Plan Review Details - Permit 08070320
Plan Review Stops For Permit 08070320
Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-08-21 Cont ID  
Sent By rbrown Date 2009-08-21 Time 11:05 Rev Time 0.00
Received By rbrown Date 2009-08-21 Time 11:05 Sent To  
Notes
2009-08-21 11:06:57SUBMITTAL ON 7/09/09 FOR STRUCTURAL INTEGRITY OF
 PACKAGE UNITS SUBJECT TO WIND LOADS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2009-06-25 Cont ID  
Sent By rbrown Date 2009-06-25 Time 19:52 Rev Time 0.00
Received By rbrown Date 2009-06-25 Time 19:52 Sent To  
Notes
2009-06-25 20:16:41BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 SUBMITTAL ON 6/22/09 FOR STRUCTURAL WIND LOAD INTEGRITY
 OF PACKAGE UNITS.
  
 1) FBCM 301.13 MECHANICAL UNITS EXPOSED TO WIND. FOR
 THE SANYO OUTDOOR UNITS THE FIFTH PAGE (UNNUMBERED) OF
 THE CALCULATION REPORT ONLY ADDRESSES AND SPECIFIES THE
 SCREWS REQUIRED FOR ATTACHMENT OF THE UNIT TO IT'S
 "BOTTOM PLATE ASSEMBLY". THE REPORT GOES ON TO SHOW
 EXPLODED VIEWS OF THE UNIT CONSTRUCTION BUT THE
 CALCULATIONS DO NOT ADDRESS THE REQUIREMENT TO SHOW
 THAT THE EXTERNAL (VERTICAL AND HORIZONTAL) PANELS OF
 THE UNIT WILL RETAIN THEIR INTEGRITY AND REMAIN
 ATTACHED TO THE UNIT WHEN SUBJECT TO THE WIND PRESSURES
 RESULTING FROM 140 MPH WIND SPEED (3 SECOND GUST).
 THERE ARE NO CALCULATIONS FOR THE SCREWS/FASTENERS
 HOLDING THE PANELS TOGETHER, AND THERE ARE NO
 CALCULATIONS FOR THE PANELS THEMSELVES (SHEAR AT HOLES
 BASED ON HOLE SIZE AND EDGE DISTANCE , ETC.). AS SUCH
 THE SUBMITTED CALCULATIONS DO NOT ADDRESS THE 12/17/08
 PROVISO GIVEN BY RON REGUEIRO, MECHANICAL PLANS
 EXAMINER II. THE MECHANICAL CODE SECTION REQUIRES THAT
 THE APPLIANCE ITSELF BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES. SUBMIT MANUFACTURER'S TEST
 DATA OR STRUCTURAL CALCULATIONS TO SHOW THAT THE
 PACKAGE UNIT HAS BEEN TESTED OR DESIGNED FOR THE WIND
 PRESSURES RESULTING FROM 140 MPH WIND SPEED (3 SECOND
 GUST). THE PROVISO GIVEN BY THE MECHANICAL PLANS
 EXAMINER ON 12/17/08 STATED THIS SAME REQUIREMENT,
 QUOTE: "PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING
 OUTDOOR APPLIANCES ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13."
  
 2) 471.025 F.S. AND 61G15-23.002 FL. ADMINISTRATIVE
 CODE. ONLY THE COVER PAGE OF BOTH CALCULATION REPORTS
 IS SIGNED AND SEALED. WHEN SUBMITTING CALCULATION
 REPORTS THE ENGINEER MUST EITHER SIGN AND SEAL EACH
 SHEET OR PROVIDE A SIGNED AND SEALED CONTENTS PAGE
 WHICH REFERENCES THE SHEET NUMBER OF EACH SHEET IN THE
 CALCULATION REPORT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2009-06-19 Cont ID  
Sent By shill Date 2009-06-19 Time 11:43 Rev Time 0.00
Received By shill Date 2009-06-19 Time 11:43 Sent To  
Notes
2009-06-19 11:44:18CAVITY SHAFT WALL SUBMITTAL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2009-06-10 Cont ID  
Sent By shill Date 2009-06-10 Time 13:05 Rev Time 0.00
Received By shill Date 2009-06-10 Time 13:05 Sent To  
Notes
2009-06-10 13:06:13REVISION A001CR2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-05-14 Cont ID  
Sent By rbrown Date 2009-05-14 Time 20:34 Rev Time 0.00
Received By rbrown Date 2009-05-14 Time 20:34 Sent To  
Notes
2009-05-14 20:35:42SUBMITTAL ON 4/27/09 FOR FIRESTOPPING RATED ASSEMBLIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2009-05-14 Cont ID  
Sent By rbrown Date 2009-05-14 Time 19:53 Rev Time 0.00
Received By rbrown Date 2009-05-14 Time 19:53 Sent To  
Notes
2009-05-14 20:09:33BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 SUBMITTAL ON 4/27/09 FOR TIE DOWN CABLES ON PACKAGE
 UNIT.
  
 1) FBCM 301.13 MECHANICAL UNITS EXPOSED TO WIND. ONLY
 TIE DOWN CABLES ARE BEING PROPOSED. THAT DOES NOT
 ADDRESS THE 12/17/08 PROVISO GIVEN BY RON REGUEIRO,
 MECHANICAL PLANS EXAMINER II. THE MECHANICAL CODE
 SECTION REQUIRES THAT THE APPLIANCE ITSELF BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES. SUBMIT
 MANUFACTURER'S TEST DATA OR STRUCTURAL CALCULATIONS TO
 SHOW THAT THE PACKAGE UNIT HAS BEEN TESTED OR DESIGNED
 FOR THE WIND PRESSURES RESULTING FROM 140 MPH WIND
 SPEED (3 SECOND GUST). THE PROVISO GIVEN BY THE
 MECHANICAL PLANS EXAMINER ON 12/17/08 STATED THIS SAME
 REQUIREMENT, QUOTE: "PROVIDE MANUFACTURER'S SUBMITTAL
 DATA SHOWING OUTDOOR APPLIANCES ARE DESIGNED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13."
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-04-02 Cont ID  
Sent By shill Date 2009-04-02 Time 18:03 Rev Time 0.00
Received By shill Date 2009-04-02 Time 18:03 Sent To  
Notes
2009-04-02 18:04:36REVISION
 A101CR5, A103CR4,106CR3, A118CR5, A119CR5, A120CR5,
 A901CR5
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-04-02 Cont ID  
Sent By shill Date 2009-04-02 Time 09:01 Rev Time 0.00
Received By shill Date 2009-04-02 Time 09:01 Sent To  
Notes
2009-04-02 09:19:17REVISION, CHANGE ROOF SYSTEM (STANDING SEAM) ON SOME
 PORTIONS OF PROJECT
  
 SUBMITTALS; ROOF SHOPS AND LIGHT POLE CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-03-30 Cont ID  
Sent By shill Date 2009-03-30 Time 10:51 Rev Time 0.00
Received By shill Date 2009-03-30 Time 10:50 Sent To  
Notes
2009-03-30 10:52:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STA
  
 1. PLEASE HAVE ALL SUBMITTALS/SHOP DRAWINGS REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL. FAC61G15-23,
 FAC61G1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-03-09 Cont ID  
Sent By shill Date 2009-03-09 Time 18:35 Rev Time 0.00
Received By shill Date 2009-03-09 Time 18:35 Sent To  
Notes
2009-03-09 18:40:21REVISION ADDRESSING BUILDING AND ELECTRIC
 PROVISOS/REDLINES:
  
 A101CR4, A118CR4, A120CR4, A123CR1, A901CR4
  
 SUBJECT TO FIRE & ELECTRIC REVIEWS
  
 RECEIVED SHOP DRAWING REVIEW LETTER FROM DOR (PROVISO
 ITEM), 1 LETTER FILED, 1 STAMPED & RETURNED TO CONTR
 WITH CALCS (STAMPED PREVIOUS REVIEW)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-02-25 Cont ID  
Sent By shill Date 2009-02-25 Time 17:12 Rev Time 0.00
Received By shill Date 2009-02-25 Time 17:12 Sent To  
Notes
2009-02-25 17:17:47REVISION DATED 2/6/9 SHEETS A101CR3, A103CR3, A106CR2,
 A110CR2, A113CR3, A118CR3, A119CR3, A120CR3, A901CR3
  
 **PROVISO**
 ALL SUBMITTALS & DELEGATED ENGINEERING TO BE REVIEWED
 BY DOR; SUBMIT LETTER
 ** ISSUED AT CONTRACTOR???S RISK
 PLAN REDLINED; 1 HR CORRIDOR REQUIRED AT EGRESS STAIR
 SUBMIT REVISION (CHANGE WALL DESIGNATION AT THIS AREA
 TO REFLECT
 CONSTRUCTION OF 1 HR WALLS, PER ARCHITECT)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-08 Cont ID  
Sent By shill Date 2008-12-08 Time 16:00 Rev Time 0.00
Received By shill Date 2008-12-08 Time 16:00 Sent To  
Notes
2008-12-08 16:01:08**PROVISO** - REVISE AS FOLLOWS, PRIOR TO INSTALLATION
  
 WBCM SUBMITTAL #8, CALCULATIONS CM MANUFACTURING,
 PLEASE ADDRESS:
  
 A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS
 CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM.
  
 B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE
 FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD,
 THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE
 JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS
 TO HAVE EXPOSURE C CONDITIONS, FBC1609.4.
  
 C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT
 PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006
 REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH
 INTERNATIONAL BUILDING CODE 2003. FOR FUTURE
 SUBMITTALS, PLEASE REVISE.
  
 D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW
 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD
 ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING
 STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY
 USE OF STRESS INCREASE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-11-21 Cont ID  
Sent By shill Date 2008-11-21 Time 11:33 Rev Time 0.00
Received By shill Date 2008-11-20 Time 07:58 Sent To  
Notes
2008-11-21 11:40:45SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-79. ADDRESSED.
  
 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT
 VENTS. PROVIDE CALCULATIONS ON THE PLAN AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 THE REQUEST FOR CONSIDERATION UNDER ALTERNATE MATERIALS
 AND METHODS HAS BEEN FORWARDED TO ROBERT BROWN FOR
 REVIEW. THIS REVIEW WILL REMAIN IN FAILED STATUS UNTIL
 HIS DECISION. IF THIS REQUEST IS DENIED, THIS REVIEW
 WILL BE PASSED WITH PROVISO TO REVISE DESIGN TO INCLUDE
 THE REQUIRED SMOKE AND HEAT VENTS. IF APPROVED, A
 PASSED STATUS WILL BE ENTERED FOR THIS REVIEW.
  
 81-87. ADDRESSED.
  
 88. **PROVISO** - REVISE AS FOLLOWS, PRIOR TO
 INSTALLATION
  
 WBCM SUBMITTAL #8, CALCULATIONS CM MANUFACTURING,
 PLEASE ADDRESS:
  
 A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS
 CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM.
  
 B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE
 FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD,
 THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE
 JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS
 TO HAVE EXPOSURE C CONDITIONS, FBC1609.4.
  
 C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT
 PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006
 REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH
 INTERNATIONAL BUILDING CODE 2003. FOR FUTURE
 SUBMITTALS, PLEASE REVISE.
  
 D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW
 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD
 ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING
 STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY
 USE OF STRESS INCREASE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By shill Date 2008-11-06 Time 12:22 Rev Time 0.00
Received By shill Date 2008-10-29 Time 10:56 Sent To  
Notes
2008-11-06 12:22:30SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-29. ADDRESSED.
  
 30. ADDRESSED.
  
 31C. PAGE 4 OF THE CALCULATIONS, OTHER SHEETS, PLANS,
 REFER TO 2004 FLORIDA STATE BUILDING CODE; PLEASE
 REVISE TO GOVERNING CODE WHICH IS FLORIDA BUILDING CODE
 2004 WITH 2007 REVISIONS/SUPPLEMENTS.
  
 2ND REVIEW, PLANS AND CALCS STILL STATE 2004 FLORIDA
 STATE BUILDING CODE; THIS SHOULD STATE FLORIDA BUILDING
 CODE OR FBC 2004 (WITH 2007 REVISIONS/SUPPLEMENTS).
  
 E. ALL SIGNED AND SEALED SHEETS ARE TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
 2ND REVIEW, A NUMBER WAS INCLUDED BUT THIS NUMBER WAS
 ISSUED TO VP CONSOLIDATED HOLDINGS, INC. THE COMPANY ON
 THE PLANS IS VP BUILDINGS, INC. I WAS UNABLE TO FIND A
 DBA, AND HAVE CONTACTED FBPE TO DETERMINE WHETHER OR
 NOT THIS IS ACCEPTABLE. ALSO, VP CONSOLIDATED HOLDINGS,
 INC. HAVE FILED A WITHDRAWAL STATING THAT THEY WILL NO
 LONGER DO BUSINESS IN FLORIDA. HAS ADDITIONAL PAPERWORK
 BEEN FILED WHICH I AM UNABLE TO LOCATE ON THE INTERNET?
 COMPLIANCE WITH FS471.023(1) IS NOT CLEAR.
 HTTP://WWW.SUNBIZ.ORG/PDF/15259987.PDF
  
 32?39. ADDRESSED.
  
 40. (INFORMATIONAL) THE 3 RING BINDER ENTITLED
 TECHNICAL SPECIFICATIONS WILL BE INCLUDED WITH THE
 RECORD SET WITH THE PROVISO IN ACCORDANCE WITH FBC2004
 AND PLAN. NO ACTION REQUIRED.
  
 41-43. ADDRESSED.
  
 44. SEE FBC TABLE 1016.1, CORRIDORS 203 AND 205 FROM
 VISITOR'S GALLERY TO STAIRS TO HAVE 1 HOUR FIRE
 RESISTIVE RATING AND THEREFORE DOORS 203 1, 204 1, 205
 1, 206 1, 200 1, TO BE RATED IN ACCORDANCE WITH
 FBC715.3.
  
 2ND REVIEW, AS DISCUSSED WITH ENGINEER, THIS ITEM WILL
 BE ADDRESSED IN RESUBMITTAL. NOTE THAT SOME DOORS FROM
 FIRST REVIEW WERE REMOVED, SO THERE IS ONLY ONE
 CORRIDOR FROM MEZZANINE LEVEL. AS DISCUSSED, THE
 CORRIDOR STARTS AT THE DOOR (MEANS OF EGRESS STAIR
 HALLWAY TO VIEWING GALLERY) AND TERMINATES AT THE EXIT,
 GROUND FLOOR (CORRIDOR MUST TERMINATE AT AN EXIT, WHICH
 IN THIS CASE IS THE EXIT DISCHARGE), SO ALTHOUGH THIS
 IS NOT A RATED EXIT STAIR, THE STAIR IS CONTAINED IN A
 1 HOUR CORRIDOR. PLEASE CONTACT ME IF YOU WISH TO
 DISCUSS.
  
 45-54. ADDRESSED.
  
 55. FBC13-101.1, ENERGY CALCS REQUIRED FOR BOTH THE
 MAIN BUILDING AND FOR THE SCALE HOUSE.
  
 2ND REVIEW, ENERGY CALCS SUBMITTED. FOR THE MAIN
 BUILDING, 2 DOORS ARE SHOWN. ISN'T THE WALL BETWEEN THE
 ADMIN AREA AND PROCESSING TO BE TREATED AS A WALL,
 INCLUDED IN THE INPUT DATA REPORT, AND THE DOORS NOTED?
 I WAS UNABLE TO LOCATE MEZZANINE WINDOWS IN THE INPUT
 DATA REPORT. THE SLAB IS NOTED AS 6.38 R VALUE; PLEASE
 CLARIFY. THE ROOF ON THE ENERGY CALC IS SHOWN AS 32.8 R
 VALUE, PLAN (SEE DETAIL 9 A110CR1) SPECIFIES R19 BATT.
 IF THE PEMB ROOF INCLUDES INSULATION, PLEASE PROVIDE
 THIS INFORMATION ON THE PLAN. NOTE THAT THE TYPED NAME
 AND LICENSE NUMBER OF THE ARCHITECT FOR CERTIFICATION
 BY THE ARCHITECT IS ACCEPTABLE ON THE ENERGY CALC IN
 LIEU OF SIGNATURE IF ALL INFORMATION IS INCLUDED ON THE
 PLAN FBC13-103.1.1.1. PLEASE CONFIRM INPUT DATA
 REQUIREMENTS AND REVISE AS NECESSARY. THIS LIST IS NOT
 BE COMPREHENSIVE; PLEASE CHECK ALL.
  
 56-58. ADDRESSED.
  
 59. SEE FBC1016.4, AIR MOVEMENT IN CORRIDORS. PLEASE
 REMOVE SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION
 AIR DUCTS FROM EXIT ACCESS CORRIDORS, SEE OTHER
 COMMENTS. PLEASE NOTE THAT THERE ARE TWO HALLS IN THE
 MEZZANINE WHICH SERVE AS CORRIDORS.
  
 2ND REVIEW, ONE DOOR WAS REMOVED, SO ONLY ONE CORRIDOR
 SERVING THE MEZZANINE REMAINS. PLEASE REVISE PLANS IN
 ACCORDANCE WITH FBC1016.4, SEE ALSO OTHER COMMENTS
 REGARDING 1 HOUR FIRE RATING REQUIRED.
  
 60-61. ADDRESSED.
  
 62. A114C, SPECIFY GUARD PICKET SPACING FBC1012.
  
 A114 WAS REVISED TO SPECIFY 4IN, BUT THIS IS TO RESIST
 A 4IN OBJECT (REQUIRES SPACING LESS THAN 4IN). THIS CAN
 BE A REDLINE ITEM IF REQUESTED.
  
 63. ADDRESSED.
  
 64. SEE 3 A007C, THE HANDRAIL IS NOT CONTINUOUS. A106C
 HANDRAIL EXTENSIONS AT BOTTOM IS NOT SHOWN. PLEASE
 PROVIDE DETAILS AND CORRELATE A SHEETS.
  
 2ND REVIEW, THE ELEVATION ON A106C DOES NOT SHOW THE
 EXTENSION REQUIRED, FBC11-4.9.4(2). AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR THE DISTANCE OF
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER, THE REMAINDER
 OF THE EXTENSION WILL BE HORIZONTAL, FBC FIGURE 19(D).
 SEE ALSO DETAIL 1 113, A A007 (BOTTOM). THE EXTENSIONS
 ARE SHOWN CORRECTLY IN OTHER DETAILS. PLEASE CHECK ALL.
  
