Plan Review Details - Permit 08070557
Plan Review Stops For Permit 08070557
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-05 Cont ID  
Sent By jwitmer Date 2009-04-05 Time 17:36 Rev Time 2.00
Received By jwitmer Date 2009-04-05 Time 17:36 Sent To  
Notes
2009-04-05 17:40:414-05-09
 BUILDING PROVISO;
  
 SHEET S2 DETAIL# 2,A/C CONDENSING UNIT STRAP CONNECTION
 BY MANUFACTURER, PLEASE PROVIDE BY INSPCTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-15 Cont ID  
Sent By jwitmer Date 2008-09-15 Time 09:31 Rev Time 0.77
Received By jwitmer Date 2008-09-15 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 13:23 Rev Time 3.33
Received By jwitmer Date 2008-08-12 Time 13:23 Sent To  
Notes
2008-08-12 13:27:34BUILDING PLAN REVIEW
 PERMIT: 08070557
 ADD: 828 SOUTHERN BLVD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9625
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 12, 2008
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2)PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND
 FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF
 AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN
 ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF
 AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN,
 INC.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.
 (ARCHITECTS)THE TITLE BLOCK FOR ANY SHEET BEARING THE
 NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION. (ENGINEER)
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET A-1 INDICATES TWO ACCESSIBLE RAMPS DETAIL
 8/A-13 AND DETAIL 10/ A-13 NEITHER RAMP INDICATES THE
 LENGTH OF THE BOTTOM LANDING. 11-4.8.4.(2) LANDINGS.
 ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR,
 & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS THAN 72"
 OF STRAIGHT & LEVEL CLEARENCE.
  
 4) S-2 GENERAL NOTE (5)INDICATESWIND DESIGN TO THE
 ASCE 7-05, THE 2004 FBC RECOGNIZES THE ASCE 7-02. 004
 FBC CHAPTER 35 REFERENECED STANDARDS RECOGNIZES ASCE
 7-02 .ALSO 1603.1.4 WIND DESIGN DATA.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-04-24 Cont ID  
Sent By dpalmer Date 2009-04-24 Time 16:27 Rev Time 0.00
Received By dpalmer Date 2009-04-24 Time 16:27 Sent To  
Notes
2009-04-24 16:28:36 
 PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR
 PLUMBING REVIEW AT HIS REQUEST.
  
 PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL
 GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE
 PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE
 REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW
 STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER
 WITH MR. ROBERT BROWN ALSO.
 ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS
 REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY
 GENERATOR.
  
  
2009-04-24 16:28:25** REDLINED PLANS**
  
 STORE 50, 828 SOUTHERN BLVD
  
 1) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO
 BE SHOWN AND FIGURED AT 125%. 215.3,230.42.
  
 2) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL
 BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE
 INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG
 WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE
 VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT
 APPLICATION.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-04-05 Cont ID  
Sent By dpalmer Date 2009-04-05 Time 13:35 Rev Time 0.00
Received By dpalmer Date 2009-04-05 Time 09:14 Sent To  
Notes
2009-04-05 13:35:56 
 ** DENIED 3RD REVIEW **
 ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS
 WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE
 NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO
 MEET MINIMUM CODES.
  
 STORE #50 828 SOUTHERN BLVD.
  
  
 1) NOTE: THE PLANS SHOW A E PANEL AND EM PANEL BOTH
 BEING TAPPED FROM THE ATS. ONLY THE E PANEL CONTAINS
 OVER CURRENT PROTECTION FOR THE TAPPED CONDUCTORS.
 PANEL EM SHOWN AS MLO. SEE 240.21, 310.16. EC
  
