Plan Review Details - Permit 08070547
Plan Review Stops For Permit 08070547
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By mperson Date 2008-07-21 Time 09:39 Rev Time 0.00
Received By mperson Date 2008-07-21 Time 09:38 Sent To PC
Notes
2008-07-21 09:52:29REVISION: "OK" CHANGED NEW PIPING TO DRYER, LONGEST
 LENGTH AND TOTAL BTU'SOF SYSTEM. NOTE, EXPIRED PERMIT
 #07070156 PLANS AND PERMIT APPLICATION WERE TRANSFERRED
 TO NEW GAS PERMIT #08070547.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-07-17 Cont ID  
Sent By spalmer Date 2008-07-17 Time 15:44 Rev Time 0.00
Received By spalmer Date 2008-07-17 Time 15:44 Sent To  
Notes
2008-07-17 15:44:44NO PLANS FOR EXPIRED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 16:17 Sent To G
Notes
2008-07-18 16:18:04TO "G" BOX/REV