLER IN THE GARAGE NEXT TO THE MAIN KITCHEN AND A | | | NEW CONDENSER UNIT UNDER THE STAIRS. AS THIS DOES NOT | | | COINCIDE WITH THE MECHANICAL PLANS AND ENERGY | | | CALCULATIONS, WHETHER NEW OR EXISTING PLEASE REMOVE, | | | SEE 2004 FBC 13-607.1.ABC.1.2. | | | | | | 7) PROVIDE FOR RETURN AIR TO BEDROOM #2 AND THE STUDY | | | ON PLAN M-2.0, PER 2004 FBC/R M1602.4. | | | | | | 8) RETURN AIR WILL NOT GET FROM THE MASTER BEDROOM TO | | | THE AIR HANDLER IF THE POCKET DOOR ARE CLOSED AT THE | | | MASTER BEDROOM OR THE POCKET DOORS AT THE HALL, PLEASE | | | CORRECT PER 2004 FBC/R M1602.4. | | | | | | 9) NO PLANS WERE SUBMITTED FOR THE THIRD FLOOR. PLEASE | | | SUBMIT PLANS FOR THE THIRD FLOOR AS DUCTS ARE GOING TO | | | IT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-16 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-15 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2009-04-16 08:49:51 | | | | | | | PASSED/PROVISO: | | | REVISION REQUIRED, NEW M/B W/C NOT VENTED & SHOWER IN | | | BATH #2 NOT VENTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-17 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-17 |
Time |
13:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-11 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-11 |
Time |
14:05 |
Sent To |
B1 |
|
| Notes |
| 2008-08-11 15:59:39 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 MECHANICAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUES | | | | | | 1. SHT A-2.3 SHOW COMPLIANCE WITH SECTIONS P305.9, | | | PROTECTION OF COMPONETS OF PLUMBING SYSTEM, (WATER | | | HEATER), AND M303.4 PROTECTION FROM DAMAGE, (WASH | | | MACHINE - A/C UNIT). INDICATE METHOD FOR BOTH. | | | | | | 2. ALL SHEETS WITH WAYNE FERRELL TITLE BLOCK. THE | | | ADDRESS INDICATED ON THE TITLE BLOCK FOR THE ARCHITECT, | | | (825 S.E. 8TH STREET DEERFIELD BEACH), DOES NOT REFLECT | | | THE ADDRESS OF RECORD ON THE FLORIDA DBPR WEBSITE. (801 | | | S.E. 12TH AVE. DEERFIELD BEACH). PLEASE UPDATE THE | | | TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING | | | FOR REVIEW. FAC 61G1-16.004(1) & FS 481.219. | | | | | | 3. SHT P-1.0 PLUMBING NOTES #10. AIR CHAMBERS ARE NOT | | | APPROVED. SECTION 604.9. PLEASE DELETE FROM REFERENCE. | | | | | | 4. SHT P-1.0 NEW WATER HEATER DETAIL. A FULL OPEN VALVE | | | IS REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER. | | | SECTION 606.1(7). PLEASE INDICATE IN DETAIL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2009-05-01 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2009-05-01 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2009-05-01 10:50:31 | ZONING PLAN REVIEW | | | | | | PERMIT NO.: 08070580 | | | ADDRESS: 203 ALPINE ROAD | | | CONTRACTOR/CONTACT: TED BERGHAUS | | | TELEPHONE NO.: 718.3997 | | | SCOPE OF REVIEW: SINGLE FAMILY RESIDENCE | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | | | | PRIOR TO FINAL INSPECTION, A LANDSCAPE PLAN WILL NEED | | | TO BE SUBMITTED AS PART OF THE PERMIT APPLICATION, | | | INDICATING THAT THE PROPERTY IS IN COMPLIANCE WITH | | | ARTICLE XIV OF THE CITY'S ZONING AND LAND DEVELOPMENT | | | REGULATIONS. THE PROPERTY IS REQUIRED TO BE IN | | | COMPLIANCE WITH THESE PROVISIONS AS THE VALUE OF THE | | | IMPROVEMENTS EXCEEDS 50% OF THE VALUE OF THE STRUCTURE. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | PHONE: (561) 822-1435 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-04-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2009-04-27 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2009-04-27 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2009-04-27 10:13:55 | ZONING PLAN REVIEW | | | | | | PERMIT NO.: 08070580 | | | ADDRESS: 203 ALPINE ROAD | | | CONTRACTOR/CONTACT: TED BERGHAUS | | | TELEPHONE NO.: 718.3997 | | | SCOPE OF REVIEW: SINGLE FAMILY RESIDENCE | | | | | | REVIEW STATUS: FAILED | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1) AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED | | | FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY | | | FENCING. THIS FORM MAY BE OBTAINED IN CONSTRUCTION | | | SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S | | | PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO | | | BE REVIEWED AND APPROVED. ONCE APPROVED BY PUBLIC | | | UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING | | | PERMIT APPLICATION. (REPEAT COMMENT) | | | | | | IMPORTANT: PRIOR TO FINAL INSPECTION, A LANDSCAPE PLAN | | | WILL NEED TO BE SUBMITTED AS PART OF THE PERMIT | | | APPLICATION, INDICATING THAT THE PROPERTY IS IN | | | COMPLIANCE WITH ARTICLE XIV OF THE CITY'S ZONING AND | | | LAND DEVELOPMENT REGULATIONS. THE PROPERTY IS REQUIRED | | | TO BE IN COMPLIANCE WITH THESE PROVISIONS AS THE VALUE | | | OF THE IMPROVEMENTS EXCEEDS 50% OF THE VALUE OF THE | | | STRUCTURE. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | PHONE: (561) 822-1435 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-11-06 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-11-06 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-11-06 |
Time |
19:34 |
Sent To |
|
|
| Notes |
| 2008-11-06 19:42:35 | ***FAILED*** | | | | | | THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO THE | | | ISSUANCE OF A PERMIT. UPON RESUBMITTAL, A WRITTEN | | | RESPONSE SHALL BE PROVIDED FOR EACH COMMENT, INDICATING | | | HOW IT HAS BEEN ADDRESSED. | | | | | | 1) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL | | | BE SUBMITTED WITH THE PERMIT PACKAGE. (REPEAT COMMENT) | | | | | | 2) ALTHOUGH THE NOTE WAS CORRECTED ON SHEET A-3.0B | | | REGARDING THE HEIGHT OF THE PRIVACY WALL, THE WALL THAT | | | IS DRAWN IN THE ELEVATION CONTINUES TO BE SIX (6) FEET | | | IN HEIGHT. THE MAXIMUM HEIGHT ALLOWED BY ZBA CASE NO. | | | 3222 WAS FIVE (5) FEET. PLEASE ENSURE THAT ALL NOTES, | | | PLANS, AND DETAILS CORRESPOND AND ADJUST THE HEIGHT OF | | | THE WALL TO SHOW A MAXIMUM OF FIVE (5) FEET. | | | | | | 3) IN REGARD TO DETAIL #4 ON SHEET A-2.0, WHICH WAS | | | ADDED REFERENCING THE SECTION OF THE PRIVACY WALL, | | | PLEASE PROVIDE DIMENSIONS THAT CORRESPOND WITH THE SITE | | | PLAN, ELEVATIONS, ETC. BE SURE THE WALL DOES NOT EXCEED | | | FIVE (5) FEET ON THE EXTERIOR FACE AND FOUR (4) FEET ON | | | THE INTERIOR FACE. | | | | | | 4 AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED | | | FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY | | | FENCING. THIS FORM MAY BE OBTAINED IN CONSTRUCTION | | | SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S | | | PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO | | | BE REVIEWED AND APPROVED. ONCE APPROVED BY PUBLIC | | | UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING | | | PERMIT APPLICATION. (REPEAT COMMENT) | | | | | | 5) REGARDING THE LIVING AREA ABOVE THE GARAGE...THE | | | REFRIGERATOR SHALL ONLY BE AN UNDERCOUNTER | | | REFRIGERATOR; AND JUST AS AN FYI, NO RENTAL LICENSE | | | WILL BE ISSUED FOR THIS AS A SEPARATE DWELLING UNIT IS | | | NOT PERMITTED. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR | | | PLANNER, AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-08-05 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-08-05 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2008-08-05 11:21:52 | ***FAILED*** | | | | | | THE FOLLOWING COMMENTS SHALL BE ADDRESSED PRIOR TO THE | | | ISSUANCE OF A PERMIT.UPON RESUBMITTAL, A WRITTEN | | | RESPONSE SHALL BE PROVIDED FOR EACH COMMENT, INDICATING | | | HOW IT HAS BEEN ADDRESSED. | | | | | | 1) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL | | | BE SUBMITTED WITH THE PERMIT PACKAGE. | | | | | | 2) THE VISIBILITY TRIANGLE SHALL BE SHOWN AND | | | DIMENSIONED ON THE SITE PLAN.(SECTION 94-305(E) AND | | | FIGURE X-1) | | | | | | 3) BUILDING HEIGHT SHALL BE MEASURED FROM GRADE. | | | PLEASE ADJUST THE DIMENSIONS ON THE ELEVATIONS | | | ACCORDINGLY.ADDITIONALLY, ENSURE THAT DIMENSIONS ARE | | | PROVIDED TO THE MEAN POINT ON ALL PITCHED ROOFS AND TO | | | THE ROOF DECK ON ALL FLAT ROOFS. (SECTION 94-611) | | | | | | 4) ON SHEET A-3.0B, THE NOTE REGARDING THE PRIVACY WALL | | | INDICATES 4 FEET WITH AN ADDITIONAL 2 FEET OF CONCRETE | | | BLOCK (OVERALL HEIGHT OF 6 FEET).THE NOTE ON THE SITE | | | PLAN INDICATES THAT THE WALL IS TO BE APPROXIMATELY 5 | | | FEET (ALLOWING FOR 4 FEET WHEN MEASURED ON THE INTERIOR | | | FACE OF THE WALL).THE VARIANCE ISSUED BY ZBA CASE NO. | | | 3222 PROVIDED FOR THE 5 FEET, NOT THE 6 FEET SHOWN ON | | | THE ELEVATIONS.(SEE FINAL ORDER FOR ZBA CASE NO. | | | 3222) | | | | | | 5) SHEET A-2.3 INDICATES A NEW FENCE NEXT TO THE | | | GARAGE.THIS IS NOT SHOWN ON THE SITE PLAN.PLEASE | | | ENSURE THAT ALL PLANS ARE CONSISTENT AND REFLECT THE | | | SAME SCOPE OF WORK. | | | | | | 6) SHEET A-2.0 REFERENCES A SECTION OF THE PRIVACY | | | WALL, INDICATING THAT IT IS DETAIL #4 ON SHEET | | | S-1.5....NO DETAIL OF THE PRIVACY WALL EXISTS ON THIS | | | SHEET.PLEASE PROVIDE A CROSS SECTION AND DETAIL OF | | | THE PRIVACY WALL, WITH DIMENSIONS, AND NOTE IT | | | CORRECTLY ON THE SITE PLAN. | | | | | | 7) AN APPROVED EASEMENT CONSENT FORM SHALL BE SUBMITTED | | | FOR THE CONSTRUCTION OF THE PRIVACY WALL AND/OR ANY | | | FENCING.THIS FORM MAY BE OBTAINED IN CONSTRUCTION | | | SERVICES AND WILL NEED TO BE TURNED INTO THE CITY'S | | | PUBLIC UTILITIES DEPARTMENT (1ST FLOOR OF CITY HALL) TO | | | BE REVIEWED AND APPROVED.ONCE APPROVED BY PUBLIC | | | UTILITIES, IT SHALL BE TURNED IN WITH YOUR BUILDING | | | PERMIT APPLICATION. | | | | | | 8) SHEET E-2.1 SHOWS THE INSTALLATION OF A 220V OUTLET | | | IN THE LIVING AREA ABOVE THE GARAGE.NO 220V OUTLETS | | | SHALL BE PERMITTED.THE PROPERTY IS LOCATED IN AN SF7 | | | ZONING DISTRICT, WHICH DOES NOT ALLOW FOR THE | | | CONSTRUCTION OF ACCESSORY DWELLING UNITS.THE SPACE | | | ABOVE THE GARAGE CANNOT BE CONSTRUCTED SO AS TO CREATE | | | A DWELLING UNIT, AS DEFINED IN SECTION 94-611 OF THE | | | CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | PLEASE REFER TO SUCH DEFINITION AND AMEND THE PLANS | | | ACCORDINGLY. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR | | | PLANNER, AT (561) 822-1435. |
|
|
|