Plan Review Details - Permit 08070537
Plan Review Stops For Permit 08070537
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-22 Cont ID  
Sent By mjacobs Date 2008-08-22 Time 16:52 Rev Time 0.00
Received By mjacobs Date 2008-08-22 Time 16:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By mjacobs Date 2008-08-04 Time 15:13 Rev Time 0.00
Received By mjacobs Date 2008-08-04 Time 14:00 Sent To  
Notes
2008-08-04 15:13:46 
 BUILDING PLAN REVIEW
 PERMIT: 08070537
 ADD: 1701 S. FLAGLER DR. #702
 CONT: CAMERON H. FOCKLER
 TEL: (561)748-8818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-4-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)SUBMIT AN ELEVATION FRAMING DETAIL FOR THE NEW
 SOFFITS INDICATING THE ATTACHMENT AND STUD SPACING
 DETAIL. THIS IS A TYPE 1 CONSTRUCTION BUILDING;
 THEREFORE, ONLY FIRE- RETARDANT-TREATED WOOD IS
 PERMITTED IN THE NON BEARING WALLS FBC 603.1 (1). SEE
 DETAIL A.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-22 Cont ID  
Sent By btrobaug Date 2008-08-22 Time 12:06 Rev Time 0.00
Received By btrobaug Date 2008-08-22 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-07-30 Time 13:42 Rev Time 0.00
Received By btrobaug Date 2008-07-30 Time 11:04 Sent To  
Notes
2008-07-30 13:42:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). LOCATE TO SHOW COMPLIANCE
 ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-22 Cont ID  
Sent By mwennerg Date 2008-08-22 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2008-08-22 Time 13:39 Sent To  
Notes
2008-08-22 13:39:43STAMPED NEW SHEET A1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-08-01 Cont ID  
Sent By mwennerg Date 2008-08-01 Time 15:13 Rev Time 0.00
Received By mwennerg Date 2008-08-01 Time 15:12 Sent To  
Notes
2008-08-01 15:15:351) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 09:17 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 09:17 Sent To  
Notes
2008-08-15 16:03:33TO "BOB"#9
2008-08-13 09:18:15WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-08 Cont ID  
Sent By lmartine Date 2008-08-05 Time 16:04 Rev Time 0.00
Received By lmartine Date 2008-07-21 Time 09:01 Sent To  
Notes
2008-07-28 08:52:58TO "BOB"#8
2008-07-21 09:02:02WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-18 Cont ID  
Sent By mperson Date 2008-08-18 Time 16:35 Rev Time 0.00
Received By mperson Date 2008-08-18 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By mperson Date 2008-07-29 Time 13:36 Rev Time 0.00
Received By mperson Date 2008-07-29 Time 13:36 Sent To  
Notes
2008-07-29 13:43:09PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. CLEARLY INDICATE ON THE PLANS THE FOLLOWING PER
 FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By bpowell Date 2008-08-05 Time 17:19 Rev Time 0.00
Received By bpowell Date 2008-08-05 Time 17:19 Sent To  
Notes
***NONE***