 65-72. ADDRESSED.
  
 73. SHOW LOCATION OF STROBES, FBC11-4.28.1.
  
 2ND REVIEW, PLEASE ADD TO BATHROOM 108, TRUCKER?S
 BATHROOM. PLEASE CONFIRM THAT STROBES ARE SHOWN IN ALL
 LOCATIONS REQUIRED.
  
 74-76. ADDRESSED.
  
 77. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE
 BACKING FOR THE GRAB BARS (A111C) TO SHOW COMPLIANCE
 WITH FBC1607.7.1.1, FBC11-4.26.3. DETAIL STATES SCREWED
 TO STUD BUT DOES NOT SPECIFY SIZE OF SCREWS OR DISTANCE
 APART, DOES NOT SPECIFY A WIDTH FOR THE 22G SHEET METAL
 BACKING.
  
 2ND REVIEW, SPECIFICATION NOT PROVIDED. THIS CAN BE A
 PROVISO ITEM; PROVIDE SHOPS BEFORE INSTALLATION. THIS
 WILL BE REDLINED TO INCLUDE CONCENTRATED LOAD
 REQUIREMENT OF 250 PLF 1607.7.2.
  
 78-79. ADDRESSED.
  
 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT
 VENTS. PROVIDE CALCULATIONS ON THE PLAN AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 THE REQUEST FOR CONSIDERATION UNDER ALTERNATE MATERIALS
 AND METHODS HAS BEEN FORWARDED TO ROBERT BROWN FOR
 REVIEW.
  
 81-85. ADDRESSED.
  
 NEW COMMENTS (NEW SUBMITTALS) ? PLEASE NOTE THAT
 SUBMITTALS ARE NOT REQUIRED AT THIS TIME; THEY CAN BE
 SUBMITTED PRIOR TO INSTALLATION:
  
 86. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT
 BEFORE INSTALLATION)**
 ASSOCIATED ENGINEERING INCORPORATED IS TO HAVE A
 CERTIFICATE OF AUTHORIZATION, FS471 (WBCM SUBMITTAL
 #7). "AUTH # PENDING" WAS WRITTEN ON THE SHEETS
 PREPARED BY RONALD T. FOSS, P.E. FOR THE SORT
 ENCLOSURES, BUT THIS COMPANY NAME CANNOT BE USED UNTIL
 THE NUMBER IS ISSUED. THE WEBSITE DOES NOT INDICATE
 THAT AN APPLICATION IS PENDING. ARE THESE SHEETS
 REQUIRED AT THIS TIME? CAN THEY BE SUBMITTED AFTER A
 COFA HAS BEEN OBTAINED? A SET HAS BEEN RETAINED. PLEASE
 INFORM MR. FOSS OF THE REQUIREMENT TO OBTAIN THIS
 CERTIFICATE AND PLEASE HAVE HIM SEND AN EMAIL
 CONFIRMING HIS UNDERSTANDING.
  
 87. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT
 BEFORE INSTALLATION)**
 THE STRUCTURAL CALCULATIONS EQUIPMENT TIE-DOWN AND
 CONNECTIONS TO ROOF STRUCTURE (WBCM SUBMITTAL #12) DOES
 NOT INCLUDE A TITLE BLOCK, FAC61G15-23.002.
  
 88. **THIS SUBMITTAL CAN BE A PROVISO ITEM (SUBMIT
 BEFORE INSTALLATION)**
 WBCM SUBMITTAL #8, CALCULATIONS, PLEASE ADDRESS:
  
 A. ASCE7-05 REFERENCED; FBC2004 REQUIRES ASCE7-02. THIS
 CAN BE DONE WITH A LETTER OR CAN BE A PROVISO ITEM.
  
 B. SEE PAGE 22, EXPOSURE B USED WITH AN IMPORTANCE
 FACTOR OF .77. IF ACCEPTABLE TO THE DESIGNER OF RECORD,
 THE REDUCED IMPORTANCE FACTOR CAN BE USED BUT PROVIDE
 JUSTIFICATION FOR USE OF EXPOSURE B. THIS JOB APPEARS
 TO HAVE EXPOSURE C CONDITIONS, FBC1609.4.
  
 C. CALCS AND PLANS DO NOT NEED TO BE REVISED, BUT
 PLEASE NOTE THAT GOVERNING CODE IS FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS. CALCS REFER TO 2005 AND 2006
 REVISIONS AND SUPPLEMENTS, PLANS STATE COMPLIANCE WITH
 INTERNATIONAL BUILDING CODE 2003. FOR FUTURE
 SUBMITTALS, PLEASE REVISE.
  
 D. PAGE 21 NOTE STATES "LATERAL IMPACT DOES NOT ALLOW
 1/3 STRESS INCREASE AS ALLOWED FOR ASD WIND LOAD
 ANALYSIS" PLEASE PROVIDE MORE INFORMATION REGARDING
 STRESS INCREASE USED AND SEE FBC1605.3.1.1 AND CLARIFY
 USE OF STRESS INCREASE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By shill Date 2008-08-08 Time 15:08 Rev Time 0.00
Received By shill Date 2008-08-08 Time 15:08 Sent To  
Notes
2008-08-08 15:09:20****PRIVATE PROVIDER AUDIT****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. THE OWNER'S ACKNOWLEDGEMENT IS REQUIRED,
 FS553.791(4)(C).
  
 2.THE PRIVATE PROVIDER AFFIDAVIT IS TO IDENTIFY THE
 PLANS REVIEWED.THERE WAS A LOG PROVIDED, BUT THIS LOG
 IS NOT A PART OF THE AFFIDAVIT.THE AFFIDAVIT STATES
 "77 PAGES - ATTACHED" BUT NOTHING WAS ATTACHED; THE LOG
 WAS SUBMITTED SEPARATELY.THE LOG DOES NOT PROPERLY
 IDENTIFY EACH SHEET (SOME SHEETS HAVE DIFFERENT PAGE,
 FOR INSTANCE E106CR1, M104C, M014C) AND THE LOG DOES
 NOT IDENTIFY THE PLAN SHEETS BY DATE.NOT ALL SHEETS
 WERE STAMPED BY GFA (E106CR1, S101CR1).IT APPEARS
 THAT THE FIRE PROTECTION PLANS WERE NOT REVIEWED, OR
 THE C SHEETS (WHICH SHOW COMPLIANCE WITH FBC11 AND FBC5
 REQUIREMENTS), BUT THIS IS REQUIRED BY
 FBC*106.3.5.1.1(5), FS553.79 (2).NOTE THAT THE
 FOUNDATION PERMIT HAS NOT YET BEEN ISSUED, SO CANNOT BE
 USED TO SHOW CODE COMPLIANCE FOR THIS PLAN.
  
 3. FIRE SPRINKLER PLANS REQUIRED.AT A MINIMUM, A HEAD
 LAYOUT IS TO BE SUBMITTED, SEE FBC*106.3.5.1.1(5),
 FS553.79(2), LETTER FROM DCA (AVAILABLE UPON REQUEST).
  
 4. M SHEETS, THE SEAL IS TO INCLUDE THE DATE,
 FAC61G15-23.002, FS471.
  
 5. PLEASE NOTE THAT AN INDEX SHEET IS USEFUL WITH A
 PLAN OF THIS SIZE.THIS IS NOT A REQUIREMENT, BUT A
 SUGGESTION TO ASSIST WITH PLAN REVIEW.PROVIDING AN
 INDEX SHEET WILL ENABLE PLAN REVIEWERS TO OBTAIN
 NECESSARY INFORMATION MORE QUICKLY, WHICH WILL HELP TO
 EXPEDITE THE PLAN REVIEW PROCESS AND CUT DOWN ON PLAN
 REVIEW TIME.
  
 6. TWO 8 1/2 X 11 SHEETS WERE SUBMITTED.NEITHER ARE
 SEALED, ONE HAS THE DESIGNER'S TITLE BLOCK BUT IS
 LACKING SOME OF THE INFORMATION REQUIRED BY
 FAC61G15-23.002; THE OTHER IS NOT SEALED.PLEASE
 INCORPORATE THESE CHANGES INTO THE SIGNED AND SEALED
 PLAN.
  
 7. N/A.
  
 8. FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD,
 561-805-6666.A RESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT (STEEL STRUCTURE ONLY), DUE
 TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH KEN CONRAD (CHIEF BUILDING
 INSPECTOR - TEL: 561 805 6666), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.THIS MUST BE DONE PRIOR TO PERMIT
 ISSUANCE.THREE ORIGINAL SETS OF ALL DOCUMENTS ARE
 REQUIRED FOR PERMITTING.
  
 9. A901C, SECTION 507.2 UNLIMITED AREA NOT APPLICABLE
 TO THIS PROJECT AS THIS IS A MIXED USE, A3 AND S1
 DECLARED.FBC507.9 UNLIMITED AREA FOR A4 OCCUPANCY
 REQUIRES THAT THE FINISHED FLOOR BE 12? FROM GRADE
 LEVEL AND HAS OTHER REQUIREMENTS FOR EXITING.I WAS
 UNABLE TO LOCATE AN ALLOWANCE FOR A3 UNLIMITED AREA,
 TYPE IIB.SEE FBC TABLE 503 AND CHAPTER 5.
  
 10. SEE FBC302.3; THIS IS A MIXED OCCUPANCY BUILDING.
 PLEASE SEE FBC302.3.2 REGARDING BUILDING RATIOS.IT
 APPEARS THAT THIS BUILDING HAS BEEN DESIGNED IN
 ACCORDANCE WITH FBC302.3.1 BUT DOES NOT COMPLY WITH THE
 MORE STRINGENT REQUIREMENT OF A3, TYPE IIB.SEE OTHER
 COMMENTS.
  
 11. IF AREA MODIFICATIONS ARE USED FOR SPRINKLERS OR
 OPEN AREA, PLEASE INCLUDE ALL CALCULATIONS ON THE PLAN.
 FBC506.
  
 12. A901C STATES THAT THE MEZZANINE COMPLIES WITH
 FBC505.PLEASE SHOW COMPLIANCE BY STATING THE TOTAL
 SQUARE FOOT AREA OF THE MEZZANINE, FBC505.2.
  
 13. A901C, S1 AND A3 DECLARED, EMPLOYEE BREAK ROOM
 SHOWN AS ACCESSORY, BUT THE ADMINISTRATION (BUSINESS)
 AREAS, FIRST FLOOR AND MEZZANINE, WERE NOT ADDRESSED.
 DECLARE TOTAL SF AREA FOR ADMINISTRATION AND SHOW
 COMPLIANCE WITH FBC302.FIRE RESISTIVE RATED
 CONSTRUCTION MAY BE REQUIRED BETWEEN THE B AND S AND B,
 S AND A OCCUPANCIES (MEZZANINE).
  
 14. A901C, DECLARE SQUARE FOOT AREA FOR THE ASSEMBLY
 AND S1 OCCUPANCIES, ACCESSORY BREAK ROOM, FBC1004,
 FBC302.ALSO SEE OTHER COMMENT; DECLARE SF AREA FOR
 THE BUSINESS (ADMINISTRATION) AREA SHOWN ON THE FIRST
 FLOOR AS WELL AS THE OFFICE IN THE MEZZANINE.IT IS
 NOT CLEAR IF THIS IS ACCESSORY OR INCIDENTAL OR MIXED
 OCCUPANCY, FBC302.
  
 15. IS THE LUBE & OIL ROOM USED AS A REPAIR GARAGE,
 FBC406.6, MAINTENANCE OR REPAIR OF AUTOMOTIVE OR
 SIMILAR EQUIPMENT?SHOW COMPLIANCE ON THE PLAN WITH
 SPECIAL REQUIREMENTS, IF ANY.
  
 16. DO ANY OF THE AREAS INCLUDE HIGH PILED OR RACK
 STORAGE OF COMBUSTIBLES, FBC413.3?SHOW COMPLIANCE ON
 THE PLAN FOR ANY SPECIAL REQUIREMENTS, IF ANY.
 17. THERE ARE SEVERAL STORAGE AREAS SHOWN ON THE PLAN.
 PLEASE NOTE MATERIALS TO BE STORED IN EACH AREA,
 HAZARDOUS MATERIALS AND AMOUNTS, AS WELL AS COMPLIANCE
 WITH ANY SPECIAL REQUIREMENTS, IF ANY, FBC413.
  
 18. SHOW ACCESSIBLE EXITS, FBC11-4.1.3(9), A901C.
  
 19. A901C, SEE THE EXIT AT THE BALED STORAGE AREA.
 PLEASE SHOW THAT THIS IS NOT A REQUIRED ACCESSIBLE EXIT
 DUE TO TRAVEL DISTANCE AS THIS EXIT DOES NOT PROVIDE
 VERTICAL ACCESSIBILITY, FBC11-4.1.3(9).
  
 20. THE LIFE SAFETY PLAN DOES NOT CORRELATE WITH A001C.
 THERE ARE SEVERAL AREAS IN THE PROCESSING FLOOR WITH
 DOORS AND WHAT APPEAR TO BE WALLS OR SOME OTHER
 OBSTRUCTION PREVENTING PASSAGE.TRAVEL DISTANCE,
 COMMON PATH OF TRAVEL, AND DEAD END CORRIDOR
 REQUIREMENTS (FBC1015, FBC1016.3) CANNOT BE DETERMINED
 UNLESS THESE OBSTRUCTIONS AS WELL AS THE EQUIPMENT IS
 PLACED ON THE LIFE SAFETY PLAN.CONVEYOR BELTS,
 CATWALKS, AND OTHER EQUIPMENT WHICH ARE SHOWN ON A001C
 BUT WHICH DO NOT AFFECT THE PATH OF TRAVEL NEED NOT BE
 SHOWN ON THE LIFE SAFETY PLAN, A901C.
  
 21. S1 DECLARED, BUT CODE ANALYSIS ITEM 5, FIRE
 PROTECTION SYSTEM, REFERS TO 903.2.3, REQUIREMENTS FOR
 F1 OCCUPANCY.PLEASE REVISE CODE REFERENCE.
  
 22. TO AVOID FIELD ISSUES AND TO ASSIST TRADES AND
 INSPECTORS, ON SHEET A901C, PLEASE SHOW HORIZONTAL FIRE
 RESISTANCE REQUIRED BETWEEN 1ST FLOOR AND MEZZANINE.
  
 23. PLEASE CLARIFY .15IN FOR EGRESS COMPONENTS, A901C.
 IT IS UNCLEAR WHERE THIS COMES FROM.SEE FBC TABLE
 1005.1.
  
 24. STAIRWAYS ARE TO BE .3 PER OCCUPANT, NOT .2, FBC
 TABLE 1005.1.REVISE A901C.
  
 25. OTHER COMPONENTS IN THE MEANS OF EGRESS ARE TO BE
 .2 PER OCCUPANT, NOT .15, REVISE A901C.THE DOORS DO
 NOT COMPLY WITH THE MINIMUM REQUIREMENTS WHEN THE
 OCCUPANT LOAD IS MULTIPLIED BY .2 RATHER THAN .15; FOR
 INSTANCE, SEE STAIR 2 EXIT DOOR, 39.4INCHES REQUIRED
 BUT ONLY 32 INCHES PROVIDED.CHECK ALL.
  
 26. DECLARE OCCUPANT LOAD FOR THE SCALE HOUSE,
 FBC1004.
  
 27. SHOPS/ENGINEERING FOR THE STEEL CONTAINMENT WALL
 PROVIDED BY CP MANUFACTURING A001C REVIEWED BY ENGINEER
 AND PRIVATE PROVIDER WILL BE REQUIRED PRIOR TO
 INSTALLATION; PROVISO ITEM.
  
 28. A004C, SECTION 2, DOES NOT APPEAR TO SHOW THE DOOR
 AND STAIR.
  
 29. A003C AND OTHER SHEETS, PLANS SHOW SEVERAL LADDERS,
 STAIRS, EQUIPMENT PLATFORMS, AND CATWALKS.SEE
 FBC505.5.1, FBC505.5.2, 505.5.3, FBC CHAPTER 10. PLEASE
 PROVIDE SHOPS WHICH SHOW CODE COMPLIANCE OR CONTACT ME
 TO DISCUSS AT WHAT POINT DESIGNER/CONTRACTOR PROPOSES
 TO SUBMIT THE DRAWINGS FOR THESE COMPONENTS.
  
 30.SHOW LOCATION OF ANY ROOFTOP MECHANICAL EQUIPMENT
 INCLUDING DISTANCE FROM EDGE, A006C.SEE FBC1012.5 AND
 SHOW ANY REQUIRED GUARDS, LOCATION AND A DETAIL,
 FBC1012.
  
 31. THE STRUCTURAL CALCULATIONS (VP BUILDINGS), SCALE
 HOUSE SHOP DRAWINGS, AND STRUCTURAL PLAN FOR THE MAIN
 BUILDING HAS A PHOTOCOPY OF THE ENGINEER?S SIGNATURE.
 AN ORIGINAL WET SIGNATURE IS REQUIRED AS WELL AS A
 TITLE BLOCK WITH ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.ALSO PLEASE NOTE THE FOLLOWING AND
 ADDRESS:
  
 A. THE STRUCTURAL CALCULATIONS AND PLANS FOR THE VP
 BUILDING STRUCTURE WERE NOT REVIEWED BY THE PRIVATE
 PROVIDER OR BY THE DESIGNER FOR THE BUILDING.
  
 B. THE CALCS AND PLANS STATE NOT FOR CONSTRUCTION;
 PLEASE PROVIDE CONSTRUCTION SET.PLEASE ALSO SEE
 FAC61G15; PRELIMINARY PLANS SHOULD NOT BE SIGNED AND
 SEALED BY THE ENGINEER.
  
 C. PAGE 4 OF THE CALCULATIONS, OTHER SHEETS, PLANS,
 REFER TO 2004 FLORIDA STATE BUILDING CODE; PLEASE
 REVISE TO GOVERNING CODE WHICH IS FLORIDA BUILDING CODE
 2004 WITH 2007 REVISIONS/SUPPLEMENTS.
  
 D. PAGE 4 CALCULATIONS, OTHER SHEETS, AISC89 SHOULD
 INCLUDE SUPPLEMENT 1, FBC35.
  
 E. ALL SIGNED AND SEALED SHEETS ARE TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.IN THE PAST,
 THIS ISSUE AS WELL AS THE PHOTOCOPIED SIGNATURE HAS
 CAUSED PERMIT DELAYS.PLEASE ONLY SUBMIT PLANS WHICH
 COMPLY, ESPECIALLY AS THE ENGINEER HAS BEEN ADVISED OF
 THESE REQUIREMENTS ON AT LEAST TWO OTHER PROJECTS IN
 THE PAST.THE ENGINEER?S COOPERATION WILL HELP TO
 EXPEDITE PLAN REVIEW AND PERMIT ISSUANCE.
  
