Plan Review Details - Permit 08070549
Plan Review Stops For Permit 08070549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-09 Cont ID  
Sent By shill Date 2008-09-09 Time 10:30 Rev Time 0.00
Received By shill Date 2008-09-09 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-29 Cont ID  
Sent By shill Date 2008-08-29 Time 13:17 Rev Time 0.00
Received By shill Date 2008-08-29 Time 13:17 Sent To  
Notes
2008-08-29 13:51:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. INSTALLATION SCHEDULE WAS COMPLETED, BUT NOTE THE
 FOLLOWING:
  
 A. SHUTTER CONNECTION MOUNTING TYPE SHOULD REFER TO THE
 TYPE OF CONNECTION USED, NOT FASTENER. YOU HAVE MARKED
 A-A ON THE PRODUCT APPROVAL, SEE SHEET 3.
 B. A-A REQUIRES USE OF CHART 1 FOR CONCRETE BLOCK; YOU
 HAVE USED CHART 3. CHECK ALL; OTHER INFORMATION MAY BE
 INCORRECT. THE SCHEDULE IS SPOT CHECKED; IT DOES NOT
 HAVE ALL INFORMATION SO EVEN A SPOT CHECK IS DIFFICULT.
 C. SPECIFIC ANCHOR TYPE SHOULD INCLUDE THE VERY BASIC
 INFORMATION FROM THE PRODUCT APPROVAL; IN THIS CASE,
 1/4" TAPCON WOULD SUFFICE.
 D. YOU'VE SPECIFIED A TAPCON LENGTH. PLEASE BE ADVISED
 THAT THE TRACK AND STUCCO MUST BE ADDED TO THE MINIMUM
 EMBEDMENT REQUIRED ON THE PRODUCT APPROVAL, SHEET 7.
 E. A 2" EDGE DISTANCE REQUIRES A FACTOR OF .71, SEE
 SHEET 7.
 THANK YOU FOR PROVIDING TWO SETS. WHEN RESUBMITTING,
 PLEASE BE SURE THAT TWO COMPLETE COLLATED SETS OF
 DOCUMENTS ARE IN THE PACKAGE.
  
 2. ADDRESSED.
  
 3. FROM PREVIOUS LIST, NOTE EXISTING CONDITIONS (TYPE
 OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC
 EB 505.1. PLEASE STATE WHAT TYPE OF WINDOW WAS ON THE
 HOUSE BEFORE THEY WERE CHANGED WITHOUT A PERMIT. TYPE
 OF WINDOW WOULD BE JALOUSY, SINGLE HUNG, ETC.
  
 4. FROM PREVIOUS LIST; ON THE INSTALLATION SCHEDULE,
 THE SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE
 WITH THE ANCHOR SCHEDULE; FOR INSTANCE, A THROUGH G,
 SEE DETAILS ON PRODUCT APPROVAL. THIS COMMENT WAS NOT
 ADDRESSED, SEE OTHER COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 15:07 Rev Time 0.00
Received By shill Date 2008-08-04 Time 15:07 Sent To  
Notes
2008-08-04 15:09:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE, ITEM 1 ABOVE.AN
 INSTALLATION SCHEDULE WAS SUBMITTED WITH ONE OPENING,
 BUT ALL OF THE WINDOWS ARE TO HAVE IMPACT PROTECTION
 FBC R301.
  
 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 4.ON THE INSTALLATION SCHEDULE, THE SHUTTER
 CONNECTION MOUNTING TYPE IS TO CORRELATE WITH THE
 ANCHOR SCHEDULE; FOR INSTANCE, A THROUGH G, SEE DETAILS
 ON PRODUCT APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 14:13 Sent To B
Notes
2008-09-03 14:14:03TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 08:08 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 08:08 Sent To B
Notes
2008-08-26 08:08:55TO "BUILD" SANANTHA H.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 15:09 Rev Time 0.00
Received By shill Date 2008-07-21 Time 11:54 Sent To  
Notes
2008-07-21 11:54:39TO "MISC" BOX#1