| Plan Review Stops For Permit 08070537 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-08-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-08-22 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-08-22 |
Time |
16:52 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-08-04 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-08-04 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2008-08-04 15:13:46 | | | | BUILDING PLAN REVIEW | | | PERMIT: 08070537 | | | ADD: 1701 S. FLAGLER DR. #702 | | | CONT: CAMERON H. FOCKLER | | | TEL: (561)748-8818 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 8-4-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION | | | SHALL BE SHOWN ON THE PLANS. | | | | | | 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN | | | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF | | | THIS CODE. | | | | | | 5)SUBMIT AN ELEVATION FRAMING DETAIL FOR THE NEW | | | SOFFITS INDICATING THE ATTACHMENT AND STUD SPACING | | | DETAIL. THIS IS A TYPE 1 CONSTRUCTION BUILDING; | | | THEREFORE, ONLY FIRE- RETARDANT-TREATED WOOD IS | | | PERMITTED IN THE NON BEARING WALLS FBC 603.1 (1). SEE | | | DETAIL A. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-22 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-22 |
Time |
11:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-30 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-30 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-07-30 13:42:42 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). LOCATE TO SHOW COMPLIANCE | | | ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-08-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-22 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-22 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2008-08-22 13:39:43 | STAMPED NEW SHEET A1. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-01 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-01 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2008-08-01 15:15:35 | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-08-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-13 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-13 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2008-08-15 16:03:33 | TO "BOB"#9 | | 2008-08-13 09:18:15 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-08-05 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-07-21 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2008-07-28 08:52:58 | TO "BOB"#8 | | 2008-07-21 09:02:02 | WAITING FOR "BOB" |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-08-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-18 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-18 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-29 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-29 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-07-29 13:43:09 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007 | | | REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5 | | | RETENTION OF CONSTRUCTION DOCUMENTS. | | | | | | 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 | | | EXISTING BUILDING CHAPTER 3. | | | | | | 3. CLEARLY INDICATE ON THE PLANS THE FOLLOWING PER | | | FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS | | | SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND | | | AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR | | | TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR | | | POURED CONCRETE SLABS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-08-05 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-08-05 |
Time |
17:19 |
Sent To |
|
|
| Notes |
|
|