 32. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR
 MIAMIDADE NOA REQUIRED FOR THE ROOF PANELS, FAC9B72.
  
 33. PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.AS THEY ARE A PART OF THE BUILDING
 ENVELOPE AND REQUIRED TO DETERMINE CODE COMPLIANCE, THE
 PRODUCT APPROVALS ARE ALSO TO BE REVIEWED BY THE
 PRIVATE PROVIDER.
  
 34. THE PRODUCT APPROVALS SUBMITTED HAVE NOT YET BEEN
 REVIEWED AS DESIGN PRESSURES HAVE NOT BEEN SPECIFIED.
 HOWEVER PLEASE NOTE THAT THE COIL DOOR PRODUCT APPROVAL
 IS FOR A 16FT WIDE DOOR MAXIMUM, BUT A 20FT DOOR IS
 SHOWN ON A002C.
  
 35. FOR FL4553, CECO DOOR, PROVIDE THE EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS FROM THE WEBSITE,
 WWW.FLORIDABUILDING.ORG.
  
 36. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.THIS IS
 REQUIRED FOR THE STRUCTURE, AND COMPONENT AND CLADDING
 PRESSURES REQUIRED BUT NOT PROVIDED.
  
 37. FOR THE PEERLESS HORIZONTAL SLIDER, PROVIDE FLORIDA
 STATE PRODUCT APPROVAL OR MIAMIDADE NOA, FAC9B72.A
 TEST REPORT WAS PROVIDED BUT ADDITIONAL INFORMATION IS
 REQUIRED.
  
 38. THE VACRO PRUDEN BUILDINGS MIAMIDADE NOA SUBMITTED
 FOR THE WALL PANELS IS EXPIRED AS OF 7/1/08.PLEASE
 PROVIDE A CURRENT PRODUCT APPROVAL, FAC9B72.
  
 39. CALCULATIONS FOR VERSAKING BUILDINGS WERE
 SUBMITTED.PLEASE NOTE THE FOLLOWING:
  
 A. THE CALCS ARE TO BE REVIEWED BY THE PRIVATE PROVIDER
 AND BY THE DESIGNER OF RECORD.
  
 B. CALCS REFER TO PORTAKING DRAWINGS.PLEASE SUBMIT.
 DRAWINGS ARE TO BE REVIEWED BY DESIGNER OF RECORD AND
 THE PRIVATE PROVIDER.
  
 C. IT APPEARS THAT THE STRUCTURES WILL BE INSTALLED
 INSIDE OF THE VP BUILDING AS NO WIND LOADS WERE
 PROVIDED.PLEASE CLARIFY ON THE PLAN; SHOW LOCATION OF
 THE PROPOSED PORTAKING STRUCTURES ON THE FLOOR PLAN.
  
 D. INCLUDE THE DOORS FOR THE STRUCTURES ON A DOOR
 SCHEDULE OR PROVIDE INFORMATION IN ANOTHER FORMAT TO
 SHOW COMPLIANCE WITH ACCESSIBILITY FBC11 AND OTHER
 REQUIREMENTS FBC10.
  
 E. CALCULATIONS ARE TO BE EITHER SIGNED, SEALED AND
 DATED WITH A TITLE BLOCK ON EACH SHEET, OR AN INDEX
 SHEET IN ACCORDANCE WITH FAC61G15-23 USED.PLEASE
 ADDRESS.
  
 F. GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 40. THE 3 RING BINDER ENTITLED TECHNICAL SPECIFICATIONS
 HAS NOT BEEN REVIEWED BY THE PRIVATE PROVIDER.ALSO IT
 WAS NOT PREPARED IN ACCORDANCE WITH FAC61G1-16.002,
 003; EITHER EVERY SHEET SIGNED AND SEALED OR AN INDEX
 SHEET USED.THIS BINDER MAY BE REMOVED IF ALL
 INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS
 INCLUDED IN THE PLANS.OTHERWISE, PLEASE SUBMIT
 REVIEWED AND IN COMPLIANCE WITH FAC RULES.PLEASE NOTE
 THAT NORMALLY THE ENTIRE DOCUMENT IS NOT REVIEWED; IT
 WILL BE INCLUDED WITH THE RECORD SET WITH THE PROVISO
 IN ACCORDANCE WITH FBC2004 AND PLAN.
  
 41. THE DOOR SCHEDULE IN THE TECHNICAL SPECIFICATIONS
 BINDER DOES NOT INCLUDE ALL OF THE DOORS ON THE DOOR
 SCHEDULE IN THE PLAN; FOR INSTANCE, DOORS 102 1, 124 5,
 205 2.IF THE TECHNICAL SPECIFICATIONS BINDER REMAINS
 A PART OF THE PERMIT SET, PLEASE CORRELATE.
  
 42. THE WALL AT DOOR 132 1 IS NOT SHOWN AS A FIRE
 RESISTANCE RATED WALL ALTHOUGH SPECIFIED AS FIRE
 RESISTANCE RATED ON THE LIFE SAFETY PLAN A901C.
  
 43. STAIR 1 OPENS INTO THE ELEVATOR LOBBY.SEE
 FBC1019.1.1.NO OPENINGS PERMITTED IN THE STAIR
 ENCLOSURE OTHER THAN THOSE REQUIRED FOR ACCESS, AND
 THOSE OPENINGS ARE TO BE RATED.
  
 43. DOOR 201 1, ASSEMBLY TO STORAGE, DOES NOT SHOW FIRE
 RESISTANCE, SEE FBC715.3.
  
 44. SEE FBC TABLE 1016.1, CORRIDORS 203 AND 205 FROM
 VISITOR?S GALLERY TO STAIRS TO HAVE 1 HOUR FIRE
 RESISTIVE RATING AND THEREFORE DOORS 203 1, 204 1, 205
 1, 206 1, 200 1, TO BE RATED IN ACCORDANCE WITH
 FBC715.3.
  
 45. A FIRE RATED WALL IS SHOWN BETWEEN TOOL & EQUIPMENT
 ROOM AND THE PROCESSING AREA, BUT NO RATING IS SHOWN
 FOR DOOR 124 3.PLEASE CLARIFY DESIGN CRITERIA.
  
 46. SEE FBC715.3, DOOR 201 1 AND WINDOWS W5 TO HAVE
 FIRE PROTECTION IN ACCORDANCE WITH FBC TABLE 715.3 IF
 AN OCCUPANCY SEPARATION IS REQUIRED.PLEASE SEE OTHER
 REQUIREMENTS REGARDING FBC302, FBC 5, REGARDING
 BUILDING HEIGHT AND AREA.AN UNLIMITED BUILDING SIZE
 WAS DECLARED BUT THIS BUILDING DOES NOT COMPLY
 (ASSEMBLY LIMITATIONS).DEPENDING ON HOW COMPLIANCE IS
 SHOWN, VERTICAL AND HORIZONTAL OCCUPANCY SEPARATION MAY
 BE REQUIRED.
  
 47. STAIR 2 SPECIFIES A 1 HOUR WALL ON THE EXTERIOR
 SIDE OF THE STAIR, A101C, BUT NO FIRE RATING FOR THE
 DOOR 136 1.CLARIFY DESIGN INTENT.
  
 48. A114C, 2 HOUR BLOCK SPECIFIED.PLEASE PROVIDE SPEC
 SHEETS AS 2 HOUR IS PROPRIETARY.
  
 49. UL905 SPECIFIED A114C, PROVIDE A COMPLETE DETAIL
 FOR THIS AND ANY OTHER UL ASSEMBLIES SPECIFIED ON THE
 PLAN.
  
 50. PROVIDE PENETRATION DETAILS, FBC712.
  
 51. SEE STAIR SHAFT DETAILS A114C, DOES THIS GO TO THE
 UNDERSIDE OF THE DECK?SEE FBC706.4, 1019.1, PROVIDE A
 DETAIL SHOWING COMPLIANCE.
  
 52. A112C SPECIFIES PLYWOOD.PLEASE CLARIFY USE OF
 COMBUSTIBLE IN THIS TYPE IIB BUILDING, FBC603.
  
 53. SPECIFY INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 54.THE WALL BETWEEN THE VISITOR?S GALLERY AND THE
 OTHER ADJACENT MEZZANINE AREAS DOES NOT SHOW ANY FIRE
 RESISTIVE RATING.PLEASE SEE OTHER COMMENTS; IS THIS
 ALL ASSEMBLY OCCUPANCY, OR DOES IT REQUIRE AN OCCUPANCY
 SEPARATION?DESIGN INTENT IS NOT CLEAR.
  
 55. FBC13-101.1, ENERGY CALCS REQUIRED FOR BOTH THE
 MAIN BUILDING AND FOR THE SCALE HOUSE.
  
 56. JANITOR?S ROOM 138 IS TO BE ACCESSIBLE
 FBC11-4.1.1(3), WORK AREAS ARE TO BE DESIGNED SO THAT
 EMPLOYEES CAN APPROACH, ENTER, AND EXIT THE AREAS. SHOW
 TURNING RADIUS.
  
 57. PROVIDE INFORMATION (SPEC SHEETS SUGGESTED) FOR THE
 DOOR AT THE VESTIBULE, 112 2 TO SHOW COMPLIANCE WITH
 FBC11-4.13 AND FBC10.
 58. PROVIDE THE ANTICIPATED OCCUPANT LOAD FOR THE AREA
 AT THE BOTTOM OF THE COMMUNICATING NON EGRESS STAIR.
 THIS APPEARS TO BE 3FT4IN.10 OCCUPANTS SHOWN FOR DOOR
 134 1, PLEASE CLARIFY HOW YOU HAVE DETERMINED
 ANTICIPATED OCCUPANTS PER DOOR.
  
 59. SEE FBC1016.4, AIR MOVEMENT IN CORRIDORS.PLEASE
 REMOVE SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION
 AIR DUCTS FROM EXIT ACCESS CORRIDORS, SEE OTHER
 COMMENTS.PLEASE NOTE THAT THERE ARE TWO HALLS IN THE
 MEZZANINE WHICH SERVE AS CORRIDORS.
  
 60. SEE FBC1019.1.2, PENETRATIONS INTO THE STAIRS ARE
 PROHIBITED EXCEPT AS PERMITTED BY THIS CODE SECTION.
 PLEASE REVISE PLANS.
  
 61. DETAIL 1 A007C STATES TO SEE STRUCTURAL DRAWINGS
 FOR THE STAIR RAIL DETAIL.PLEASE SPECIFY DETAIL,
 NUMBER AND PAGE. THERE ARE MANY REFERENCES THROUGHOUT
 THE A SHEETS TO SEE STRUCTURAL DWGS.PLEASE REVISE ALL
 TO REFER SPECIFICALLY TO A DETAIL.
  
 62. A114C, SPECIFY GUARD PICKET SPACING FBC1012.
  
 63. GUARDRAILS AND HANDRAILS, SPECIFY DESIGN STRENGTH
 TO COMPLY WITH FBC1607.7.
  
 64. SEE 3 A007C, THE HANDRAIL IS NOT CONTINUOUS. A106C
 HANDRAIL EXTENSIONS AT BOTTOM NOT SHOWN. PLEASE PROVIDE
 DETAILS AND CORRELATE A SHEETS.
  
 65. 2 A107 IS LOCATED ON SHEET A102 RATHER THAN 101. IS
 ACCESSIBILITY REQUIRED?PLEASE CONFIRM THAT ALL
 DETAILS ARE REFERRED TO PROPERLY ON THE PLAN.
  
 66. IT APPEARS THAT THE CHAIN LINK FENCE AND GATE
 OBSTRUCT THE MEANS OF EGRESS CONTINUITY, FBC1003.1. THE
 GATE AND COIL DOOR DO NOT MEET ANY OF THE REQUIREMENTS
 AS A MEANS OF EGRESS COMPONENT OF CHAPTER 10.
  
 67. PROVIDE A SITE PLAN AND A SURVEY TO BE INCORPORATED
 INTO THIS PLAN TO SHOW COMPLIANCE WITH THE OPEN SPACE
 REQUIREMENT FBC507.2, REVIEWED BY PRIVATE PROVIDER, AS
 WELL AS ACCESSIBILITY REQUIREMENTS FOR PARKING AND
 ACCESSIBLE ROUTE, SEE OTHER COMMENTS.PLANS WERE
 SUBMITTED WHICH WERE PREPARED BY THE LANDSCAPE
 ARCHITECT; IT IS NOT CLEAR IF THE LANDSCAPE PLAN IS TO
 BE USED TO SHOW CODE COMPLIANCE WITH LIFE SAFETY, FBC
 CHAPTER 5, AND ACCESSIBILITY.PLEASE PROVIDE A PLAN TO
 BE USED FOR THAT PURPOSE OR INCORPORATE THE REQUIRED
 INFORMATION INTO THE C SHEETS.
  
 68. THE SITE PLAN IS TO DECLARE TOTAL NUMBER OF PARKING
 SPACES AND TOTAL NUMBER OF ACCESSIBLE PARKING SPACES
 FBC11-4.1.2(5)(A).
  
 69. THE ACCESSIBLE PARKING SPACES ARE TO BE DISPERSED
 FBC11-4.6.2.PLEASE SHOW THE DOORS ON THE SITE PLAN IN
 RELATION TO THE PROPOSED ACCESSIBLE PARKING SPACES AND
 ALSO SHOW ACCESSIBLE ENTRANCES.
  
 70. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY TO
 THE ACCESSIBLE BUILDING ENTRANCE FBC11-4.3.2.1(1).
  
 71. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE
 FBC11-4.6 AND SHOW WIDTH OF ACCESSIBLE ROUTE, NO LESS
 THAN 44INCHES, FBC11-4.6.2(1).
  
 72. PLEASE NOTE THAT THE FOUNDATION PERMIT HAS NOT BEEN
 ISSUED; THEREFORE, ANY INFORMATION INCLUDED IN THAT
 PERMIT CANNOT BE USED TO SHOW CODE COMPLIANCE FOR THIS
 PERMIT AT THIS TIME.
  
 73. SHOW LOCATION OF STROBES, FBC11-4.28.1.
  
 74. ELEVATOR SIGNAGE TO COMPLY WITH FBC11-4.10.5, CALL
 BUTTONS WITH FBC11-4.10.3.
  
 75. SEE FC1009.4, STAIR LANDINGS, INTERMEDIATE LANDING
 IS 44 IN, 48 INCHES REQUIRED, A113C.
  
 76. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE GRAB
 BARS TO THE SHEET METAL TO SHOW COMPLIANCE WITH
 FBC1607.7.1.1, FBC11-4.26.3.
  
 77. PROVIDE A SPECIFICATION FOR ATTACHMENT OF THE
 BACKING FOR THE GRAB BARS (A111C) TO SHOW COMPLIANCE
 WITH FBC1607.7.1.1, FBC11-4.26.3.DETAIL STATES
 SCREWED TO STUD BUT DOES NOT SPECIFY SIZE OF SCREWS OR
 DISTANCE APART, DOES NOT SPECIFY A WIDTH FOR THE 22G
 SHEET METAL BACKING.
  
 78. SEE FBC1006 AND SHOW COMPLIANCE.IT IS NOT CLEAR
 WHAT ILLUMINATION WILL BE PROVIDED FOR THE EQUIPMENT
 PLATFORMS, STAIRS.
  
 79. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 SIGNS.THEY ARE USUALLY APPLIED FOR BY THE SIGN
 CONTRACTOR PRIOR TO INSTALLATION.
  
 80. PLEASE SHOW COMPLIANCE WITH FBC910, SMOKE AND HEAT
 VENTS.PROVIDE CALCULATIONS ON THE PLAN AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 81. FBC505.5.2, FP101C DOES NOT MAKE REFERENCE TO
 SPRINKLERS ABOVE AND BELOW PLATFORMS.ON THE SPRINKLER
 HEAD LAYOUT PLAN, SHOW COMPLIANCE.
  
 82. SEE OTHER COMMENTS.IT IS NOT CLEAR WHETHER THE
 EXIT LIGHTS PROVIDED ARE ADEQUATE, FBC1006.3; CANNOT
 DETERMINE WHETHER OR NOT EQUIPMENT OBSTRUCTS THE EXIT
 LIGHTS.PLEASE ADDRESS ON THE PLAN, PREFERABLY THE
 LIFE SAFETY PLAN.
  
 83. SEE FBC1503.6, PROVIDE A DETAIL FOR CONDENSATE
 LINES AND ROOF DOWNSPOUTS.
  
 84. WHEN RESUBMITTING, PLEASE INCLUDE A DETAILED
 RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED,
 INCLUDING PAGE NUMBER(S) IF POSSIBLE.THIS WILL HELP
 TO EXPEDITE PLAN REVIEW.
  
 85. SOME OF THE PLANS HAVE BEEN RETAINED.WHEN
 RESUBMITTING, PLEASE SUBMIT THREE COMPLETE SETS. THE
 PLANS WHICH HAVE BEEN RETAINED WILL NOT BE RELEASED FOR
 PERMITTING PURPOSES.CONTACT DEWEY PALMER IF YOU HAVE
 QUESTIONS REGARDING THIS ISSUE.

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 16:04 Sent To PC
Notes
2009-09-24 16:05:13REVISED PANELS.

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2009-08-31 Cont ID  
Sent By dpalmer Date 2009-08-31 Time 12:10 Rev Time 0.00
Received By dpalmer Date 2009-08-31 Time 12:10 Sent To PC
Notes
2009-08-31 12:10:48 
  
 ** REDLINED REVIEW **
  
  
  
 1) NOTE: LARGEST BRANCH CIRCUIT ON SCS IS SHOWN AS
 30AMP. AS ELP1 HAS NOW BEEN REVISED TO REMOVE FEED TO
 SUB PANEL, THEN THE ACTUAL LARGEST BREAKER IS 2-P
 20AMP.
  
 2) NOTE: E-117 NEEDS TO BE REVISED FOR ELP1
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2009-07-16 Cont ID  
Sent By dpalmer Date 2009-07-16 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2009-07-16 Time 09:55 Sent To  
Notes
2009-07-16 09:56:02 
  
 ** DENIED **
  
 SUBMISSION OF THE SELECTIVE COORDINATION STUDY.
  
