Plan Review Details - Permit 08070391
Plan Review Stops For Permit 08070391
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-08-21 Cont ID  
Sent By jwitmer Date 2008-07-31 Time 16:31 Rev Time 2.22
Received By jwitmer Date 2008-07-31 Time 16:31 Sent To  
Notes
2008-07-31 16:44:44BUILDING PLAN REVIEW
 PERMIT:08070391 "STRUCTURE ONLY"
 ADD: 1760 PALM BEACH LAKES BLVD.
 CONT: RYAN COMPANIES
 TEL: (813)352-0254
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
  
 ACTION: REVIEWEDOK TO ISSUE
  
 1) BUILDING PROVISO:105.13. SPECIAL STRUCTURAL
 PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE STRUCTURE
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 2) BUILDING PROVISO: FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) BUILDING PROVISO: 105.13. SPECIAL STRUCTURE PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE STRUCTURE
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 4) BUILDING PROVISO 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-29 Cont ID  
Sent By dpalmer Date 2008-07-29 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2008-07-29 Time 11:24 Sent To  
Notes
2008-07-29 11:25:25** REDLINED PLANS **
  
 PLANS ARE STAMPED AND REDLINED FOR CONDUIT INSTALLATION
 ON SITE, UNDERGROUND AND IN BUILDING. THIS ALSO
 INCLUDES COMPLETE GROUNDING ELECTRODE SYSTEM FOR MAIN
 ELECTRICAL SERVICE AS WELL AS GROUNDING ELECTRODE
 SYSTEM TO THE ELECTRICAL ROOMS.
 CONDUITS AND GROUNDING ELECTRODE SYSTEM ONLY.
  
 ** ELECTRICAL PERMIT REQUIRED.
  
  
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-07-30 Cont ID  
Sent By rchokshi Date 2008-07-30 Time 13:14 Rev Time 0.00
Received By rchokshi Date 2008-07-30 Time 13:14 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By rchokshi Date 2008-07-17 Time 15:36 Rev Time 0.00
Received By RCHOKSHI Date 2008-07-17 Time 11:24 Sent To  
Notes
2008-07-17 15:36:30FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OFPOLLUTION PREVENTION . PLEASE
 SHOW ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE,
 & TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE TOO.HEIGHT OF FENCE SHOULD BE
 HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES. TURBIDITY
 MUST BE AROUND ALL CATCH BASINS AND ALL OTHER OUT FALLS
 DURING CONSTRUCTION PHASE & DEMOLITION PHASE.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS TO 1000
 45TH STREET FOR THEIR APPROVAL BEFORE WE APPROVE.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-07-31 Cont ID  
Sent By mwennerg Date 2008-07-31 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2008-07-31 Time 10:42 Sent To  
Notes
2008-07-31 10:49:19***PROVISO***
  
 STRUCTURAL PERMIT ONLY
  
 IN ADDITION TO THIS PERMIT APPLICATION, THE FOLLOWING
 COMMENTS ARE REQUIRED TO BE ADDRESSED AT THE TIME OF
 APPLICATION FOR BUILDING PERMIT.
  
 1) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY
 WITH NFPA 1, 2003 CHAPTER-18.
  
 2) NEW FIRE HYDRANTS SHALL BE FULLY OPERATIONAL PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 3) FIRE LINES SHALL NOT PASS BENEATH ANY PART OF THE
 STRUCTURE, PAD, FOUNDATION ETC.
  
 4) PROPER CLEARANCES SHALL BE MAINTAINED AROUND FIRE
 HYDRANT ASSEMBLIES. CLEARANCES OF 7'-6" TO FRONT AND
 SIDES AND 4' TO REAR ARE REQUIRED AT ALL TIMES. ALL
 FIRE PROTECTION EQUIPMENT SHALL REMAIN CLEAR OF ANY
 OBSTRUCTIONS THAT WOULD IMPACT ACCESS OR USE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-31 Cont ID  
Sent By jwitmer Date 2008-07-31 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2008-07-15 Time 11:40 Sent To  
Notes
2008-07-15 13:14:06TO "COMM" BD#25/PLANS ON RACK/1 ROLL

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-07-29 Cont ID  
Sent By kstevens Date 2008-07-29 Time 10:40 Rev Time 0.00
Received By kstevens Date 2008-07-29 Time 09:52 Sent To  
Notes
2008-07-29 10:41:12UNDERGROUND/SLAB WORK ONLY THIS PERMIT

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-31 Cont ID  
Sent By jroach Date 2008-07-31 Time 08:01 Rev Time 0.00
Received By jroach Date 2008-07-31 Time 08:00 Sent To  
Notes
2008-07-31 08:01:03STRUCTURAL REVIEW ONLY.....THE FOLLOWING PROVISOS
 CORRESPOND WITH THE MAIN BUILDING PERMIT.
  
 ***PROVISOS***
  
 1) ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT, AND SHALL CONFORM TO THE REGULATIONS OF THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT.
  
 2) ALL REMOVAL AND RELOCATION OF TREES SHALL BE DONE IN
 ACCORDANCE WITH APPROVED TREE ALTERATION PERMIT.
  
 3) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING SHALL OCCUR:
  
 A) THE SHOPPING CART CONTAINMENT SYSTEM SHALL BE
 INSTALLED.
  
 B) THE CITY OF WEST PALM BEACH CRIME PREVENTION OFFICER
 SHALL BE PROVIDED WITH A WALK-THROUGH OF THE FACILITY
 AND SHALL APPROVE THE SECURITY PLAN, INCLUDING THE
 PLACEMENT OF CAMERAS, SECURITY PERSONNEL, ETC.
  
 C) THE POLICE SUBSTATIONS SHALL BE PROVIDED WITH
 ELECTRIC, PHONE, AND DATA CONNECTIONS, AS WELL AS
 DESK/WORK SPACE, AND A MONITOR CONNECTED TO THE
 SECURITY SYSTEM.
  
 D) THREE (3) PARKING SPACES, AS DESIGNED ON THE
 APPROVED PLAN, SHALL BE DESIGNATED AS "POLICE ONLY"
 SPACES.
  
 E) THE ENTIRE PROPERTY SHALL BE REPLATTED BY SUBMITTING
 AN APPLICATION TO THE CITY'S PLANNING AND ZONING
 DEPARTMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
2008-07-22 16:42:23REVIEW CANNOT BE COMLETED UNTIL INFORMATION HAS BEEN
 PROVIDED REGARDING POTENTIAL DEED RESTRICTION FROM 1975
 REGARDING BUILDING SETBACK OFF OF PALM BEACH LAKES
 BOULEVARD.STAFF HAS CONTACTED ED STACKER, ATTORNEY
 FOR TARGET, REGARDING THIS MATTER.HE HAS FORWARDED IT
 ON TO TARGET TO BE ADDRESSED.ZONING WILL PASS THE
 REVIEW UPON RECEIPT OF INFORMATION THAT THE DEED
 RESTRICTION HAS BEEN REMOVED.IF IT HAS NOT BEEN
 ADDRESSED PRIOR TO COMPLETION OF REVIEW BY THE OTHER
 TRADES, ZONING WILL FAIL THIS REVIEW AND PASS IT UPON
 RESUBMITTAL.
  
 CONTACT JOHN ROACH, SENIOR PLANNER, FOR ADDITIONAL
 INFORMATION AND/OR QUESTIONS REGARDING THIS MATTER.
 (561) 822-1435.