  
 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE
 HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE
 INFORMATION. BASED ON THE RISER AND PANELS, THERE IS
 OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED
 SYSTEMS IN THE SAME EQUIPMENT. SEE E PANEL WHICH SHARES
 NUMEROUS OTHER OPTIONAL STAND-BY LOADS.
 CODES HAS NOT PERMITTED 700 AND 702 SYSTEMS IN THE SAME
 EQUIPMENT FOR MORE THAN TWENTY YEARS. SOME OF THESE
 ITEMS HAVE BEEN DONE IN THE LAST TWENTY YEARS AND
 PANELS SHOW ADDING MORE OPTIONAL STAND-BY TO PANELS
 WHERE LIFE SAFETY WIRING IS LOCATED.
 ALL OPTIONAL STAND-BY LOADS NEED TO COME FROM SEPARATE
 SYSTEM.
 THERE ARE OTHER OPTIONS HOWEVER THIS IS BEING NOTED BY
 REVIEWER AS NEEDING TO MEET MINIMUM CODES.
 SYSTEMS NEED TO BE LABELED ACCORDINGLY SUCH AS *
 OPTIONAL STAND-BY AND LIFE SAFETY. BASED ON PANEL
 SCHEDULES SUBMITTED THERE IS LIFE SAFETY, LEGALLY
 REQUIRED AND OPTIONAL STAND-BY LOADS.
 700,701, OR 702 SYSTEM LOADS.
  
 *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT
 DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS
 SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO
 THE CITY OF WEST PALM BEACH.
 ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED,
 THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE
 PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE
 CONTACT/MEETING HAS BEEN HELD.
  
 3) NOTE: LAYOUT FOR ATS, E AND EM NEED TO BE SHOWN ON
 PLANS.
 7.2,NFPA-110 , NEC 110.26, 240.24 ETC
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE,
 ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE
 MORE THAN ONE.
 ENCLOSURES SHALL MEET NFPA-110 7.2.1.1
 NEC 110.3, 700.6, 90.7 ETC
  
 5) NOTE: FUEL STAND-BY TIME, CAPACITY, SIZING ETC NEEDS
 TO BE ON PLANS. MINIMUM TIMES ARE STATED IN NFPA-110
 CHAPTER 4 ALONG WITH NEC 700.12
  
 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR
 FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN
 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL
 BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE
 PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS
 NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE
 COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT
 MEET 225.38, 225.39.
 THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD
 SERVED.
 ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR
 MAY OR MAY NOT MEET READILY ACCESSIBLE DEPENDING ON
 LOCKED ENCLOSURE, FENCING AROUND ENCLOSURE ETC.
  
 7) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL
 BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY
 AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD
 CREATE A SAFETY ISSUE.
 OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH
 AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE
 LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING
 PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING
 INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2
 PLEASE EXPLAIN THE DEVICES WHICH SEEM TO BE A STANDARD
 SWITCH WITH AN *A* OR *B* DESIGNATION NEXT TO THEM. ARE
 THESE AUTOMATED OVER RIDES?
 THE CATALOG NUMBER USED ON PLANS FOR THE WALL DEVICES
 WAS NOT READILY LOCATED ON HUBBELL WEBSITE WITH OTHER
 DEVICES.
 NEW OUTSIDE LIGHTS INDICATE CONTROLS PER ENERGY
 MANAGEMENT SYSTEM HOWEVER PLEASE SEE 13-415.1.ABC.1.4.
 DOES THIS PROVIDE 10HRS MINIMUM BACK UP FOR SCHEDULING
 OR MEET PHOTO-SENSOR REQUIREMENTS? IF THIS WAS THE ONLY
 ITEM IT WOULD HAVE BEEN REDLINED.
  
 8) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002.
 ( ON ELECTRIC HOWEVER NOT ON COVER) THIS CAN BE
 REDLINED)
  
 9) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR
 GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF
 NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED
 FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE
 PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER
 REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS
 EXAMINERS.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-02 Cont ID  
Sent By dpalmer Date 2008-10-02 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2008-10-02 Time 15:42 Sent To  
Notes
2008-10-02 15:42:16 
 ** DENIED 2ND REVIEW **
  