 ** THE FOLLOWING COMMENTS ARE BASED ON THE SELECTIVE
 COORDINATION STUDY AND NEW COMMENTS DERIVED DURING
 REVIEW. A CALL WAS MADE TO GIPE AND ASSOCIATES AND
 SPOKE TO MICHAEL PURTELL.
  
 ** IN THE NOTES BELOW THE SELECTIVE COORDINATION STUDY
 WILL BE NOTED AS SCS.
  
 1) NOTE: NEW COMMENT: PLEASE SEE 700.9(B). PLEASE SEE
 NEC 2005 HANDBOOK COMMENTARY FOR WIRING OF SYSTEMS.
 PLEASE EXPLAIN HOW OPTIONAL STAND-BY LOADS SUCH AS
 CEILING FANS, SCALES AND OTHER GENERAL LOADS MAY BE
 PART OF THE LIFE SAFETY/ EMERGENCY SYSTEM. THIS WAS ON
 PREVIOUS PLANS HOWEVER WAS MISSED BY REVIEWER.
 STAND-BY LOADS MAY BE FED FROM SEPARATE FEED ON
 GENERATOR WITH SEPARATE TRANSFER SWITCH OR REMOVE ALL
 LOADS FROM EMERGENCY PANELS.
 IF ELP-1 WAS A * SWITCHBOARD * THEN THERE COULD BE A
 SEPARATE BRANCH FEED TO A STAND-BY ATS WHICH WOULD THEN
 FEED TERP-1.
  
 2) NOTE: PLEASE COORDINATE THE SCS WITH THE PLANS.
 PLEASE SEE THE SCS RISER AS THIS INDICATES ONLY ONE SET
 OF FEEDERS TO ATS-2 WHERE THE PLANS ON RECORD INDICATES
 2 SETS OF PARALLEL 3/0.
  
 3) NOTE: PLEASE EXPLAIN THE SCS RISER WHICH SEEMS TO
 INDICATE 100HP AND 50HP FOR FIRE PUMP.
  
 4) NOTE: PLEASE COORDINATE THE BREAKER ON THE GENERATOR
 FOR ATS-2E WHICH SHOWS 250A ON SCS RISER AND 200AMP ON
 PLANS.
  
 5) NOTE: ALL OCP DEVICES ON THE GENERATOR SHALL BE PART
 OF THE STUDY. PLEASE KNOW BASED ON THE 60AMP BREAKER ON
 ELP-1 THIS WOULD ALSO BE ON STUDY. ALTHOUGH PLEASE SEE
 COMMENT #1 ABOVE AS THIS DOES AFFECT THE RISER AS IT
 STANDS.
  
  
 240.12, 701.18, 700.27
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2009-05-18 Cont ID  
Sent By dpalmer Date 2009-05-18 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2009-05-18 Time 14:51 Sent To  
Notes
2009-05-18 14:52:01REVS FOR BALER

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2009-04-20 Cont ID  
Sent By dpalmer Date 2009-04-20 Time 14:28 Rev Time 0.00
Received By dpalmer Date 2009-04-20 Time 14:28 Sent To PC
Notes
2009-04-20 14:28:35ELEC REV E 107 CR5, 120 CR3

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2009-04-12 Cont ID  
Sent By dpalmer Date 2009-04-12 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2009-04-12 Time 11:03 Sent To PC
Notes
2009-04-12 11:03:50** DENIED**
  
 1) NOTE: THE PLANS SUBMITTED DO NOT CONTAIN THE SAME
 SIGNATURE AS ALL OTHER PLANS IN FILE FOR THE SAME
 ENGINEER OF RECORD. THE PLANS ARE SIGNED WITH A
 SIGNATURE WHICH IS COMPLETELY DIFFERENT. PLEASE SEE FS
 471.023 AND FAC 61G15-23.002.
 PLANS SHALL BE SIGNED AND SEALED BY THE ENGINEER BY OF
 RECORD. AN ENGINEER MAY NOT DESIGNATE ANOTHER PERSON TO
 SIGN PLANS. THIS HAS BEEN CONFIRMED ON MANY OCCASIONS
 WITH THE ATTORNEYS AND INVESTIGATORS FOR THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. PLEASE CONTACT THE
 BOARD, JERRY ONGLEY, OR JACK BEAMISH WITH ANY QUESTIONS
 ON THIS MATTER.
 ** THIS REVIEWER HAD PLACE PHONE CALL TO THE ENGINEER'S
 OFFICE ON THE 3RD OF APRIL IN WHICH THE OFFICE SAID THE
 ENGINEER WAS OUT ON A VACATION. THIS IS THE SAME DATE
 ON PLANS WHEN SIGNED AND SEALED.
 ** ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-04-02 Cont ID  
Sent By dpalmer Date 2009-04-02 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2009-04-02 Time 19:26 Sent To  
Notes
2009-04-02 19:26:59REV 104, 105 AND 108

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-04-01 Cont ID  
Sent By dpalmer Date 2009-04-01 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2009-04-01 Time 17:49 Sent To PC
Notes
2009-04-01 17:50:04** DENIED REVIEW **
  
 1) NOTE: SHEETS E107, 120 AND 121 SHALL COORDINATE WITH
 THE ELECTRICAL PLANS FOR THE EQUIPMENT ELECTRICAL
 ENGINEERED PLANS.
 PLEASE SEE THE PANEL PP-EC IS STILL NOT LISTED ON THE
 MSB SWITCHBOARD.
 THE RISER SUBMITTED FOR THE EQUIPMENT ENGINEERED PLANS
 ALONG THE REVISED RISER ON E120 SHOWS A 175AMP BREAKER
 FEEDING PANEL PP-EC HOWEVER PLEASE TAKE A LOOK AT MSB
 SCHEDULE. THE ONLY 175 BREAKER ON EITHER E107 OR E120
 IS THE 175AMP BREAKER WHICH IS STATED FOR THE
 *RELOCATED BALER*. TO DATE THERE IS NO PP-EC LISTED ON
 EITHER MSB SCHEDULE.
 PLEASE COORDINATE ALL.
 PLEASE REVISE LOAD CALCULATIONS.
 408.4, 310.16, 240, 220 ETC
  
 2) NOTE: SHEET E-1 THROUGH E-4 HAS BEEN STAMPED FOR
 ELECTRICAL ENGINEERED EQUIPMENT PLANS. THIS SCOPE OF
 WORK IS NOT PART OF THE BASE BUILDING ELECTRICAL. IN
 FACT THIS SCOPE OF WORK IS DONE BY A SEPARATE
 ELECTRICAL CONTRACTOR.
  
 A PHONE CALL WAS PLACED TO THE BASE BUILDING ELECTRICAL
 ENGINEER FOR A RETURN CALL.
 ONE SET OF ELECTRICAL PLANS FOR BASE BUILDING HAVE BEEN
 RETAINED BY THIS REVIEWER.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2009-03-27 Cont ID  
Sent By dpalmer Date 2009-03-27 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2009-03-27 Time 14:35 Sent To  
Notes
2009-03-27 14:36:28HORN/ STOBE RFI, PER BUIDLING AND FIRE REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-03-26 Cont ID  
Sent By dpalmer Date 2009-03-26 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2009-03-26 Time 18:15 Sent To PC
Notes
2009-03-26 18:15:14** DENIED REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEAS SUBMIT A COMPLETE COORDINATION STUDY.
 THIS NEEDS TO INCLUDE COORDINATION RISER, STUDY AND
 TIME CURVES. THE SUBMITTED SHORT CIRCUIT ANALYSIS IS
 NOT ALL THE INFORMATION THAT IS NEEDED TO VERIFY
 MINIMUM CODE COMPLIANCE. IT WAS GONE OVER ON THE PHONE
 THAT THE COMPLETE STUDY ALONG WITH TIME CURVES.
 700.27, 701.8, 240.12 ETC.
 *** IT IS IMPORTANT TO KNOW THAT SINCE THE COORDINATION
 STUDY HAS YET TO BE SUBMITTED THERE MAY BE NEW COMMENTS
 ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 2) NOTE: AS STATED ON PREVIOUS REVIEW. THE ENGINEER FOR
 THE BASE BUILDING ELECTRICAL PLANS NEEDS TO SIGN THE
 SHOP DRAWING REVIEW STAMPED OF THE SUBMITTED ELECTRICAL
 ENGINEERED SYSTEMS PLANS.
 THE PERSON SIGNED IS NOT THE ENGINEER OF RECORD. ALL
 ELECTRICAL WORK, LOADS ETC IN THE BUILDING BEFORE THE
 CERTIFICATE OF OCCUPANCY IS ISSUED IS UNDER THE REVIEW
 AND RESPONSIBILITY OF THE BASE BUILDING DESIGN
 PROFESSIONAL TO BE AWARE OF TRACK AND ADJUST MAIN
 PLANS.
 FS 471.025
  
 3) NOTE: PLEASE SEE BASE BUILDING RISER AND SUBMITTED
 ELECTRICAL ENGINEERING PLANS ARE STILL NEED
 COORDINATION. PLEASE SEE E120CR1 WHICH IS NOW NOT
 REVISED TO MATCH THE UPDATED MSB ON E107CR4.
 FOR EXAMPLE: REVISED MCC1 ON E107
 FOR EXAMPLE: REVISED PP-EC ON E120 WHICH IS NOT ON E
 107.
 PLEASE PROVIDE LOADS/CIRCUITS FOR THE LC. (LOAD
 CENTERS) LC210- LC217
 215.5, 408.4, 230, 240 SECTIONS GIVEN FOR COORDINATION
 OF ELECTRICAL PLANS.
 THE TOTAL LOAD SHOWN ON MSB IS NOT ACCURATE. PLEASE
 UPDATE WITH ALL NEW LOADS.
  
 4) NOTE: FOR CONTRACTOR INFORMATION: IF THE EQUIPMENT
 PLANS AND BASE BUILDING PLANS ARE CLEARED UP BASED ON
 NOTES #2 AND #3 THE EQUIPMENT CONTRACTOR WILL BE ABLE
 TO APPLY FOR PERMIT. COMMENT #1 MAY REMAIN OUTSTANDING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-03-10 Cont ID  
Sent By dpalmer Date 2009-03-10 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2009-03-10 Time 19:15 Sent To PC
Notes
2009-03-10 19:15:57** DENIED REVISIONS **
  
 REVISION OF PLANS FOR BASE BUILDING AND SUBMITTAL OF
 ELECTRICAL MANUFACTURING EQUIPMENT PLANS.
  
 1) NOTE: THE REVISED SHEETS FOR ARCHITECTURAL NOTES AND
 SHEET E104CR4 ARE OK.
  
 2) NOTE: ELECTRICAL RISER SHEET E107CR3 WILL REMAIN IN
 FAILED STATUS UNTIL COORDINATION WITH MANUFACTURING
 PLANS AND REVISIONS ARE MADE.
 SEE NOTE #4 BELOW AND OTHER NOTES.
  
 ** REVIEW FOR PLANS BY ASSOCIATED ENGINEERING
 INCORPORATED:
  
 3) NOTE: THE TITLE BLOCKS NEED TO CONTAIN THE PRINTED
 NAME AND LICENSE NUMBER OF THE PROFESSIONAL ENGINEER
 EVEN IF THIS INFORMATION IS IN THE SAID SEAL OF THE
 SAME DESIGN PROFESSIONAL.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002
  
 4) NOTE: PLANS SHOWS GFI PROTECTION FOR THE 3000AMP
 MAIN DISTRIBUTION CENTER. PLEASE SEE 240.13,230.95 AS
 THIS SHOULD BE NOTED OR IDENTIFIED AS GFP. (GROUND
 FAULT PROTECTION) GFI IS FOR PERSONNEL PROTECTION.
 THE RISER NOTES # 7 ON E107CR3 STILL NOTES GFI EVEN AS
 THE MSB PANEL STATES GFP.
 PLEASE COORDINATE.
  
 5) NOTE: PLEASE SEE MCC1 AS THIS EQUIPMENT IS SHOWN
 RATED AT 450AMP YET THERE IS A 500AMP BREAKER ON E107
 SHOWN FEEDING THIS EQUIPMENT. THIS IS THE SAME ON THE
 EQUIPMENT PLANS.
 240, 230, 310, 110.14 ETC.
  
 6) NOTE: PLEASE SEE THE EQUIPMENT PLANS AS THEY CLEARLY
 INDICATE A 600AMP DISTRIBUTION SECTION WHICH IS NOT ON
 THE E107 SHEET/ RISER.
 NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE
 BASE BUILDING PLANS.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND
 ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5,
 240.4,230 ETC. THESE SECTIONS ARE GIVEN AS GENERAL
 CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS NOT
 POSSIBLE TO DO A SPECIFIC REVIEW.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT RISER
 INDICATES A NEW 300AMP BREAKER ON THE MSB FEEDING A NEW
 225KVA TRANSFORMER. NEITHER OF THESE TWO ITEMS IS ON
 THE BASE BUILDING ELECTRICAL RISER DIAGRAM ON SHEET
 E107.
 NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE
 BASE BUILDING PLANS.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND
 ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5,
 240.4,230, 408.4ETC. THESE SECTIONS ARE GIVEN AS
 GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS
 NOT POSSIBLE TO DO A SPECIFIC REVIEW.
  
 8) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT RISER AS
 THIS RISER CONTAINS TEN ELECTRICAL PANELS WHICH ARE
 IDENTIFIED AS SE1 THROUGH SE 10. NONE OF THESE PANELS
 ARE ON THE BASE BUILDING ELECTRICAL PLANS ON E107.
 PLEASE SEE NOTES # 6 AND 7 ABOVE AS THESE ARE DIRECTLY
 AFFECTED BY THESE ITEMS.
 NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE
 BASE BUILDING PLANS.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND
 ADDITIONAL INFORMATION ON RECORD PLANS. NEC 220,215.5,
 240.4,230, 408.4ETC. THESE SECTIONS ARE GIVEN AS
 GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED. IT IS
 NOT POSSIBLE TO DO A SPECIFIC REVIEW.
  
 9) NOTE: THE BASE BUILDING ELECTRICAL RISER INDICATES A
 MCCB YET THE EQUIPMENT RISER FROM MANUFACTURE DOES NOT
 INDICATE THIS MCCB. THIS IS NOT ON THE RISER OR IN THE
 LOAD CALCULATIONS.
 215.5,220,408.4,240.4, 310.16 ETC
 NO INFORMATION IS PROVIDED FOR THIS PROVISION ON THE
 BASE BUILDING PLANS.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2, COORDINATION AND
 ADDITIONAL INFORMATION ON RECORD PLANS. SECTIONS ARE
 GIVEN AS GENERAL CHAPTERS AS PLANS ARE NOT COORDINATED.
 IT IS NOT POSSIBLE TO DO A SPECIFIC REVIEW.
  
 10) NOTE: PLEASE KEEP IN MIND A COMPLETE REVISED
 ELECTRICAL COORDINATION STUDY ALONG WITH TIME CURVES
 ETC WILL BE REQUIRED NOT THAT ALL ELECTRICAL EQUIPMENT
 IS NOTED, FIGURED ETC.
 PLEASE SEE 240.12, 700.27, 701.8.
 FBC 106.1.1, 106.1.2 FOR CLARITY, COORDINATION AND
 INFORMATION ON THE RECORD PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-02-23 Cont ID  
Sent By dpalmer Date 2009-02-23 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2009-02-23 Time 18:23 Sent To  
Notes
2009-02-23 18:24:35** DENIED/ PASSED REVISIONS **
  
  
  
 1) NOTE: PLEASE SEE PROVISO ISSUED 12/17/08. ITEMS
 NUMBERS 2, 4 AND 5 NEED TO BE REVISED AT THIS TIME.
 THESE ARE NOT ITEMS FOR *AS BUILTS*.
 FOR INFORMATION.
 AS-BUILTS ARE PLANS MADE UP OF ALL REVISED PLANS ALONG
 THE PROGRESS OF THE PROJECT. THE CITY OF WEST PALM
 BEACH DOES REQUIRE REVISIONS HOWEVER NOT A FINAL SET OF
 AS-BUILDS.
  
 2) NOTE: THE POWER PLAN SHEET WAS OK, STAMPED.
  
 3) NOTE: COMMENTS FROM PROVISO WITH RESPECT TO
 CERTIFICATE OF AUTHORIZATION NUMBERS ON REQUIRED
 PREVIOUS PLANS IS STILL IN EFFECT. THIS WILL BE
 ADDRESSED WHEN SUBMITTING PLANS WHICH WERE NOT REVIEWED
 AND STAMPED. THIS IS FOR EQUIPMENT MANUFACTURE PLANS
 AND MANUFACTURES ELECTRICAL PLANS.
 FS 471.023,FAC 61G15-23.002. REVIEW OF SAID DOCUMENTS
 STILL NEEDS TO TAKE PLACE FOR CODE COMPLIANCE.
 110.3,90.7 ETC
  
 ** THIS REVIEW WILL REMAINED IN A FAILED STATUS EVEN AS
 POWER PLAN SHEET E105 IS OK.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-17 Cont ID  
Sent By dpalmer Date 2008-12-17 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2008-12-17 Time 11:44 Sent To  
Notes
2008-12-17 11:48:35** PROVISO/REDLINED PLANS***
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED AND SUBMITTED.
  
 1) NOTE: ELECTRICAL MANUFACTURER'S SHOP DRAWINGS WILL
 BE SUBMITTED AT LATER DATE ONCE CA # FROM STATE IS
 OBTAINED.
 FS471.023,FAC 61G15-23.002
  
  
 2) NOTE: THE RISER STILL INDICATES * EQUIPMENT
 GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF
 DISCONNECT FROM THE FPL TRANSFORMER WHICH IS NOT
 PERMITTED. THIS HAS BEEN NOTED IN ALL OF THE THREE
 PREVIOUS REVIEWS YET THE RISER NOTES HAVE NOT BEEN
 CORRECTED. THE RESPONSE LETTER MENTIONS REVISIONS WERE
 MADE HOWEVER THIS IS NOT THE CASE.
  
