| 2008-08-29 13:51:26 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | |
| | 1. INSTALLATION SCHEDULE WAS COMPLETED, BUT NOTE THE |
| | FOLLOWING: |
| | |
| | A. SHUTTER CONNECTION MOUNTING TYPE SHOULD REFER TO THE |
| | TYPE OF CONNECTION USED, NOT FASTENER. YOU HAVE MARKED |
| | A-A ON THE PRODUCT APPROVAL, SEE SHEET 3. |
| | B. A-A REQUIRES USE OF CHART 1 FOR CONCRETE BLOCK; YOU |
| | HAVE USED CHART 3. CHECK ALL; OTHER INFORMATION MAY BE |
| | INCORRECT. THE SCHEDULE IS SPOT CHECKED; IT DOES NOT |
| | HAVE ALL INFORMATION SO EVEN A SPOT CHECK IS DIFFICULT. |
| | C. SPECIFIC ANCHOR TYPE SHOULD INCLUDE THE VERY BASIC |
| | INFORMATION FROM THE PRODUCT APPROVAL; IN THIS CASE, |
| | 1/4" TAPCON WOULD SUFFICE. |
| | D. YOU'VE SPECIFIED A TAPCON LENGTH. PLEASE BE ADVISED |
| | THAT THE TRACK AND STUCCO MUST BE ADDED TO THE MINIMUM |
| | EMBEDMENT REQUIRED ON THE PRODUCT APPROVAL, SHEET 7. |
| | E. A 2" EDGE DISTANCE REQUIRES A FACTOR OF .71, SEE |
| | SHEET 7. |
| | THANK YOU FOR PROVIDING TWO SETS. WHEN RESUBMITTING, |
| | PLEASE BE SURE THAT TWO COMPLETE COLLATED SETS OF |
| | DOCUMENTS ARE IN THE PACKAGE. |
| | |
| | 2. ADDRESSED. |
| | |
| | 3. FROM PREVIOUS LIST, NOTE EXISTING CONDITIONS (TYPE |
| | OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC |
| | EB 505.1. PLEASE STATE WHAT TYPE OF WINDOW WAS ON THE |
| | HOUSE BEFORE THEY WERE CHANGED WITHOUT A PERMIT. TYPE |
| | OF WINDOW WOULD BE JALOUSY, SINGLE HUNG, ETC. |
| | |
| | 4. FROM PREVIOUS LIST; ON THE INSTALLATION SCHEDULE, |
| | THE SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE |
| | WITH THE ANCHOR SCHEDULE; FOR INSTANCE, A THROUGH G, |
| | SEE DETAILS ON PRODUCT APPROVAL. THIS COMMENT WAS NOT |
| | ADDRESSED, SEE OTHER COMMENTS. |
| | |
| | |