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLANS DO NOT SHOW ANY LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2,13-415.2.ABC.1.1, .1.2.
 THE RESPONSE LETTER SUBMITTED MAKES NOTE OF COMPLIANCE
 HOWEVER THE PLANS WHICH ARE THE RECORD SET OF DRAWINGS
 ARE REQUIRED TO BE DESIGNED AND SHOW COMPLIANCE WITH
 THE MINIMUM CODE(S). FS 553.73
 PLEASE BE SURE TO SEE ALL LIGHTING SHOWN ON PLANS FOR
 ALL AREAS IN WHICH NEW LIGHTING IS BEING ADDED. IF THE
 EXISTING AMOUNT OF WATTS PER SQUARE FOOT EXCEEDS
 ALLOWANCE NEW LIGHTING MAY NOT SIMPLY BE ADDED. THIS IS
 FOR ALL AREAS IN WHICH NEW LIGHTING IS BEING SHOWN.
 OTHER ALLOWANCES ETC MAY NEED TO BE LOOKED INTO FOR
 DESIGN.
  
 2) NOTE: PLEASE SEE SECTIONS OF THE CODE AS NOTED
 PREVIOUSLY FOR REQUIRED LIGHTING CONTROLS WAS NOT
 ADDRESSED. THE RESPONSE MENTIONS *SWITCHES* ARE AND
 WERE PROVIDED ON PLANS. PLEASE SEE FBC 13-415.1.ABC.1.
 THIS SECTION OF THE CODE REQUIRES AUTOMATED LIGHTING
 CONTROLS FOR ALL BUILDINGS OVER 5K SQ FT. AS THIS
 BUILDING MOST CERTAINLY MEETS THIS DEFINITION CONTROLS
 ARE REQUIRED. THE SUBSEQUENT SECTIONS 13-415.1.ABC.1.1,
 .1.2 AND .1.3 IN THIS SITUATION ALSO APPLY. THIS
 REQUIRES ANY SEPARATE SPACES TO CONTAIN SEPARATE
 CONTROLS. A *STANDARD SWITCH* DOES NOT MEET THESE
 SECTIONS OF THE CODE AS AUTOMATED SHUT OFF OF SOME KIND
 IT REQUIRED. THIS MAY BE DONE BY OCCUPANCY SENSORS, OR
 MANUAL SWITCH WHICH OVER RIDE SOME SORT OF LIGHTING
 CONTROL SYSTEM. THERE ARE LITERALLY DOZENS OF WAYS TO
 ACHIEVE MINIMUM CODE COMPLIANCE. PLEASE ADDRESS THIS
 COMMENT.
 ** THE ENERGY CODE REQUIRES ALL NEW BEING INSTALLED OR
 REPLACED TO MEET PRESCRIPTIVE REQUIREMENTS.
  
 3) NOTE: PLEASE OBTAIN A LETTER FROM PUBLIX CORPORATE
 OFFICES/ LAW DEPARTMENT WHICH NEEDS TO STATE THE STORE
 WILL NOT BE OCCUPIED WHEN THE NORMAL POWER AS WELL AS
 THE OPTIONAL STAND-BY GENERATOR IS LOST AND UNDER LIFE
 SAFETY GENERATOR POWER. (OR WORDS TO THAT AFFECT). THIS
 INCLUDES EMPLOYEES NOT ONLY THE PUBLIC.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-11 Cont ID  
Sent By dpalmer Date 2008-08-11 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2008-08-11 Time 13:18 Sent To  
Notes
2008-08-11 13:25:40 
 ** DENIED **
  
 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS
 LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN
 IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT
 A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS
 LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE
 WEBSITE.
 PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE
 NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR
 ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL
 BUSINESS.
 PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH) AND FAC
 61G15-23.002, 61G1-16.004.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER
 SHEETS.
 PLEASE SEE THE COVER SHEET AS IT STATES A 2004 NEC. YET
 THERE IS NO SUCH CODE.
 THE LIFE SAFETY PLAN HOWEVER DOES LIST THE 2005 NEC.
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP
 LIGHTING FOR EGRESS PATHS IN AREAS IN WHICH WORK IS
 BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH
 OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT
 OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT
 CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2.
  
 ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION
 UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE
 *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO
 HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION.
  
 ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH
 BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY
 AREAS, PLEASE INDICATE.
 AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN
 AREAS ARE KNOWN TO BE BATTERY BACK UP.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW
 BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND
 .1.3.
  