 3) NOTE: PLEASE SEE THE SUBMITTED ELECTRICAL PLANS FOR
 EQUIPMENT FROM ASSOCIATED ENGINEERS STILL DOES NOT HAVE
 ALL INFORMATION ON TITLE BLOCKS COMPLETE. IN FACT THE
 TITLE BLOCK WHERE THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER IS SUPPOSE TO BE STATES THE CA
 NUMBER IS PENDING. THESE MAY NOT BE PART OF THE
 SUBMITTED DOCUMENTS WITHOUT COMPLETE INFORMATION. THE
 TITLE BLOCKS ARE REQUIRED TO CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER ALONG WITH THE
 CERTIFICATE OF AUTHORIZATION NUMBER.\
 FAC 61G15-23.002, FS 471.023
  
  
 4) NOTE: THE STAIRS FROM THE MEZZANINE LEVEL STILL DO
 NOT INDICATE ANY LIGHTING MEETING EGRESS REQUIREMENTS.
 THE RESPONSE AND PER PHONE CONVERSATION PREVIOUSLY
 MENTIONED THIS WAS AND IS NOT AN EGRESS PATH REQUIRED
 OR OTHER WISE. THIS IS A MEANS OF ESCAPE AS DEFINE IN
 THE LIFE SAFETY CODE.
 IN ORDER NOT TO BE PART OF ANY EGRESS PATH SIGNAGE FOR
 DOOR MUST BE ON LIFE SAFETY PLANS AS WELL AS ELECTRICAL
 PLANS. PLEASE SEE NFPA-101
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS:
 NO
 EXIT
 7.10.8.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM ( IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
  
 5) NOTE: PLEASE CLARIFY JOCKEY PUMP WHICH RISER
 INDICATES 30AMP DISCONNECT FUSED AT 30AMPS YET BRANCH
 FROM ELP1 ONLY HAS 20AMP OCP WITH #12 CONDUCTORS.??
 240.4,310.16, 430.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
 *** PRO
  
 *** NOTED SEPARATE PERMITS FOR LIGHTNING PROTECTION,
 LOW VOLTAGE SYSTEMS, FIRE ALARM, FIRE SPRINKLER. THE
 BASE PLANS MAY BE REFERENCED FOR LOW VOLTAGE SYSTEM
 ONLY. SEPARATE PLANS WILL BE REQUIRED FOR LP, FS AND
 FA.
 THIS IS NOTED FOR REVIEW ONLY. NO RESPONSE OR CHANGES
 ARE NEEDED ON PLANS OR SUBMITTED DOCUMENTS.
  
  
 *** LETTER IN FILE WITH RESPECT TO BUILDING OCCUPANCY
 WHEN UNDER EMERGENCY BACK UP POWER. IN COMPLIANCE WITH
 FBC CHAPTER 10 AS WELL AS NFPA-101 THE BUILDING SHALL
 BE EVACUATED WHEN NORMAL POWER IS LOST INCLUDING ALL
 EMPLOYEEST. LETTER SUBMITTED SIGNED AND NOTARIZED FROM
 MR. PATRICK CARROLL DIRECTOR OF FACILITIES DEVELOPMENT
 IS IN FILE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-17 Cont ID  
Sent By dpalmer Date 2008-12-15 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2008-12-12 Time 17:10 Sent To  
Notes
2008-12-17 11:44:30** DENIED 3RD REVIEW **
  
 ** SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
 ** SOME OF THE ITEMS MAY BE ABLE TO BE SET UP AS PART
 OF A PROVISO/ISSUANCE WITH CONDITIONS HOWEVER SOME MUST
 BE ADDRESSED AT THIS TIME.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNER. THE CERTIFICATION SHEET CONTAINS A SIGNATURE
 AND DATE HOWEVER NOT SEALED WITH THE RAISED SEAL. THIS
 IS FOR BOTH THE MAIN FACILITY BUILDING AS WELL AND
 SCALE HOUSE.
  
 2) NOTE: PLEASE SEE THE CALCULATIONS FOR ELECTRICAL
 LIGHTING APPEAR TO SHOW NO GROSS ERRORS AS NOTED IN FBC
 13-103.3. HOWEVER PLEASE SEE THE SCALE HOUSE
 CALCULATIONS AS THESE MOST CERTAINLY COULD NOT BE
 SIGNED AS COMPLIANT BY ELECTRICAL WHEN THERE ARE ITEMS
 FOR OTHER TRADES LEFT COMPLETELY BLANK.
 SOME OF THESE EXAMPLES WOULD BE THE IDR INDICATES:
 NO WINDOWS YET THERE ARE WINDOWS ON THE BUILDING AND
 FENESTRATIONS ARE ALSO BLANK.
 NO DOORS, YET THERE ARE DOORS ON PLANS.
 FLOORS FOR ALL AREAS NOTED AS CARPET AND RUBBER
 PADDING. THIS IS NOT POSSIBLE. THERE ARE AREAS WITH
 TILE AND OTHER SURFACES WHICH ARE NOT CARPET AND RUBBER
 PADDING.
  
 ** THESE ITEMS ARE CLEAR TO THIS REVIEWER AS GROSS
 ERRORS AND THESE CALCULATIONS COULD NOT BE STAMPED BY
 ELECTRICAL AS CODE COMPLIANT WHETHER OR NOT THEY WERE
 SIGNED AND SEALED.
 ** THESE ITEMS NEED TO BE ADDRESSED WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEW STAFF.
  
 13-400.A.3, 13-401, 13-403, 13-405
  
 3) NOTE: THE RISER STILL INDICATES * EQUIPMENT
 GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF
 DISCONNECT FROM THE FPL TRANSFORMER WHICH IS NOT
 PERMITTED. THIS HAS BEEN NOTED IN ALL OF THE THREE
 PREVIOUS REVIEWS YET THE RISER NOTES HAVE NOT BEEN
 CORRECTED. THE RESPONSE LETTER MENTIONS REVISIONS WERE
 MADE HOWEVER THIS IS NOT THE CASE.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ELECTRICAL PLANS FOR
 EQUIPMENT FROM ASSOCIATED ENGINEERS STILL DOES NOT HAVE
 ALL INFORMATION ON TITLE BLOCKS COMPLETE. IN FACT THE
 TITLE BLOCK WHERE THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER IS SUPPOSE TO BE STATES THE CA
 NUMBER IS PENDING. THESE MAY NOT BE PART OF THE
 SUBMITTED DOCUMENTS WITHOUT COMPLETE INFORMATION. THE
 TITLE BLOCKS ARE REQUIRED TO CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER ALONG WITH THE
 CERTIFICATE OF AUTHORIZATION NUMBER.\
 FAC 61G15-23.002, FS 471.023
 ***PRO
  
 5) NOTE: THE STAIRS FROM THE MEZZANINE LEVEL STILL DO
 NOT INDICATE ANY LIGHTING MEETING EGRESS REQUIREMENTS.
 THE RESPONSE AND PER PHONE CONVERSATION PREVIOUSLY
 MENTIONED THIS WAS AND IS NOT AN EGRESS PATH REQUIRED
 OR OTHER WISE. THIS IS A MEANS OF ESCAPE AS DEFINE IN
 THE LIFE SAFETY CODE.
 IN ORDER NOT TO BE PART OF ANY EGRESS PATH SIGNAGE FOR
 DOOR MUST BE ON LIFE SAFETY PLANS AS WELL AS ELECTRICAL
 PLANS. PLEASE SEE NFPA-101
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS:
 NO
 EXIT
 7.10.8.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM ( IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
 *** PRO
  
 6) NOTE: PLEASE CLARIFY JOCKEY PUMP WHICH RISER
 INDICATES 30AMP DISCONNECT FUSED AT 30AMPS YET BRANCH
 FROM ELP1 ONLY HAS 20AMP OCP WITH #12 CONDUCTORS.??
 240.4,310.16, 430.
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
 *** PRO
  
 7) SEPARATE PERMITS FOR LIGHTNING PROTECTION, LOW
 VOLTAGE SYSTEMS, FIRE ALARM, FIRE SPRINKLER. THE BASE
 PLANS MAY BE REFERENCED FOR LOW VOLTAGE SYSTEM ONLY.
 SEPARATE PLANS WILL BE REQUIRED FOR LP, FS AND FA.
 THIS IS NOTED FOR REVIEW ONLY. NO RESPONSE OR CHANGES
 ARE NEEDED ON PLANS OR SUBMITTED DOCUMENTS.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-12-12 17:11:31REVIEW IS IN PROGRESS.
 REVIEW WILL BE GOING INTO FAILED STATUS ONCE COMPLETED
 AND NOTES WILL FOLLOW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-27 Cont ID  
Sent By dpalmer Date 2008-10-27 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2008-10-27 Time 16:49 Sent To  
Notes
2008-10-27 16:49:54 
 ** DENIED 2ND REVIEW**
  
  
 1) NOTE: PLEASE SEE THE LETTER SUBMITTED FOR THE
 BUILDING NOT TO BE OCCUPIED UNDER THE LOSS OF
 NORMAL/MAIN POWER IS TO BE REVISED. THE LETTER STATES
 THE FACILITY WILL NOT OPERATE HOWEVER THE LETTER NEEDS
 TO STATE THE BUILDING WILL NOT BE OCCUPIED BY ANY
 PERSONNEL. THE LETTER(S) NEED TO BE ORIGINAL AND
 NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARIES.
 NFPA-101 7.8, 7.9
  
 2) NOTE: THE PREVIOUS REVIEW REQUESTED THE REQUIRED
 ENERGY CALCULATIONS TO BE SUBMITTED. AS THEY WERE NOT
 SUBMITTED ON THE FIRST REVIEW THEY COULD NOT BE
 REVIEWED. PLEASE SEE THE ENERGY CALCULATIONS AND THE
 INPUT DATA REPORT NEED TO COORDINATE WITH THE PLANS.
 THE INPUT DATA REPORT WILL BE NOTED BELOW AS IDR.
 TWO SEPARATE CALCULATIONS WERE SUBMITTED. THE
 *CERTIFICATIONS* SHEETS NEED TO BE COMPLETED WITH THE
 SIGNATURE, DATE AND SEAL FROM THE RESPONSIBLE DESIGNER
 OF RECORD. THE COVER SHEET WAS SIGNED AND SEALED.
 EXAMPLES OF SOME INCONSISTENCIES OF THE SUBMITTED
 CALCULATIONS AND THE IDR WILL BE NOTED.
  
 FOR EXAMPLE: PLEASE SEE THE SQUARE FOOTAGE OF THE
 CALCULATION COVER SHEET SHOWS A TOTAL OF 7022 SQ FT
 TOTAL OF CONDITIONED AND UNCONDITIONED SPACE. THIS IS
 NOT POSSIBLE AS THE SQUARE FOOTAGE SHOWN ON A001CR1
 SHOWS NUMBERS FAR GREATER. THE SUBMITTED METHOD *A* IS
 FOR WHOLE BUILDING.
  
 FOR EXAMPLE: PLEASE SEE THAT NOT ALL EXTERIOR LIGHTS ON
 PLANS ARE IN THE IDR> ONE FIXTURE TYPE ALONE WOULD BE
 THE S-7. THIS IS A 70W FIXTURE BASE DON THE FIXTURE
 LEGEND AND THERE ARE NO 70W FIXTURES ON THE IDR FOR
 EXTERIOR LIGHTING. ** THESE ARE NOT EXEMPT EVEN IF FOR
 THE SIGN** PLEASE SEE THE FBC CHAPTER 13 IN ORDER TO
 FALL UNDER EXCEPTIONS FOR THESE NOT TO BE
 INCLUDED.13-415.2.ABC.1.3
 ** PLEASE SEE SHEET E123CR1 DOES NOT LIST THESE
 FIXTURES AS PART OF THE CONTROLS EVEN AS THE SITE PLANS
 CALL FOR SLP-25.
  
 FOR EXAMPLE: THE FIXTURE S2 IS A 400W FIXTURE HOWEVER
 THE IDR SHOWS 800W. IT WAS ASSUMED THAT EACH POLE WHICH
 CONTAINS TWO FIXTURES WERE COUNTED AS ONE AND THIS IS
 WHY THE IDR SHOWS 800W WHICH ACCOUNTS FOR BOTH
 FIXTURES. HOWEVER AS THE IDR SHOWS A TOTAL OF 6-800W
 FIXTURES, WHAT ABOUT THE FIXTURES ON THE POLES WHICH
 INDICATES ONLY ONE S2 FIXTURE?
 THIS WAS NOT ACCOUNTED FOR IN THE IDR.
  
 FOR EXAMPLE: THE IDR INDICATES ALL * UNCOVERED PARKING
 AREAS* AND THESE ASSOCIATED LIGHT FIXTURES. WHAT ABOUT
 ALL OF THE OTHER FIXTURES WHICH ARE EXTERIOR FIXTURES
 ON THE OUTSIDE OF THE BUILDING? BASED ON THE IDR, THE
 LIGHTING PLANS AND THE FIXTURE LEGEND NONE OF THESE
 FIXTURES WERE INCLUDED.
 SEE E FIXTURE ALONE WHICH IS AN EXTERIOR WALL PACK.
  
 FOR EXAMPLE: PLEASE SEE THE INTERIOR LIGHT FIXTURES AS
 THERE ARE SEVERAL FIXTURES ON THE PLANS WHICH ARE NOT
 IN THE IDR. ONE OF THESE ALONE WOULD BE THE TYPE *A*
 FIXTURE.
  
 ****** THESE ARE SOME EXAMPLES ONLY OF ITEMS ON THE
 ELECTRICAL PLANS WHICH ARE NOT COORDINATED WITH THE IDR
 AND THE SUBMITTED ENERGY CALCULATIONS. ALL AREAS,
 TYPES, WATTAGES ETC NEED TO MEET THE MINIMUMS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 *******
  
 3) NOTE: PLEASE BE MORE SPECIFIC TO THE TYPE OF
 OCCUPANCY SENSOR DEVICES. THE SYMBOL LEGEND DOES NOT
 EXPAND ON DEVICES FOR AREAS SUCH AS EGRESS PATHS WHICH
 ARE NOW ADDED TO PLANS.
 PLEASE INDICATE THE FAIL SAFE OPERATION FOR THESE
 DEVICES AS REQUIRED PER FBC 1006.1.2, NFPA-101
 7.8.1.2.2
 DEVICES IN THE FIRE PUMP ROOM, MAIN ELECTRICAL ROOM AND
 ELEVATOR EQUIPMENT ROOM ALSO NEED TO BE *FAIL SAFE ON*
 OPERATION ON OCCUPANCY SENSING DEVICES.
 PLEASE BE SURE THE SYMBOL LEGEND INDICATES THE TYPE AND
 MAXIMUM TIME.
  
 4) NOTE: PLEASE SEE THAT THE PREVIOUS REVIEW REQUESTED
 INFORMATION ON THE FIRE PUMP, CONTROLLER ETC. THE
 SUBMITTED PACKAGE DOES CONTAIN SHOP DRAWINGS/PRODUCT
 APPROVALS WHICH DO CONTAIN THE INFORMATION HOWEVER SOME
 OF THE SHEETS FOR THE FIRE PUMP ARE VERY FAINT AND NOT
 READABLE.
 PLEASE ALSO SHOW ON RISER, PLANS, SCHEDULE(S) WHERE AND
 HOW THE JOCKEY PUMP IS BEING FED. COULD NOT LOCATE THIS
 ON THE RISER ETC. SHEET E105CR1 INDICATES CIRCUITING TO
 LP2, THIS IS A LIFE SAFETY SYSTEM, PLEASE EXPLAIN WHY
 THIS IS NOT ON THE GENERATOR.
 PLEASE SEE SAME SHEET E105CR1 WHICH DRAWING NOTE #44
 INDICATES A 10HP FIRE PUMP. THIS SEEMS TO BE A
 MISPRINT?
 PLEASE BE SURE TO SEE NFPA-20 CHAPTERS 6 AND 7 AND ALSO
 SEE NFPA-70 695.6.C.1, 695.5 A, B.
  
 5) NOTE: PLEASE SEE THE SHEET E120C WHICH STILL SHOWS
 THE PREVIOUS RISER WHICH INDICATED THE NUMEROUS MAINS
 AND OTHER ITEMS FROM PREVIOUS REVIEW WHICH HAVE NOW
 BEEN REVISED.
 PLEASE COORDINATE PLANS/SHEETS.
 THE PREVIOUS NOTES GAVE SOME EXAMPLES OF COORDINATION
 NEEDED.
 EXAMPLE: PLEASE SEE E119C WHICH NOTES 3,4 AND 5
 INDICATE TWO PANELS AND A TRANSFORMER WHICH IS NOT ON
 THE PRIMARY RISER SHEET. THERE ARE NO PANEL SCHEDULES
 FOR THESE TWO PANELS ON THE SHEETS WITH THE OTHER PANEL
 SCHEDULES AND THE 112.5 KVA TRANSFORMER IS NOT LISTED
 ON EITHER OF THE TWO TRANSFORMER SCHEDULES ON SHEET
 E107CR1 YET THIS IS NOTED ON SHEET E120C. PLEASE
 EXPLAIN THE WORK SHOWN ON THESE OTHER SHEETS. ARE THESE
 PERMITTED UNDER THIS SAME PERMIT OR SCOPE OF WORK?
 NEC 230,240, 250, 215.5, 450ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: NEW NOTE: PLEASE EXPLAIN SUPPLEMENTAL LIGHTING
 PLAN.
 NEC 2005
 FBC 106.1.1 FOR ADDITIONAL INFORMATION/CLARITY
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2, AND .1.3.
 THE OVER RIDES INDICATED ARE NOTED ON PLANS WITH NOTES
 FOR LABELS AND PHONETIC LETTERING HOWEVER PLEASE SEE
 SECTIONS NOTED. THE CODE REQUIRES THE OCCUPANT TO SEE
 ALL LIGHTING WHICH IS BEING OVER RIDDEN OR MEET THE
 EXCEPTION WHICH IS NOT ONLY DETAILED SIGNAGE FOR ALL
 AREAS BEING OVER RIDDEN BUT ALSO FOR REQUIRED *PILOT
 LIGHTS* OR * INDICATOR LIGHTS* OF SOME KIND.
  
 8) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 OF PREVIOUS
 NOTES WITH RESPECT TO EGRESS LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 SOME LEVELS SHOWN ARE INDICATING LEVELS OF AVERAGE
 BELOW THE 10FT CANDLES UNDER NORMAL CONDITIONS. THIS
 LEVEL OF LIGHTING SHOULD BE FIGURED FROM THE STAIR
 AREAS ONLY AND NOT FIGURING IN OTHER AREAS OF AVERAGE.
 IF THERE ARE FIXTURES WHICH CONTRIBUTE TO THE LIGHTING
 LEVELS THEN PLEASE CALL TO GO OVER CONTRIBUTIONS. THE
 RESPONSE LETTER MENTIONS SOME STAIRS ARE NOT EGRESS
 LOCATIONS USED FOR EXITING.
 PLEASE SEE THE LIFE SAFETY CODE AS THE LIGHTING LEVEL
 DOES APPLY TO EGRESS PATHS FOR ALL NOT ONLY THE GENERAL
 PUBLIC.
 PLEASE SEE NFPA-101 7.10.8.3,.3.1 AND .3.2 WHICH
 REQUIRES SIGNAGE FOR ANY DOOR WHICH IS NOT AN EXIT DOOR
 TO BE LABELED AS SUCH. PLEASE SEE SECTIONS FOR MINIMUM
 SIZE AND WORDING.
  
