Plan Review Details - Permit 08070485
Plan Review Stops For Permit 08070485
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By mjacobs Date 2008-09-09 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2008-09-08 Time 14:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By mjacobs Date 2008-08-04 Time 11:29 Rev Time  
Received By mjacobs Date 2008-08-01 Time 16:04 Sent To PC
Notes
2008-08-04 11:29:51BUILDING PLAN REVIEW
 PERMIT: 08070485
 ADD: 120 S. DIXIE HWY SUITE 103-105
 CONT: WILK CONSTRUCTION
 TEL: (561)876-2724
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)SHEET A-1.01 DOOR #101; FBC 11-4.13.6 MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE 25. THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES
 SHALL BE LEVEL AND CLEAR.
  
 6)THE LOUVERS IN THE EXTERIOR WALLS SHALL BE DESIGNED
 TO RESIST WIND -DRIVEN RAIN WHERE THE RESULTS OF
 TESTING INDICATE THAT WATER DID NOT PENETRATE CONTROL
 JOINTS IN THE EXTERIOR WALL ENVELOPE, JOINTS AT THE
 PERIMETER OF OPENINGS OR INTERSECTIONS OF TERMINATIONS
 WITH DISSIMILAR MATERIALS. FBC 1403.2. LOUVERS
 PROTECTING INTAKE AND EXHAUST VENTILATION DUCTS NOT
 ASSUMED TO BE OPEN THAT ARE LOCATED WITHIN 30 FEET OF
 GRADE SHALL MEET REQUIREMENTS OF LARGE MISSILE TEST.
 1609.1.4 (5).
  
 7)PROVIDE THE PRODUCT APPROVALS FOR (A) LOUVERS (B)
 LINTEL. THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL. 106.3*
  
 8)SHEET A-1.01 AN UNOBSTRUCTED TURNING SPACE
 COMPLYING WITH SECTION 11-4.2.3 SHALL BE PROVIDED
 WITHIN AN ACCESSIBLE TOILET ROOM. THE CLEAR FLOOR SPACE
 AT FIXTURES AND CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING SPACE MAY OVERLAP.THE CLEAR FLOOR SPACE SHALL
 EXTEND A MAXIMUM OF 19 INCHES UNDERNEATH THE SINK (SEE
 FIG 32). SEE ROOM #110
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-29 Cont ID  
Sent By btrobaug Date 2008-08-29 Time 10:27 Rev Time 0.00
Received By btrobaug Date 2008-08-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 14:46 Rev Time 0.00
Received By btrobaug Date 2008-07-22 Time 12:16 Sent To  
Notes
2008-07-22 13:16:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FIXTURE TYPES ON SHEET E-2 DO NOT MATCH THE THE
 TYPES ON SHEET A-2.01, THE NUBMER AND TYPES ON SHEET
 E-0 AND NONE OF THESE SHEETS MATCH THE THE NUMBER OR
 WATTAGE ON THE INPUT DATA REPORT. PLEASE CORRELATE ALL
 INFORMATION.
  
 2} THE AIR HANDLER AND COMPRESSER OCP IN THE PANEL
 SCHEDULES DO NOT CORRELATE WITH THE MANUFACTURERS
 SRECOMENDATION ON SHEET M-2. VERIFY THE OCP WITH THE
 MANUFACTURER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-04 Cont ID  
Sent By mwennerg Date 2008-09-04 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2008-09-04 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By mwennerg Date 2008-08-01 Time 13:05 Rev Time 0.00
Received By mwennerg Date 2008-08-01 Time 13:05 Sent To  
Notes
2008-08-01 13:20:35***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. OK ON
 ELECTRICAL SHEETS. PLEASE ADD TO CODE ANALYSIS ON SHEET
 A-0.00.
  
 2) FIRE PROTECTION SYSTEMS ON SHEET A-0.00 INDICATES A
 FIRE ALARM. PLEASE INDICATE WHAT FIRE ALARM EQUIPMENT
 AND SHOW EQUIPMENT LAYOUT. SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR FIRE ALARM REMODEL IF APPLICABLE.
 IF NOT PART OF THIS PROJECT, PLEASE REMOVE REFERENCE
 FROM PLANS.
  