 6) NOTE: PLEASE SEE SHEET E-6 AS THIS DOES NOT
 CORRELATE WITH THE INFORMATION ON THE RISER DIAGRAM
 SHEET E-7.
 FOR EXAMPLE:
 E-6 SHOWS CU #4, YET RISER SHEET DOES NOT INDICATE ANY
 CU#4.
  
 FOR EXAMPLE:
 PLEASE SEE E-7 AS A NOTE MENTIONS NEW WORK TO BE SHADED
 IN BLACK LINES. HOWEVER BASED ON NEW UNITS AND
 ELECTRICAL EQUIPMENT SHOWN ON E-6 THIS IS NOT DONE.
 PLEASE COORDINATE ALL.
  
 7) NOTE: PLEASE UPDATE THE ELECTRICAL RISER DIAGRAM
 WITH THE ACTUAL ELECTRICAL ON-SITE.
 230, ETC
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-04-27 Cont ID  
Sent By dpalmer Date 2009-04-27 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2009-04-27 Time 08:47 Sent To  
Notes
2009-04-27 08:48:48FIRE REVIEW OK, SHEETS STAMPED, WILL REVISE LS AND A
 SHEETS TO COORDINATE FOR EXIT SIGNS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 14:21 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 13:52 Sent To  
Notes
2009-04-06 14:21:17*****PROVISO*****
  
 PLAN SHEETS LS-1, FP-1, FA-1 & FA-2 WERE PREVIOUSLY
 FIRE-STAMPED ON 10/07/08; SHEET A-4 WAS STAMPED,
 INITIALED, AND DATED. PLAN SHEETS A-4 AND E-2 TO BE
 FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S COMMENTS AS
 WELL AS THE BELOW COMMENT HAS BEEN ADDRESSED:
  
 1. EXIT LIGHTS SHOWN E-2 NOT CORRELATING TO THOSE SHOWN
 ON LS-1 AND A-2 SHEETS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By mwennerg Date 2008-10-07 Time 10:10 Rev Time 0.00
Received By mwennerg Date 2008-10-07 Time 10:10 Sent To  
Notes
2008-10-07 10:11:22STAMPED LS-1, FP-1, FA-1 AND FA-2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-15 Cont ID  
Sent By mwennerg Date 2008-08-15 Time 15:45 Rev Time 0.00
Received By mwennerg Date 2008-08-15 Time 15:45 Sent To  
Notes
2008-08-15 15:54:13***DENIED***
  
 1) PLEASE INDICATE DOORS PROVIDED WITH PANIC HARDWARE
 ON DOOR SCHEDULE. PANIC HARDWARE IS INDICATED ON EXIT
 ANALYSIS PLAN.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 3) PLEASE CLARIFY THE SCOPE OF WORK REGARDING THE FIRE
 ALARM SYSTEM. SOME NEW EQUIPMENT IS SHOWN BUT CONTROL
 PANEL ILLUSTRATES AS EXISTING TO REMAIN.
  
 4) ILLUMINATED EXIT SIGNS SHALL BE PROVIDED AT
 DISTANCES NOT TO EXCEED 100'.
  
 5) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH THE REQUIREMENTS OF NFPA 241.
  
 7) CLARIFY IF HOOD EQUIPMENT IS FOR WARMING ONLY AS
 PLANS INDICATE GREASE HOOD. PLANS DO NOT INDICATE
 SUPPRESSION SYSTEM.
  
 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-04-27 Cont ID  
Sent By dwise Date 2009-04-27 Time 19:58 Rev Time 0.00
Received By dwise Date 2009-04-27 Time 19:58 Sent To  
Notes
2009-04-27 19:59:10GAS UNDER SEPERATE PERMIT AND REVIEW.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-06 Cont ID  
Sent By kstevens Date 2009-04-06 Time 07:13 Rev Time 0.00
Received By kstevens Date 2009-04-06 Time 07:13 Sent To  
Notes
2009-04-06 07:17:50DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 NFPA-58
  
 A. SHT P-3 & P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF
 ITS SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE
 LOCATED SO THAT THE FILLING CONNECTION AND FIXED
 MAXIMUM LIQUID LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY
 EXTERNAL SOURCE OF IGNITION. SEE TABLE 6.3.9. TANK IS A
 MAXIMUM 7 FT TO THE FAR SIDE OF THE GENERATOR.
  