 9) NOTE: MSB ON SHEET E120C STILL INDICATES GFIC
 PROTECTION. RESPONSE AND OTHER SHEETS WERE REVISED TO
 GFP FOR PROTECTION OF MAIN SWITCH GEAR EQUIPMENT.
  
 10) NOTE: PLEASE SEE THE RISER IS STILL SHOWING
 EQUIPMENT GROUNDING FROM FPL TRANSFORMER TO THE FIRST
 MEANS OF DISCONNECT WHICH IS NOT PERMITTED. THE
 RESPONSE MENTION FIRE PUMP CALCULATIONS PROVIDED AND
 THE MISINTERPRETATION OF THE CODE WITH RESPECT TO THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.24C REQUIRES THE *GROUNDED* CONDUCTOR TO BE BROUGHT
 TO THE FIRST MEANS OF DISCONNECT. AS THE CODE REQUIRES
 BINDING OF THE GROUNDING CONDUCTOR AT THE FIRST MEANS
 OF DISCONNECT IF AN *EQUIPMENT GROUNDING* CONDUCTOR IS
 IN THE SAME CONDUIT THIS WOULD CREATE OBJECTIONABLE
 CURRENTS PER 250.6.
 ** PLEASE CALL TO GO OVER AS THERE MUST BE A LOSS IN
 COMMUNICATION.
 ** RESPONSE ALSO MENTIONS THE PLANS/RISER WAS REVISED
 HOWEVER THE PLANS/RISER STILL INDICATES THE SAME.
  
 11) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 REQUIRED DEDICATED CIRCUITS FOR ELEVATOR EQUIPMENT
 ROOMS. 645.23,22,24.
 RESPONSE MENTIONS THE PLANS AND PANEL SCHEDULES HAVE
 BEEN REVISED HOWEVER PLEASE SEE SHEET E105CR1. BASED ON
 PLANS RECEPTACLES FED FROM RP2-35 ARE NOT MEETING THIS
 REQUIREMENT.
  
 12) NOTE: NEW NOTE: PLEASE PLACE NOTE ON PLANS FOR THE
 *COMMUNICATION ROOM*. AS THIS IS NOT AN IT ROOM BY
 DEFINITION IN NEC 645.2 PLEASE PLACE NOTE ON PLANS
 WHICH STATES * NO WIRING METHODS FROM NEC 645
 PERMITTED*
  
 13) NOTE: NOW THAT THE PLANS INDICATE THE GENERATOR
 LOCATED OUTSIDE PLEASE SEE NFPA-110 CHAPTER 7 FOR THE
 INSTALLATION REQUIREMENTS OF OUTDOOR UNITS. PLEASE
 INDICATE THE ELEVATION MEETING THE SLOSH CHARTS/100
 YEAR FLOOD. 7.3
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 16:29 Sent To  
Notes
2008-08-01 08:26:49** NOTE ADDED
  
  
 ** ALL CIRCUITING FOR EMEGENCY LIGHTING SHALL MEET
 700.12F. MANY LOCATIONS ON PLANS DO NOT MEET THE
 EXCEPTIONS IN THE CODE.
2008-07-30 16:29:24 
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** DENIEDAUDIT **
  
 *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND
 DOCUMENTATION NOT SUBMITTED DOES NOT COMPLETE PACKAGE
 FOR AUDIT AND DOES NOT PROVIDE THE MINIMUM REQUIRED BY
 THE FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE LAWS
 AND ORDINANCES.
  
 1) NOTE: *** PLEASE KNOW ALL PLANS AND DOCUMENTS WILL
 BE RETAINED BY THIS OFFICE. PLANS AND SUPPORTING
 DOCUMENTS MAY BE FORWARDED TO THE LICENSING BOARD FOR
 BUILDING CODE ADMINISTRATORS AND INSPECTORS BOARD ALONG
 WITH FLORIDA BOARD OF ENGINEERS FOR REVIEW OF SAID
 PLANS AND DOCUMENTS.
  
 2) NOTE: PLEASE SEE THERE ARE SEVERAL DOCUMENTS IN
 PACKAGE SUBMITTED IN WHICH RAISED SEALS ARE PLACED OVER
 PHOTO-COPIED SIGNATURES AND DATES. THIS IS NOT
 PERMITTED UNDER FAC 61G15-23.002 AND FS 471.025. PLEASE
 KNOW THIS SAME COMPANY IN WHICH MANY OF THESE DOCUMENTS
 WERE DONE THIS MANOR HAS BEEN NOTIFIED ON PREVIOUS
 PROJECTS THAT THIS IS NOT ACCEPTABLE UNDER FLORIDA LAW
 HOWEVER THIS IS STILL BEING DONE.
  
 3) NOTE:PLEASE PROVIDE AFFIDAVITS AS REQUIRED PER FS
 553.791 FOR EACH TRADE WHERE EACH AFFIDAVIT ACTUALLY
 DOES LIST THE SHEETS.
 PLACING ONE AND NOTING SEE ATTACHED IS NOT ACCEPTABLE.
  
  
 4 NOTE: PLEASE PROVIDE NOTICE TO BUILDING OFFICIAL AS
 REQUIRED. FS553.791
  
 5) NOTE: PLEASE DO NOT SUBMIT REVISION TO THE STAMPED
 PLANS WHEN THE
  
 6) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS/LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 *** IT IS IMPORTANT TO KNOW THAT INFORMATION AND
 DOCUMENTATION IS NOT COMPLETE.
  
 7) NOTE: PLEASE KNOW THE LIGHTING PROTECTION SYSTEM
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS AND SHALL
 CONTAIN NOTES AND DESIGN PER NFPA-780.
  
 8) NOTE: AN AUDIT OF SIGNED, DATED AND SEALED
 ELECTRICAL PLANS WAS NOT DONE AS NONE OF THESE CONTAIN
 ANY STAMPS FROM THE PRIVATE PROVIDER.
 FS 553.791
  
 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE
 PROVIDE ALL MINIMUM LEVELS FOR FIRE ALARM DEVICES TO
 MEET ADA REQUIREMENTS. PLEASE BE SURE TO STATE THE
 LEVELS OF DEVICES.
  
 10) NOTE: THE PLANS AND NOTES MENTIONS AUTOMATE
 LIGHTING CONTROL SYSTEMS WITH CONTACTORS HOWEVER
 COMPLETE DETAILS OF SYSTEMS, OVER RIDES, OVER RIDE
 TIMES ETC ARE NOT LOCATED ON PLANS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS INCLUDING
 MEZZANINE LIGHTING WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS FOR AUTOMATED SYSTEMS. THESE AREAS DO INDICATE
 STANDARD SWITCHING DEVICES WHICH DO NO MEET
 13-415.1.ABC.1.1,.1.2, .1.3.
 PLEASE ALSO SEE OTHER LOCATIONS ON E-112
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE SEVERAL
 SECTIONS ON PLANS WHICH DO NOT MEET MINIMUM CODE
  
 11) NOTE: PLEASE PROVIDE COMPLETE INFORMATION ON
 LIGHTING CONTROLS FOR EXTERIOR LIGHTING MEETING FBC
 13-415.1.ABC.1.4
  
 11) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1, .1.2
  
 12) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1,.2.2.
  
 13) NOTE: PLEASE SEE SOME AREAS AS NOTED ON SHEET E102
 MENTION TO SEE E112, HOWEVER THESE SAME AREAS WHICH
 MENTION TO SEE ENLARGED PLANS ARE NOT SHOWN. PLEASE SEE
 SOME OF THESE AREAS ARE BREAK ROOM, BATHROOMS ETC WHICH
 ARE NOT ON E112.
  
 14) NOTE: PLEASE COMPLETE AND COORDINATE ALL SYMBOLS ON
 PLANS. THIS INCLUDES ALL DEVICES SHOWN FOR LIGHTING
 CONTROLS WHICH ARE NOT ON SYMBOL LEGEND. AN EXAMPLE OF
 THIS IS SM.
 FBC 13-415, NEC ALL
 FBC 106.1.1 FOR CLARITY OF PLANS AND MINIMUM
 INFORMATION. 106.3.5.1.2
  
 15) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS TO MEET
 THE MINIMUM FOR LIFE SAFETY FOR ALL EGRESS PATHS.
 PLEASE SEE SOME AREAS SUCH AS STAIRS INCLUDING THAT OF
 EXTERIOR STAIRS DO NOT SHOW ANY BATTERY BACK UP
 LIGHTING AS REQUIRED.
 PLEASE SEE SECTIONS 7.8.1.3,7.9.2.1,79.2.2.
 FAC 61G15-33.004
 ** EGRESS LIGHTING SHALL BE PROVIDED UNDER NORMAL AND
 EMERGENCY CONDITIONS OUT OF THE BUILDING. PLEASE BE
 SURE TO SEE THE LEVELS DID INCREASE UNDER THE 2003
 NFPA-101
  
 16) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM FOR THIS TRADE. FBC
 2004 W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-20
 2002 NFPA-110
  
 17) NOTE: PLEASE COMPLETE ALL INFORMATION ON PLANS FOR
 FIRE PUMP, FIRE PUMP CONTROLLER. PLEASE KNOW AS THE
 INFORMATION ON THE FP IS NOT COMPLETE PLEASE SUBMIT
 COMPLETE PLANS FOR MINIMUM. PLEASE KNOW THAT CHAPTERS
 OF THEN CODES WILL BE CITED NOT SECTIONS AS THERE TOO
 MANY SECTIONS OF THE CODE MISSING.
 PLEASE INDICATE LOCK ROTOR MAXIMUM OVER CURRENT
 PROTECTION.
 PLEASE SEE NFPA-70 695.4B1 (1) OVER-CURRENT DEVICE
 SELECTION THE OVER-CURRENT PROTECTIVE DEVICE(S) SHALL
 BE SELECTED OR SET TO CARRY INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR CURRENT OF THE FIRE PUMP MOTOR(S) AND THE
 PRESSURE MAINTENANCE PUMP MOTOR(S) AND THE FULL-LOAD
 CURRENT OF THE ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY. THE REQUIREMENT TO
 CARRY THE LOCKED-ROTOR CURRENTS INDEFINITELY SHALL NOT
 APPLY TO CONDUCTORS OR DEVICES OTHER THAN OVER-CURRENT
 DEVICES IN THE FIRE PUMP MOTOR CIRCUIT(S).
  
 PLEASE SEE NFPA-20 CHAPTERS 9, 10 ETC
 PLEASE SUBMIT MANUFACTURES SPEC/CUT SHEETS FOR THE FIRE
 PUMP AND FIRE PUMP CONTROLLER.
 110.3,90.7, NFPA-20.
 ** AS PLANS AND INFORMATION IS NOT COMPLETE MANY ITEMS
 FOR MINIMUM CODE COMPLIANCE CAN NOT BE DETERMINED AT
 THIS TIME.
  
 18) NOTE: PLEASE SEE 230.2 AS THE NUMBER OF SERVICES
 SHOWN ON PLANS ARE NOT PERMITTED AND NOT ALL MEET THE
 EXCEPTIONS IN THE CODE AT THIS TIME.
 PLEASE LOOK AT RISER AS THE EQUIPMENT FED FROM MSB ARE
 BEING NOTED AS *MAINS*.
  
 19) NOTE: PLEASE SEE 230.95, 240.13 AS THE 3000AMP MAIN
 INDICATE GFIC PROTECTION. SHOULD THIS NOT BE GFP FOR
 GROUND FAULT PROTECTION? GFCI IS FOR PERSONNEL.
  
 20) NOTE: PLEASE SUBMIT AND SHOW A COMPLETE GROUNDING
 ELECTRODE RISER FOR ALL TRANSFORMERS AND COMMON
 SYSTEM.
 250.58, 250.66
  
 21) NOTE: PLEASE SEE THERE ARE LOCATIONS WHERE
 EQUIPMENT GROUNDING CONDUCTORS ARE BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE CLARIFY THE #4 TO FIRE PUMP CONTROLLER. PLEASE
 BE SURE TO SIZE THE NEUTRAL (GROUNDED CONDUCTOR) AS
 THIS IS REQUIRED TO CONTAIN A NEUTRAL TO THE FIRST
 MEANS OF DISCONNECT. IN NO CASE MAY THIS BE SMALLER
 THAN THE GROUNDING ELECTRODE
 CONDUCTOR.250.4,250.6,250.50,ETC
 THIS IS ALSO NOTED FOR THE 3000AMP MAIN AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS ALSO SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT WHICH IS NOT PERMITTED. THIS
 CREATES OBJECTIONABLE CURRENTS.
  
 22) NOTE: PLEASE SEE 230.95, 240.13, 700.7D, 700.26,
 NFPA-110 6.2.1.5
 AS THE TRANSFER SWITCH ON PLANS DOES NOT INDICATE HOW
 MANY POLES. BASED ON THE CODE SECTIONS GIVEN THIS IS
 REQUIRED TO BE A FOUR POLE UNIT. THE FOLLOWING TEXT MAY
 BE OF USE FOR THE TRANSFER SWITCH. THIS WORDING IS FROM
 ONE WHITE PAPER FROM ONE MANUFACTURE AND THERE ARE
 SEVERAL OTHERS AVAILABLE.
  
 *WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE CODE
 AND AN ALTERNATE POWER SUPPLY IS INCLUDED, SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT SHOWN ABOVE
 ILLUSTRATES SUCH A CIRCUMSTANCE.
 THE SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY,
 GROUND FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING
 THE LOAD WILL CAUSE THE MAIN SERVICE DISCONNECT TO
 OPEN. THIS WILL NOT DISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS LOST.*
  
 THIS WAS FROM ASCO WHITE PAPER PAGE #5. OTHERS SUCH AS
 CATERPILLAR ETC HAVE MUCH OF THE SAME.
  
  
 23) NOTE: PLEASE SEE NFPA-110 9.6.2.2 AND INDICATE THE
 MINIMUM TIMES FOR ON-SITE FUEL AS REQUIRED FOR POWER
 FOR FIRE PUMP ALONG WITH OTHER EMERGENCY LOADS. 9.6.2.2
 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE
 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT OF THE
 RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY REQUIRED
 FOR OTHER DEMANDS.
  
  
 24) NOTE: PLEASE KNOW BATTERY BACK UP LIGHTING SHALL BE
 REQUIRED FOR THE EGRESS LIGHTING PATHS PER NFPA-7.8,
 7.9.PLEASE KNOW THIS BUILDING SHALL NOT RELY ON THE
 SINGLE TRIPPING OF A BREAKER, SWITCHING OF A DEVICE TO
 LEAVE ANY ONE ARE IN TOTAL DARKNESS.
 PLEASE BE SURE OTHER LOCATIONS SUCH AS THE MAIN
 ELECTRICAL ROOM, FIRE PUMP ROOM, ELEVATOR EQUIPMENT
 ROOM ALSO CONTAIN BATTERY BACK UP LIGHTING.
  
 25) NOTE: PLEASE SUBMIT THE PLANS WITH THE COMPLETED
 INFORMATION FOR LOCATION OF THE GENERATOR. THE RISER
 SHOWS A GENERATOR HOWEVER WHERE IS THIS UNIT GOING TO
 BE INSTALLED? PLEASE SEE OTHER PLANS SUCH AS SITE,
 MECHANICAL, BUILDING ETC DO NOT SHOW ANY LOCATIONS.
  
 26) NOTE: PLEASE SEE NEC 645.,23AS THE MINIMUM
 REQUIRED DEDICATED CIRCUITS ARE NOT LOCATED ON PLANS.
 IN FACT ONE EXAMPLE OF NON-COMPLIANCE IS THE FACT THE
 LIGHTING IN THE MACHINE ROOM WHICH IS REQUIRED TO BE ON
 A DEDICATED CIRCUIT PER 620.23 IS SHOWN CIRCUITED TO
 OTHER NORMAL LIGHTING OUTSIDE OF THIS ROOM.
 PANEL SCHEDULE INDICATES OTHERS PER 620.22, 620.24
 HOWEVER PLANS DO NOT SHOW SOME OF THESE CIRCUITS,
 LIGHTS, PIT LIGHTING, GFI RECEPTACLES ETC. RECEPT SHOWN
 HOWEVER SECTIONS AS NOTED REQUIRE GFCI PROTECTION. THIS
 IS NO ON PLANS OR ON PANEL SCHEDULE
 IF THE PANEL SCHEDULE ONLY INDICATES *RECEPTACLES FOR
 EXAMPLE ON RP1-16 THE DEDICATE CIRCUIT IS NOT
 DETERMINED
  
  
 27) NOTE: PLEASE SEE NFPA-110 CHAPTER 7, 7.3.3 AS THE
 MINIMUM LIGHTING IN ANY GENERATOR ROOM SHALL MEET THIS
 MINIMUM.
 PLEASE KEEP IN MIND AS THE GENERATOR IS NOT SHOWN THIS
 IS GIVEN FOR INFORMATION ONLY.
 PLEASE SEE THE FOLLOWING FOR LOCATION AS THIS WAS NOT
 SHOWN AT THIS TIME.
  
 7.2 LOCATION.
 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED
 OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY
 LOCAL BUILDING CODES.
 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1 TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS
 HOUSING LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE
 DESIGNED AND LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE FOLLOWING: (1)
 FLOODING RESULTING FROM FIRE FIGHTING
 (2)SEWER WATER BACKUP
 (3)SIMILAR DISASTERS OR OCCURRENCES
 7.2.4*MINIMIZING THE POSSIBILITY OF DAMAGE RESULTING
 FROM INTERRUPTIONS OF THE EMERGENCY SOURCE SHALL BE A
 DESIGN CONSIDERATION FOR LEVEL 1 AND LEVEL 2 EPSS
 EQUIPMENT.
 7.2.5 THE EPS EQUIPMENT SHALL BE INSTALLED IN A
 LOCATION THAT PERMITS READY ACCESSIBILITY AND A MINIMUM
 OF 76 CM (30 IN.) FROM THE SKID RAILS' OUTERMOST POINT
 IN THE DIRECTION OF ACCESS FOR INSPECTION, REPAIR,
 MAINTENANCE, CLEANING, OR REPLACEMENT. THIS REQUIREMENT
 SHALL NOT APPLY TO UNITS IN OUTDOOR HOUSINGS.
  