 3) IS PROJECT PROTECTED BY AUTOMATIC FIRE SPRINKLER
 SYSTEM? IF SO, PROVIDE SPRINKLER HEAD LAYOUT. SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 REMODEL.
  
 4) PLANS INDICATE A TOTAL OF (3) EXITS. EACH EXIT
 APPEARS TO BE SEPARATED WITH NO COMMON PATH OF TRAVEL.
 PLEASE MAKE CORRECTION.
  
 5) PLANS SUGGEST EXISTING CONDITIONS THAT WILL REMAIN
 IN UNIT #105, BUT SCOPE OF WORK INCLUDES THIS UNIT. IF
 PART OF THE SCOPE OF THIS WORK, PLEASE CLARIFY AND SHOW
 NEW OR EXISTING EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 16:51 Sent To  
Notes
2008-11-18 08:20:58TO "BOB"#8
2008-11-17 16:52:14WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 15:40 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 15:40 Sent To  
Notes
2008-08-26 16:29:338-26-08 TO "BOB" BD #11.
2008-08-26 15:41:02WAITING FOR "BOB" BD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-08-04 Time   Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 09:09 Sent To  
Notes
2008-07-17 09:10:49TO "BOB"#17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 15:50 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 15:49 Sent To PC
Notes
2008-12-06 15:50:03REVISED M-1, M-2, M-3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 09:47 Rev Time 1.00
Received By tgordon Date 2008-08-28 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By tgordon Date 2008-07-17 Time 11:01 Rev Time 0.45
Received By tgordon Date 2008-07-17 Time 11:01 Sent To  
Notes
2008-07-17 11:08:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR 12"X12"
 LOUVERS (RUSKIN), SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 14:29 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 14:28 Sent To  
Notes
2008-11-25 14:29:23REVISION OK -- SHT P2

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-03 Cont ID  
Sent By mperson Date 2008-09-03 Time 09:03 Rev Time 0.00
Received By mperson Date 2008-09-03 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By mperson Date 2008-07-17 Time 15:27 Rev Time 0.00
Received By mperson Date 2008-07-17 Time 15:27 Sent To  
Notes
2008-07-17 16:16:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-3.01 DETAIL #3 LOUNGE SINK: PLEASE ADD THE
 FOLLOWING FOR THE ADA COMPLIANT LOUNGE SINK ON THE
 ELEVATION DETAIL PER FBC- CHAPTER 11, SECTIONS.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEET A-3.01 DETAIL #9 NEW ADA COMPLIANT LAVATORY
 DETAIL FOR EXISTING RESTROOM #110: PLEASE ADD THE
 FOLLOWING FOR THE ADA COMPLIANT LAVATORY ON THE
 ELEVATION DETAIL REQUIRED PER FBC- CHAPTER 11,
 SECTIONS.
  
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 3. SHEET P-1 PLUMBING PLAN PLEASE ADD THE FOLLOWING
 PER FBC-PLUMBING SECTIONS.
  
 A} THE UNDERGROUND POTABLE HOT AND COLD WATER IS
 MISSING TO THE SHAMPOO STATIONS. PER SECTION 601.1
 SCOPE.
  
 B} THE REQUIRED TWO-WAY CLEANOUTS AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER ARE MISSING FROM
 THE SANITARY PIPES IN SUITE #103 & #104. PER FBC-
 PLUMBING SECTION 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
  
 4. SHEET P-2 SANITARY RISER DIAGRAM: THE REQUIRED
 TWO-WAY CLEANOUTS AT THE JUNCTION OF THE BUILDING DRAIN
 AND BUILDING SEWER ARE MISSING FROM THE SANITARY PIPES
 IN SUITE #103 AND #104. PER FBC- PLUMBING SECTION
 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-28 Cont ID  
Sent By mflis Date 2008-07-28 Time 10:47 Rev Time 0.00
Received By mflis Date 2008-07-28 Time 10:47 Sent To  
Notes
2008-07-28 10:48:16ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR BUILDOUT ONLY
  
 MATT FLIS - 822-1445