 B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE
 GAS PERMIT REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC
 TRANSFER VALVE AND SHUT OFF VALES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT
 WILL BE REMOVED.
  
 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC
 TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS
 TO NATURAL GAS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 09:11 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 09:11 Sent To  
Notes
2009-03-31 09:12:18TO "C40"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 08:42 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 08:42 Sent To  
Notes
2009-03-09 08:47:15TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 15:51 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 15:51 Sent To  
Notes
2008-10-06 11:03:3010/6/08--FIRE THE LAST REVIEW, PLANS TAKEN OFF THE BD
 AND ROUTED TO MIKE WENNERGREN'S DESK
2008-09-10 15:54:38TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-15 Cont ID  
Sent By mwennerg Date 2008-08-15 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 13:09 Sent To  
Notes
2008-07-21 13:15:51TO "COMM" BD#5--PLANS ON RACK/1 ROLL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 19:42 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 19:37 Sent To  
Notes
2009-04-02 19:42:03***PROVISO***
 ALL MECHANICAL APPLIANCES EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.13. PROVIDE DATA SHOWING ALL
 OUTDOOR APPLIANCES CAPABLE OF WITHSTANDING ANTICIPATED
 WIND PRESSURES AND REVISE PLANS AS NECESSARY PRIOR TO
 MECHANICAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-09-18 Cont ID  
Sent By rregueir Date 2008-09-18 Time 09:45 Rev Time 0.00
Received By rregueir Date 2008-09-18 Time 09:16 Sent To  
Notes
2008-09-18 09:45:12REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. DETAIL HAS BEEN PROVIDED IN STRUCTURAL PAGES SHOWING
 HOW THE CURBS FOR NEW AHU AND CU ARE TO BE ATTACHED TO
 EXISTING CURB AS WELL AS FOR THE NEW REMOTE CONDENSERS
 TO THE STANDS. HOWEVER, THE NOTES ON PAGE S-2 CALL FOR
 THE APPLIANCE MANUFACTURER TO PROVIDE SHOP DRAWINGS
 WITH THE ATTACHMENT DETAILS FOR THE APPLIANCES TO THE
 CURBS AND/OR STANDS. NO SUCH INFORMATION WAS PROVIDED
 WITH THIS SUBMISSION FOR REVIEW. ALSO, NO INFORMATION
 WAS PROVIDED FROM THE APPLIANCE/EQUIPMENT MANUFACTURERS
 SHOWING THE PROPOSED APPLIANCES THEMSELVES ARE DESIGNED
 TO RESIST WIND PRESSURES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 AS DETERMINED IN ACCORDANCE WITH FBCM 301.13. PROVIDE
 ALL DOCUMENTATION NECESSARY TO DEMONSTRATE COMPLIANCE
 WITH THESE REQUIREMENTS FOR REVIEW.
 NOTE: THIS REQUIREMENT ALSO APPLIES TO THE PROPOSED NEW
 GREASE EXHAUST FAN F-3.
  
 2. OK
  
 3. OK
  
 4. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-07 Cont ID  
Sent By rregueir Date 2008-08-07 Time 13:08 Rev Time 0.00
Received By rregueir Date 2008-08-07 Time 13:08 Sent To  
Notes
2008-08-07 13:09:55REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO DETAIL WAS PROVIDED REGARDING INSTALLATION OF NEW
 AHU 2 AND CU 2 ON EXISTING ROOF CURB(S). PROVIDE WIND
 LOAD DATA AND ATTACHMENT DETAIL. MECHANICAL EQUIPMENT
 AND APPLIANCES THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBCM 301.13.
 ALSO, PROVIDE DOCUMENTATION FROM THE
 EQUIPMENT/APPLIANCE MANUFACTURER SHOWING THE
 EQUIPMENT/APPLIANCES ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 2. PAGE M-5 A/C EQUIPMENT SCHEDULE SHOWS THE AHU AT
 8000 CFM WITH A FAN MOTOR RATED AT 10 HP. THIS GIVES A
 RATIO OF 1.25 HP PER 1000 CFM. THIS EXCEEDS THE FAN
 POWER LIMITATION LISTED IN TABLE 13-410.1.ABC.1.1.1. IF
 CLAIMING CONDITION 2 OR 3 UNDER THIS SECTION, PROVIDE
 SUPPORTING CALCULATIONS AS LISTED IN THIS SECTION.
  