 28) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION ON THE TRANSFORMER TRP1 SHALL BE 125% UNLESS
 MEETING EXCEPTIONS. AS THE PLANS DO NOT INDICATE WHAT
 TYPE OF UNIT THIS IS PLEASE SEE SECTION AS NOTED.
  
 29) NOTE: PLEASE SEE 408.4 AS THE CIRCUITS SHOWN ON
 PANEL SCHEDULES SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. STATING *RECEPTACLES* OR *LIGHTING* IS
 NOT ACCEPTABLE. PLEASE KNOW A NUMERICAL OR ALPHA
 DESIGNATION MAY BE USED.
  
 30) NOTE: PLEASE INCLUDE FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50.
  
 31) NOTE: PLEASE SEE RISER AS ERP1 INDICATES A FEED TO
 PANEL ERPSH HOWEVER THE PANEL SCHEDULE FOR ERP1 DOES
 NOT INDICATE ANY SUB FEED FOR PANEL ERPSH.
 PLEASE COMPLETE WITH OCP, CONDUCTORS, LOADS ETC.
 408.4,310.16,240.4,220,ETC
  
 32) NOTE: PLEASE SUBMIT AND SHOW COMPLETE LOAD
 CALCULATIONS PER NEC 220.
 PLEASE BE SURE ALL CONTINUOUS LOADS ALONG WITH LARGEST
 MOTOR LOADS ARE FIGURED SHOWN AT 125%.
 PLEASE BE SURE THE WATER HEATER LOADS ARE FIGURED AND
 SHOWN AT 125%. 220,12,220.14,220.42,,220.44,220.50, ETC
 215.3,230.42, 422.13 FOR CONTINUOUS LOADS.
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND MINIMUM
 REQUIRED ON PLANS.
  
 33) NOTE: PLEASE SEER RISER AS LPSH INDICATES A FEED TO
 PANEL RPSH YET THERE IS NO BREAKER, LOAD, CIRCUIT
 LISTED ON PANEL LPSH FOR THIS NEW PANEL.
 PLEASE COMPLETE.
 240.4,220,310.16 ETC
  
 34) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE
 RISER/DIAGRAM FOR SCALE HOUSE PER
 250.50,250.30,250.32.
  
 35) NOTE: PLEASE SEE THE RISER SHOWS THE TRANSFORMER AT
 THE SCALE HOUSE AS TRP-SH WHICH BY THE TRANSFORMER
 CALLS FOR THIS UNIT AS A 30KVA UNIT YET THE LEGEND AND
 PLANS ON SHEET E-112 INDICATES THIS SAME UNIT AT THE
 SCALE HOUSE IS SHOWN AS 15KVA.
 PLEASE KNOW AS BOTH UNITS ARE SHOWN WITH TWO DIFFERENT
 SIZES THE OVER CURRENT PROTECTION ETC CAN NOT BE
 DETERMINED AS CODE COMPLIANT.
 PLEASE COORDINATE
 450.3, 240.21, 310.16, 240.4 ETC.
  
 36) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM PART ROOM
 PLAN WHICH INDICATES ANOTHER 15KVA TRANSFORMER YET THE
 ELECTRICAL TRANSFORMER LEGEND ON SHEET ON E-107 DOES
 NOT INDICATE ANY 15K TRANSFORMERS. AS THESE DOE NOT
 COORDINATE DETERMINATION FOR CODE COMPLIANCE CAN NOT BE
 DONE.
 240.21,450.3,310.16 ETC
 FBC 106.1.1 FOR COORDINATION AND CLARITY OF PLANS.
  
 37) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE ATS, GENERATOR, AS NOTED ABOVE FOR OTHER
 EQUIPMENT. 110.3,90.7
  
  
 ** PLEASE KNOW AS THERE IS INFORMATION AND
 DOCUMENTATION NOT YET SUBMITTED FOR AUDIT THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING AUDIT WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-11-19 Cont ID  
Sent By mgonzale Date 2008-11-19 Time 10:55 Rev Time 1.00
Received By mgonzale Date 2008-11-19 Time 10:54 Sent To  
Notes
2008-11-19 10:55:03- PASSED -
  
 ENGINEER HAS COMPLIED WITH ALL REQUESTS SET FORTH BY
 THE ENGINEERING DEPT.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR (561) 494-1040
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 CITY'S WEB SITEHAS ALL OUR REFERENCE MATERIAL YOU NEED
 TO COMPLY:
 FEEL FREE TO SEE THE LINKS BELOW:
 WWW.CITYOFWPB.ORG
  
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-11-05 Cont ID  
Sent By mgonzale Date 2008-11-05 Time 12:43 Rev Time 1.00
Received By mgonzale Date 2008-11-05 Time   Sent To ENG
Notes
2008-11-05 12:42:56ENGINEER HAS POMPLIED WITH ALL REQUESTS SET FORTH BY
 THE ENGINEERING DEPT. INCLUDES WATER, SEWER AND STORM
 ISSUES.
 MANNY GONZALEZ, PROJECT COORDINATOR
 CITY OF WPB ENGINEERING (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By rchokshi Date 2008-09-23 Time 10:46 Rev Time 0.00
Received By rchokshi Date 2008-09-23 Time 10:41 Sent To  
Notes
2008-09-23 10:46:04FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OF POLLUTION PREVENTION . PLEASE SHOW
 ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE, &
 TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE. HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By rchokshi Date 2008-07-24 Time 11:08 Rev Time 0.00
Received By rchokshi Date 2008-07-24 Time 11:04 Sent To  
Notes
2008-07-24 11:08:18FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OFPOLLUTION PREVENTION . PLEASE
 SHOW ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE,
 & TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE.HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
 STORM WATER CALS APPROVED PER DEAN L'S E-MAILPERMIT#
 08050249
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS TO 1000
 45TH STREET FOR THEIR APPROVAL BEFORE WE APPROVE.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-05-26 Cont ID  
Sent By mawillia Date 2009-05-26 Time 09:31 Rev Time 0.00
Received By mawillia Date 2009-05-26 Time 09:03 Sent To  
Notes
2009-05-26 09:12:55*****REVISIONS, DATED 04/24/09, APPROVED*****
  
  
 OF THE SUBMITTED NINE REVISED SHEETS, SHEETS E103CR2,
 E105CR5, AND E112CR3 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 11:09 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 10:34 Sent To  
Notes
2009-04-06 10:44:19*****REVISIONS, DATED 03/27/09, APPROVED*****
  
  
 REVISED PLAN SHEETS A103CR4, A106CR3, A118CR5, A901CR5,
 E104CR5, AND E105CR4 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-04-06 Cont ID  
Sent By mawillia Date 2009-04-06 Time 10:33 Rev Time 0.00
Received By mawillia Date 2009-04-06 Time 10:03 Sent To  
Notes
2009-04-06 10:33:09*****SUBMITTAL APPROVED*****
  
  
 RFI 244 - HORN STROBE MOUNTING ELEVATION IN PUSH WALLS
 WAS BLOCK STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-03-10 Cont ID  
Sent By mwennerg Date 2009-03-10 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2009-03-10 Time 10:33 Sent To  
Notes
2009-03-10 10:34:43REVISION #4 DATED 2/24/09 STAMPED SHEET A901CR4.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-02-24 Cont ID  
Sent By mawillia Date 2009-02-24 Time 14:20 Rev Time 0.00
Received By mawillia Date 2009-02-24 Time 13:35 Sent To  
Notes
2009-02-24 13:37:15*****REVISION #3, DATED 1/18/09, APPROVED*****
  
  
 PLAN SHEETS A103CR3, A106CR2, A113CR3, AND A118CR3 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-17 Cont ID  
Sent By mawillia Date 2008-12-17 Time 14:40 Rev Time 0.00
Received By mawillia Date 2008-12-17 Time 14:27 Sent To  
Notes
2008-12-17 14:39:56*****APPROVED*****
  
  
 PLAN SHEETS A002CR1, A103CR2, A104C, A106CR1, A113CR2 &
 A114CR2, A118CR2, A123C, C001CR3, C004CR2, E102CR2,
 E111CR2, FP101CR1 THRU FP103CR1, AND FP104C & FP105C
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-04 Cont ID  
Sent By mwennerg Date 2008-11-04 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2008-11-04 Time 11:17 Sent To  
Notes
2008-11-04 11:26:51***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING FROM THE PREVIOUS REVIEW FOR
 CORRECTION OR FURTHER CLARIFICATION:
  
 1) OK- PLEASE ADD NFPA 101, 2003 TO THE CODE ANALYSIS
 ON SHEET A901CR1.
  
 19) OK- PLEASE ILLUSTRATE THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION(S) ON SHEET CO12CR1.
  
 20) PLEASE ILLUSTRATE THE LOCATION OF THE DOUBLE CHECK
 DETECTOR ASSEMBLY AND ADD NOTE REGARDING CHAIN AND LOCK
 REQUIREMENT IN ADDITION TO ELECTRONIC SUPERVISION.
  
 23) EXIT SIGN IS STILL MISSING ON SHEET E102CR1.
  
 ADDITIONAL NOTE FOR CLARIFICATION:
 HOSE STATIONS SHALL BE PROVIDED WITH 2 1/2" - 1 1/2"
 CONNECTIONS WITH CHAINS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-08 Cont ID  
Sent By mwennerg Date 2008-08-08 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2008-08-08 Time 10:55 Sent To  
Notes
2008-08-08 11:24:15***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 2) ADDRESS ON BUILDING SHALL BE MINIMUM 6" IN HEIGHT,
 1" WIDTH AND CONTRASTING WITH BACKGROUND. PLEASE ADD TO
 ELEVATIONS.
  
 3) KNOX BOX TO BE LOCATED AT WHAT IS CONSIDERED TO BE
 FRONT ENTRANCE TO BUILDING. CONTACT WPBFR BUREAU OF
 FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 4) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 5) EMERGENCY VEHICLE ACCESS AND WATER SUPPLY TO COMPLY
 WITH NFPA 1, 2003, CHAPTER-18.
  
 6) ELEVATOR SHALL COMPLY WITH REQUIREMENTS OF ASME
 A17.1.
  
 7) FIRE RATED DOORS SHALL BE PROVIDED WITH UL LISTED
 DOOR CLOSERS TO CREATE POSITIVE LATCH. DOOR SCHEDULE ON
 SHEET A118C.
  
 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 9) A FACTOR OF .2" PER PERSON HAS BEEN CALCULATED ON
 SHEET A901C FOR STAIRWAYS. PLEASE NOTE THAT TABLE
 7.3.3.1 NFPA 101 USES A FACTOR OF 0.2" FOR LEVEL
 COMPONENTS AND RAMPS AND 0.3" FOR STAIRWAYS. THIS WILL
 HAVE AN OVERALL IMPACT ON CALCULATIONS.
  
 10) PLEASE EXPLAIN FACTOR OF .15 FOR DOOR EGRESS.
 PLEASE NOTE LAST COMMENT REGARDING LEVEL COMPONENTS.
  
 11) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH REQUIREMENTS OF NFPA 241.
  
 12) CLARIFY OCCUPANT CLASSIFICATION FOR EACH AREA.
 MODERATE HAZARD IS INDICATED IN CODE ANALYSIS UNDER USE
 OF OCCUPANCY. ADDITIONALLY, PLANS INDICATE VARIOUS
 PROCESSING AREAS WHICH SEEMS TO SUGGEST INDUSTRIAL
 USE.
  
  
 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 14) FIRE ALRM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
 15) PENETRATIONS INTO EXIT ENCLOSURES SHALL BE LIMITED
 AND IN COMPLIANCE WITH SEC. 7.1.3.2 (6), NFPA 101.
 SHEET M102C
  
 16) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 17) NEW FIRE DAMPERS TO BE TESTED FOR CLOSURE IN
 ACCORDANCE WITH THE REQUIREMENTS OF UL 555.
  
 18) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR
 PROPOSED FIRE PUMP.
  
 19) KNOX LOCKING CAPS ARE REQUIRED FOR FIRE DEPARTMENT
 CONNECTION. SHEET FP 103C
  
 20) PROVIDE DETAIL FOR DOUBLE CHECK DETECTOR ASSEMBLY.
 IN ADDITION TO ELECTRONIC SUPERVISION, CONTROL VALVES
 TO BE SECURED WITH CHAIN AND LOCK.
  
 21) PROVIDE LOCATION OF AND MANUFACTURER SPECIFICATIONS
 FOR GENERATOR.
  
 22) PLEASE SHOW LOCATION OF NEW FIRE HYDRANTS THAT
 SHALL BE OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 23) EXIT SIGN IS MISSING AT EXTERIOR CORRIDOR DOOR
 BETWEEN THE LOCKERS AND TOOL/EQUIPMENT ROOM. ELECTRICAL
 LIGHTING SHEET
  
 24) FIRE ALARM RISER DOES NOT APPEAR TO ILLUSTRATE
 SMOKE DETCTION DEVICES WITH EXCEPTION OF AIR DUCTS.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON EACH
 SHEET EACH COMMENT WAS ADDRESSED WILL HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-16 Time 08:37 Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 08:36 Sent To  
Notes
2009-09-22 08:38:45ELECTRICAL COORDINATION STUDY, GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 07:45 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 07:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-07-10 Cont ID  
Sent By lmartine Date 2009-07-10 Time 16:30 Rev Time 0.00
Received By lmartine Date 2009-07-10 Time 16:30 Sent To  
Notes
2009-07-10 16:31:08GAVE TO ROBERT BROWN

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 08:25 Sent To  
Notes
2009-07-01 08:26:38ELECTRICAL COORDINATION STUDY TO D.PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 15:41 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 15:41 Sent To  
Notes
2009-06-16 15:42:42GAVE TO RON
2009-06-16 15:41:53MINOR MECHANICAL DUCT REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 13:32 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 13:32 Sent To B
Notes
2009-06-11 13:32:30TO JW DESK - HORIZONTAL SHAFT ASSEMBLY

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date   Cont ID  
Sent By   Date 2009-05-12 Time   Rev Time 0.00
Received By jgomez Date 2009-05-12 Time 16:49 Sent To  
Notes
2009-05-12 16:49:43SENT TO C12

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 12:55 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 12:55 Sent To B
Notes
2009-05-05 10:39:10PLANS ROUTED TO DOUG WISE FOR EXPEDITED REVIEW
2009-04-29 12:56:13TO SH

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 15:34 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 15:34 Sent To E
Notes
2009-04-17 15:41:27TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 13:03 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 13:03 Sent To I
Notes
2009-04-08 13:04:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 14:38 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 14:38 Sent To  
Notes
2009-04-02 14:42:02TO "C19"

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 14:05 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 14:05 Sent To E
Notes
2009-04-02 14:06:15TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-04-01 Cont ID  
Sent By shill Date 2009-04-01 Time 16:21 Rev Time 0.00
Received By shill Date 2009-04-01 Time 16:21 Sent To  
Notes
2009-04-01 16:21:23BLDG REVISION/SUBMITTAL TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 16:56 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 16:56 Sent To B
Notes
2009-03-30 16:56:57TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-03-26 Cont ID  
Sent By adarroug Date 2009-03-26 Time 17:00 Rev Time 0.00
Received By adarroug Date 2009-03-26 Time 17:00 Sent To B
Notes
2009-03-26 17:00:39TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 17:24 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 17:24 Sent To E
Notes
2009-03-24 17:24:32SENT TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 11:56 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 11:56 Sent To  
Notes
2009-03-09 11:58:45TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 11:46 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 11:46 Sent To  
Notes
2009-03-09 11:49:00TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-23 Cont ID  
Sent By rregueir Date 2009-02-23 Time 16:28 Rev Time 0.00
Received By rregueir Date 2009-02-23 Time 16:27 Sent To  
Notes
2009-02-23 16:27:24TO COMM BOARD #37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 16:01 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 16:01 Sent To  
Notes
2008-11-19 16:04:03TO "COMM" BD#27/PLANS ON RACK/7 ROLLS/3 BOXES--PRIVATE
 PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 08:50 Sent To  
Notes
2008-09-29 08:53:25TO "COMM" BD#28/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2008-08-08 Cont ID  
Sent By rbrown Date 2008-08-08 Time 00:05 Rev Time 0.00
Received By rbrown Date 2008-07-11 Time 10:25 Sent To  
Notes
2008-07-11 10:26:04TO "COMM" BD#22/PLANS ON RACK--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-08-03 Cont ID  
Sent By hmoser Date 2009-08-03 Time 08:26 Rev Time 0.00
Received By hmoser Date 2009-08-03 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-04-14 Cont ID  
Sent By rregueir Date 2009-04-14 Time 17:56 Rev Time 0.00
Received By rregueir Date 2009-04-14 Time 17:41 Sent To PC
Notes
2009-04-14 17:56:44REVISED M102CR5

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 19:16 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 19:16 Sent To  
Notes
2009-04-02 19:16:50REVISED M102CR4

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 17:56 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 17:46 Sent To PC
Notes
2009-03-30 17:55:59THREE SIGNED/SEALED INSTALLATION DETAILS:
  
 1. WALL PROPELLER FAN
 2. OUTSIDE AIR MOTORIZED DAMPER
 3. PERLIN ATTACHMENT FOR HANGERS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-02-23 Cont ID  
Sent By rregueir Date 2009-02-23 Time 19:16 Rev Time 0.00
Received By rregueir Date 2009-02-23 Time 19:15 Sent To  
Notes
2009-02-23 19:16:16REVISED M203CR3. WIND LOAD CALCS FOR APPLIANCES AND
 DUCTWORK SUBJECT TO BUILDING (STRUCTURAL) PLAN REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-17 Cont ID  
Sent By rregueir Date 2008-12-17 Time 14:56 Rev Time 0.00
Received By rregueir Date 2008-12-16 Time 19:40 Sent To  
Notes
2008-12-17 15:18:50PASSED WITH PROVISO
  
 *********PROVISO**********
  
 PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING OUTDOOR
 APPLIANCES ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13. THIS DOCUMENTATION SHALL
 BE PROVIDED FOR REVIEW AND APPROVAL PRIOR TO
 INSTALLATION AND INSPECTION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
2008-12-16 20:49:36 
  
 12/16/08: REVIEW IN PROGRESS. PLANS HAVE BEEN REVIEWED
 FOR CODE COMPLIANCE AND STAMPED. CORRECTIONS ARE NEEDED
 TO ENERGY CALCULATIONS.
  
