Plan Review Details - Permit 08070579
Plan Review Stops For Permit 08070579
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-10 Cont ID  
Sent By mjacobs Date 2008-09-10 Time 07:25 Rev Time 0.00
Received By mjacobs Date 2008-09-09 Time 12:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By mjacobs Date 2008-08-11 Time 09:52 Rev Time 0.00
Received By mjacobs Date 2008-08-11 Time 07:52 Sent To PC
Notes
2008-08-11 09:52:17 
 1)SHOW THE LAYOUT OF THE FIRE SPRINKLER HEADS ON THE
 CEILING PLAN NOW THE SPACE IS ALTERED. IS THERE A
 SPRINKLER HEAD IN THE NEW CLOSET? IF YES, PLEASE SHOW
 THE LOCATION OF THE SPRINKLER HEAD IN THE NEW CLOSET
 AND THROUGH THE SPACE. FBC* 106.3.5.1.1(5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-30 Cont ID  
Sent By btrobaug Date 2008-07-30 Time 14:18 Rev Time 0.00
Received By btrobaug Date 2008-07-30 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By mawillia Date 2008-09-09 Time 10:45 Rev Time 0.00
Received By mawillia Date 2008-09-09 Time 10:22 Sent To  
Notes
2008-09-09 10:36:07*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A1.1, A3.1, AND E2 WERE
 STAMPED, INITIALED, AND DATED
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By mawillia Date 2008-08-05 Time 11:52 Rev Time 0.00
Received By mawillia Date 2008-08-04 Time 16:51 Sent To  
Notes
2008-08-05 12:01:21*****PROVISO*****
  
  
 1. ON SHEET T IN THE CODES SECTION, ELIMINATE NFPA 72
 LISTED BEHIND FLORIDA FIRE PREVENTION CODE 2004
 EDITION. PLEASE BE ADVISED THAT NFPA 72 IS THE NATIONAL
 FIRE ALARM CODE NOT A FLORIDA FIRE PREVENTION CODE.
  
 2. ON SHEET A3.1, REFERENCE THE 2003 EDITION OF NFPA
 NOT THE 2000 AS LISTED IN THE DOOR SCHEDULE SECTION.
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENTS HAVE BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 16:38 Sent To  
Notes
2008-08-25 08:52:44TO BOB #6.
2008-08-21 16:38:47WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-11 Time   Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 16:41 Sent To  
Notes
2008-07-28 08:48:21TO "BOB"#6
2008-07-18 16:42:52WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-28 Cont ID  
Sent By tgordon Date 2008-07-28 Time 11:31 Rev Time 0.30
Received By tgordon Date 2008-07-28 Time 11:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-30 Cont ID  
Sent By astelly Date 2008-07-30 Time 10:40 Rev Time 0.00
Received By astelly Date 2008-07-30 Time 10:40 Sent To  
Notes
***NONE***