Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-16 Cont ID  
Sent By btrobaug Date 2008-07-16 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2008-07-16 Time 09:01 Sent To I
Notes
2008-07-16 11:57:32 
  
  
  
 PROVISO
  
 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 LOCATE DETECTORS ON THE PLAN IF APPLICABLE. NOTE: MAY
 BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 SUBMIT A PANEL SCHEDULE PRIOR TO THE ROUGH INSPECTION
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-16 Cont ID  
Sent By btrobaug Date 2008-07-16 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2008-07-16 Time 09:01 Sent To PC
Notes
***NONE***