 3. DETAIL 1 PG M-5 SHOWS A NEW GRIDDLE UNDER NEW GH-1.
 HOWEVER, GH-1 HOOD NOTES CALLS FOR A NEW ROTISSERIE TO
 BE INSTALLED UNDER THIS HOOD. PLEASE CLARIFY. A
 ROTISSERIE IS LIKELY TO BE MUCH LARGER THAN THE GRIDDLE
 SHOWN. THE INSIDE LOWER EDGE OF CANOPY-TYPE COMMERCIAL
 COOKING HOODS SHALL OVERHANG OR EXTEND A HORIZONTAL
 DISTANCE OF NOT LESS THAN 6 INCHES BEYOND THE EDGE OF
 THE COOKING SURFACE IN ACCORDANCE WITH FBCM 507.12.
  
 4. FAN SCHEDULE PG M-5: NOTE #3 FOR GREASE EXHAUST FAN
 F-3 CALLS FOR THE FAN TO BE UL 705 LISTED. GREASE
 EXHAUST FANS SHALL BE LISTED AND LABELED IN ACCORDANCE
 WITH UL 762 PER FBCM 506.5.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-06 Cont ID  
Sent By kstevens Date 2009-04-06 Time 07:25 Rev Time 0.00
Received By kstevens Date 2009-04-06 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-11 Cont ID  
Sent By kstevens Date 2008-09-11 Time 08:43 Rev Time 0.00
Received By kstevens Date 2008-09-11 Time 08:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By kstevens Date 2008-07-31 Time 15:29 Rev Time 0.00
Received By kstevens Date 2008-07-30 Time 16:53 Sent To  
Notes
2008-07-31 15:35:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLUMBING SHEETS. THE TITLE BLOCK SHALL CONTAIN
 THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER. THE ADDRESS DOES NOT REFLECT THE ADDRESS OF
 RECORD ON THE STATE OF FLORIDA, DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR THE TITLE BLOCKS TO REFLECT EACH
 OTHER PRIOR TO RESUBMITTING FOR REVIEW AT THE CITY WPB.
 FAC 61G15-23.002(2) & FS 471.025.
  
 2. SHT P-5 CAFE PLUMBING ISOMETRIC. A CHECK VALVE AND A
 FULL OPEN VALVE SHALL BE INSTALLED IN THE PUMP
 DISCHARGE PIPING BETWEEN THE PUMP AND THE GRAVITY
 SYSTEM. SECTION 712.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-07 Cont ID  
Sent By eschneid Date 2009-04-07 Time 14:40 Rev Time 0.50
Received By eschneid Date 2009-04-07 Time 14:39 Sent To  
Notes
2009-04-07 14:41:05PASSED
  
 NOTE: GENERATOR AND ITS SCREEN WALL AND LANDSCAPE
 REQUIRE A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-22 Cont ID  
Sent By bpowell Date 2008-09-22 Time 09:41 Rev Time 0.00
Received By bpowell Date 2008-09-22 Time 09:41 Sent To  
Notes
2008-09-22 09:42:491. NO NEW SHEETS FOR ZONING PREVIOUS APPROVAL STANDS.
  
 BOBBY POWELL JR., PLANNER, (561) 822-1449

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-29 Cont ID  
Sent By bpowell Date 2008-07-29 Time 17:07 Rev Time 0.00
Received By bpowell Date 2008-07-29 Time 17:07 Sent To  
Notes
***NONE***