 THESE CORRECTIONS HAVE BEEN COMMUNICATED TO PERMIT
 APPLICANT. REVIEW STATUS WILL BE PASSED ONCE ENERGY
 CALCULATIONS HAVE BEEN CORRECTED.
  
 A PROVISO WILL BE ISSUED RELATED TO WIND RESISTANCE OF
 ALL OUTDOOR APPLIANCES.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-10-25 Cont ID  
Sent By rregueir Date 2008-10-25 Time 14:47 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 14:46 Sent To  
Notes
2008-10-25 14:47:50REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 7: OK
  
 8. CONDENSATE DISCHARGING OUTDOORS IS OK. HOWEVER,
 DETAIL 12 ON PAGE M104CR1 SHOWS CONDENSATE TYING INTO
 STORM WATER PIPING AT AN ELEVATION LOWER THAN THE STORM
 WATER INLET. THIS CONFIGURATION CREATES AN OPENING IN
 THE STORM WATER DRAIN WITHIN THE BUILDING. SHOULD THE
 STORM WATER DRAIN EVER BACK UP AT A POINT DOWNSTREAM OF
 THE CONDENSATE PIPE, THIS WILL CAUSE THE STORM WATER TO
 BACKUP INTO THE CONDENSATE PIPE AND MAKE THE CONDENSATE
 PIPE A STORM DRAIN PIPE DISCHARGING WITHIN THE
 BUILDING. THIS IS NOT AN APPROVED PLACE OF CONDENSATE
 DISPOSAL. SEE FBCM 307.2.1 AND THE DEFINITION OF
 APPROVED IN SECTION 202 OF FBCM.
  
 9 AND 10: OK
  
 11. PROVIDE PRODUCT APPROVALS AND SUPPORTING
 DOCUMENTATION FOR WIND RESISTANCE FOR ALL OUTDOOR
 APPLIANCES WHICH ARE EXPOSED TO WIND, INCLUDING EXHAUST
 FANS, PACKAGE UNITS AND CONDENSING UNITS. ALL OF THESE
 APPLIANCES ARE NOT ONLY REQUIRED TO BE SECURED TO
 RESIST WIND PRESSURES, BUT ALSO BE DESIGNED AND
 CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13. ALSO, NO INFORMATION COULD BE FOUND IN
 STRUCTURAL PLANS FOR CONSTRUCTION AND SUPPORTS FOR WIND
 RESISTANCE RELATED TO EXTERIOR DUCTWORK. PLEASE PROVIDE
 MISSING INFORMATION IN ACCORDANCE WITH FBCM 301.13.
  
 12. OK
  
 13. WRITTEN RESPONSE INDICATES A CARRIER HAP REPORT IS
 ATTACHED TO THE WRITTEN RESPONSES FOR THE PURPOSE OF
 SHOWING COMPLIANCE WITH ASHRAE 62.1-2004. NO SUCH
 REPORT COULD BE FOUND ATTACHED TO THE WRITTEN
 RESPONSES. PLEASE PROVIDE THE REPORT MENTIONED IN THE
 RESPONSE TO DEMONSTRATE COMPLIANCE WITH FBCM 401.1.
  
 14. OK
  
 15. ENERGY CODE COMPLIANCE FORMS HAVE BEEN PROVIDED IN
 RESPONSE TO THIS COMMENT. HOWEVER, THERE ARE MULTIPLE
 MITSUBISHI SPLIT-SYSTEMS NOT INCLUDED IN THE ENERGY
 CODE COMPLIANCE FORM. PLEASE INCLUDE ALL COOLING
 APPLIANCES IN THE COMPLIANCE FORM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By rregueir Date 2008-07-29 Time 11:49 Rev Time 0.00
Received By rregueir Date 2008-07-24 Time 16:48 Sent To  
Notes
2008-07-29 11:49:27PRIVATE PROVIDER AUDIT #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M101C: EF 18 IS SHOWN SERVING STORAGE ROOM 122 WITH
 2200 TOTAL CFM OF EXHAUST. HOWEVER, THE FAN SCHEDULE ON
 M106C SHOWS EF 18 PROVIDING 3650 CFM OF EXHAUST. WHICH
 IS CORRECT? PLEASE COORDINATE FLOOR PLANS AND EQUIPMENT
 SCHEDULES SHOWING THE REQUIRED DISTRIBUTION OF AIR IN
 ACCORDANCE WITH FBCM 603.1, 501.1 AND FBCB 106.1.1.
  
 2. M101C AND A002C: THE FOLLOWING ROOMS: 124, 125, 126
 AND 127 HAVE A ROOF WHICH IS LOWER THAN THE MAIN ROOF
 OF THE BUILDING. THIS ROOF HAS MULTIPLE EXHAUST FANS
 WHICH ARE REQUIRED TO BE ACCESSIBLE FOR SERVICE AND
 REPLACEMENT IN ACCORDANCE WITH FBCM 306.1. ALSO, WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT EXCEEDING
 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE IN ACCORDANCE WITH FBCM
 306.5. THIS LOWER ROOF IS SHOWN ON PAGE A002C TO HAVE A
 HEIGHT OF 25 FEET ABOVE GRADE. PLEASE SHOW A PERMANENT
 MEANS OF ACCESS TO THIS ROOF LEVEL IN ACCORDANCE WITH
 THIS SECTION.
  
 3. M102C DETAIL 3: STAIR #1 ENCLOSURE 209 IS SHOWN
 BEING PENETRATED BY A 20X16 EXHAUST DUCT FROM EF 30 ON
 THE 2ND FLOOR. PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED
 EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR
 INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE IN ACCORDANCE WITH FBCB 1019.1.2 AND 1020.5.
  
 4. M102C DETAIL 2: STAIR #1 ENCLOSURE 110 IS SHOWN WITH
 MULTIPLE DUCT PENETRATIONS OF THIS EXIT ENCLOSURE/EXIT
 PASSAGEWAY ON THE FIRST FLOOR. THIS AREA ALSO SHOWS A
 SUPPLY DUCT AND RETURN GRILL SERVING THE EXIT ENCLOSURE
 FROM VAV-1. THIS METHOD OF EXIT ENCLOSURE VENTILATION
 IS PROHIBITED. IF VENTILATION IS TO BE PROVIDED FOR
 THIS ENCLOSURE, IT SHALL BE PROVIDED IN ACCORDANCE WITH
 ONE OF THE THREE METHODS LISTED IN ACCORDANCE WITH FBCB
 1019.1.3. UNDER ANY OF THESE CONDITIONS, THE EXIT
 ENCLOSURE VENTILATION SYSTEM SHALL BE INDEPENDENT OF
 OTHER BUILDING VENTILATION SYSTEMS IN ACCORDANCE WITH
 THIS SECTION.
  
 5. M102C DETAIL 3: RELIEF AIR DUCT FROM 1ST FLOOR
 MECHANICAL ROOM CALLS FOR 24X12 WHILE DETAIL 5 CALLS
 FOR THIS SAME DUCT TO BE 20X12. WHICH IS CORRECT?
 PLEASE CLARIFY IN ACCORDANCE WITH FBCM 603.1 AND FBCB
 106.1.1.
  
 6. M102C DETAIL 1: EF #31 IN CORRIDOR 123 IS PROVIDING
 VENTILATION FOR THIS EXIT ENCLOSURE. THERE IS NO
 INDICATION ON PLANS WHAT THE SOURCE OF MAKEUP AIR WILL
 BE FOR THE 300 CFM OF EXHAUST. MECHANICAL VENTILATION
 SHALL BE PROVIDED BY A METHOD OF SUPPLY AIR AND RETURN
 OR EXHAUST AIR. THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND EXHAUST
 AIR IN ACCORDANCE WITH FBCM 403.1. ALSO, PLEASE SHOW
 THE SOURCE OF SUPPLY OR MAKEUP AIR TO BE IN COMPLIANCE
 WITH FBCM 401.4, 401.5 AND 401.6.
  
 7. M102C DETAIL 3: NOTE 17 CALLS FOR EF 30 TO BE
 MOUNTED VERTICALLY ON A WALL. THE ONLY INSTALLATION
 DETAIL FOUND IN PLANS FOR INLINE FANS IS FOR HORIZONTAL
 INSTALLATIONS. PROVIDE DETAIL SHOWING VERTICAL
 INSTALLATION, VIBRATION ISOLATION AND SUPPLEMENTAL
 RESTRAINT METHODS TO BE USED. EQUIPMENT AND APPLIANCES
 SHALL BE INSTALLED AS REQUIRED BY THE TERMS OF THEIR
 APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF THE
 LISTING, THE MANUFACTURER?S INSTALLATION INSTRUCTIONS
 AND THIS CODE IN ACCORDANCE WITH FBCM 304.1. WHERE
 VIBRATION ISOLATION OF EQUIPMENT AND APPLIANCES IS
 EMPLOYED, AN APPROVED MEANS OF SUPPLEMENTAL RESTRAINT
 SHALL BE USED TO ACCOMPLISH THE SUPPORT AND RESTRAINT
 IN ACCORDANCE WITH FBCM 301.10
  
 8. M102C DETAIL 5: MECHANICAL ROOM DETAIL AND
 CONDENSATE TRAP DETAIL SHOWS THE CONDENSATE FROM AHU 2
 DISCHARGING TO A FLOOR DRAIN. THIS DRAIN IS TIED TO THE
 SANITARY SEWER SYSTEM. AIR CONDITIONING CONDENSATE
 SHALL NOT DISCHARGE INTO THE SANITARY SEWER SYSTEM IN
 ACCORDANCE WITH LOCAL ORDINANCE ARTICLE 3 SECTION
 90-125(5). CONDENSATE FROM ALL COOLING COILS AND
 EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET
 TO AN APPROVED PLACE OF DISPOSAL IN ACCORDANCE WITH
 FBCM 307.2.1. CONDENSATE SHALL NOT DISCHARGE INTO A
 STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE.
 NOTE: THESE REQUIREMENTS APPLY TO ALL CONDENSATE
 DISPOSAL SYSTEMS FROM ALL COOLING COILS. SHOW
 COMPLIANCE WITH THESE SECTIONS.
  
 9. M102C DETAIL 2: VAV #1 ON FLOOR PLAN CALLS FOR 355
 CFM OF SUPPLY. HOWEVER, EQUIPMENT SCHEDULE ON M106C
 CALLS FOR A MAXIMUM CFM OF 225 FOR THE SAME VAV. PLEASE
 COORDINATE FLOOR PLANS WITH EQUIPMENT SCHEDULES. AIR
 DISTRIBUTION SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE
 WITH FBCM 603.1.
  
 10. M102C: FLOOR PLAN SHOWS AHU #2 SERVING THE EMPLOYEE
 BREAK ROOM AND AHU #2 ALSO SERVING THE ADMIN AREA.
 THESE APPLIANCES APPEAR TO BE MISLABELED. THE AHU
 SERVING THE ADMIN AREA IS ATTACHED TO ACCU #1 AND THE
 AHU SERVING THE EMPLOYEE BREAK AREA IS ACTUALLY A
 PACKAGE UNIT. PLEASE COORDINATE FLOOR PLANS AND
 EQUIPMENT SCHEDULES, SHOWING ALL APPLIANCES PROPERLY
 LABELED IN RELATION TO THE AREAS BEING SERVED IN
 ACCORDANCE WITH FBCM 301.1, 304.11 AND FBCB 106.1.1.
  
 11. M104C: ROOF CURB DETAIL HAS NO INFORMATION
 REGARDING ATTACHMENT OF CURB TO STRUCTURE OR ATTACHMENT
 OF FAN TO ROOF CURB. MECHANICAL EQUIPMENT, APPLIANCES
 AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES ON THE
 EQUIPMENT AND THE SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH FBCM 301.13. PROVIDE SUFFICIENT DETAIL WITH
 SUPPORTING WIND LOAD CALCULATIONS AS NEEDED (FOR
 BUILDING PLAN REVIEW) TO SHOW THE INSTALLATION OF ALL
 APPLIANCES AND DUCTWORK WHICH IS EXPOSED TO WIND IS
 SUFFICIENT TO RESIST ANTICIPATED WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION AND FBCB SECTION 1609.
 ALSO PROVIDE SUPPORTING DOCUMENTATION SHOWING OUTDOOR
 APPLIANCES THEMSELVES DESIGNED TO RESIST WIND
 PRESSURES. THIS INCLUDES ROOFTOP FANS AS WELL AS GROUND
 MOUNTED PACKAGE UNITS AND CONDENSING UNITS.
  
 12. M105C: THE RELIEF AIR DUCT WHICH IS SHOWN
 DISCHARGING ONTO THE RECYCLING FLOOR IS ALSO SHOWN
 ATTACHED TO THE RETURN AIR PLENUM OF AHU #1. ACCORDING
 TO THE SEQUENCE, DAMPERS ARE TO MODULATE BASED ON THE
 PRESSURE IN THE CONDITIONED SPACE TO ALLOW RELIEF AIR
 TO BE DISCHARGED. HOWEVER, THE RETURN AIR PLENUM WILL
 BE UNDER A CONSTANT NEGATIVE PRESSURE. THIS DESIGN WILL
 CAUSE THE RELIEF AIR DUCT TO ACT AS AN INTAKE DUCT,
 DRAWING AIR FROM THE RECYCLING FLOOR INTO THE ADMIN
 AREA. THIS DESIGN IS NOT IN COMPLIANCE WITH FBCM
 401.5.1, 403.2.1(1) AND FBCM 603.1. PLEASE SHOW A
 DESIGN WHICH IS CAPABLE OF ACHIEVING THE DESIGN INTENT
 AS DESCRIBED IN THE RELIEF AIR SEQUENCE OF OPERATIONS.
 ALSO, THE RELIEF AIR SEQUENCE CALLS FOR 3 DIFFERENT
 MODULATING DAMPERS TO BE OPENED IN STAGES. FLOOR PLANS
 AND CONTROL DIAGRAM ONLY SHOW ONE MOTORIZED DAMPER ON
 THE RELIEF AIR SYSTEM. PLEASE CLARIFY.
  
 13. OUTSIDE AIR: NO INFORMATION REGARDING THE REQUIRED
 RATES OF OUTSIDE AIR HAS BEEN PROVIDED. PLEASE PROVIDE
 OUTSIDE AIR CALCULATIONS SHOWING THE VENTILATION METHOD
 USED, SUCH AS FBCM TABLE 403.3, THE VENTILATION RATE
 METHOD OF AHSRAE 62.1-2004 OR THE IAQ METHOD OF ASHRAE
 62.1-2004 AS ALLOWED UNDER FBCM 403.4. PROVIDE
 SUPPORTING DOCUMENTATION AND/OR CALCULATIONS
 APPROPRIATE FOR THE METHOD USED IN ACCORDANCE WITH FBCM
 401.1. IT IS ACKNOWLEDGED THAT CO2 CONTROLS ARE SHOWN
 ON THE VAV SEQUENCE, BUT THE REQUIRED RATES OF
 VENTILATION FOR THE SPACES BEING SERVED ARE NOT
 PROVIDED ON PLANS. ALSO, THE EMPLOYEE BREAK ROOM IS NOT
 SERVED BY A VAV SYSTEM AND IS THEREFORE NOT ACCOUNTED
 FOR IN THIS SEQUENCE.
  
 14. REHEAT: THE CO2 CONTROL SEQUENCE CALLS FOR ELECTRIC
 REHEAT OF VAV SYSTEMS WHEN OUTSIDE AIR IS REQUIRED TO
 PREVENT OVER-COOLING. REHEATING OR THE SIMULTANEOUS
 OPERATION OF THE HEATING AND COOLING SYSTEMS TO THE
 SAME ZONE ARE PROHIBITED IN ACCORDANCE WITH FBCB
 13-407.1.ABC.2.1.1. IF REHEAT IS TO BE USED, PLEASE
 PROVIDE DOCUMENTATION SHOWING AT LEAST ONE OF THE
 EXCEPTIONS UNDER THIS SECTION HAS BEEN SATISFIED.
  
 15. ENERGY: ENERGY CALCULATIONS WERE NOT PROVIDED WITH
 THIS APPLICATION FOR PERMIT. PROVIDE A COMPLETED ENERGY
 CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCM 301.2 AND
 FBCB 13-101.1.1. ALSO, COOLING LOAD CALCULATIONS SHALL
 BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1. AUDIT FOR
 COMPLIANCE WITH THE REQUIREMENTS OF FBCB CHAPTER 13 CAN
 NOT BE PERFORMED AT THIS TIME.
  
 16. THIS PERMIT APPLICATION WAS SUBMITED UNDER THE
 PRIVATE PROVIDER PROVISIONS OF FS 553.791. AS SUCH THE
 FOLLOWING REQUIREMENTS HAVE NOT BEEN SATISFIED:
 A) A NOTICE TO BUILDING OFFICIAL HAS NOT BEEN PROVIDED
 AS REQUIRED UNDER FS 553.791(4).
 B) PLANS FOR THE "SORT ENCLOSURE" AIR CONDITIONING
 SYSTEMS HAVE BEEN SUBMITTED AS SHOP DRAWINGS, BUT THEY
 ARE ACTUALLY SIGNED AND SEALED PLANS BY THE DESIGNER OF
 RECORD FOR THIS PROJECT. EITHER WAY, THESE PLANS WERE
 NOT STAMPED AS REVIEWED AND NO AFFIDAVIT WAS PROVIDED
 FOR THESE PLANS BY THE PRIVATE PROVIDER AS REQUIRED
 UNDER FS 553.791(6). THESE PLANS WILL NOT BE AUDITED
 PRIOR TO REVIEW AND SUBMISSION OF AFFIDAVIT BY THE
 PRIVATE PROVIDER.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DETAILED EXPLANATION OF HOW EACH COMMENT HAS BEEN
 ADDRESSED AS WELL AS WHERE THE SUPPORTING INFORMATION
 CAN BE FOUND. ALSO, PLEASE RETURN ONE OLD/VOIDED SET OF
 PLANS FOR REFERENCE. THESE STEPS WILL ASSIST IN A
 TIMELY AUDIT OF RESUBMITTED PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By kstevens Date 2008-10-07 Time 09:56 Rev Time 0.00
Received By kstevens Date 2008-10-06 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-16 Cont ID  
Sent By kstevens Date 2008-07-16 Time 16:05 Rev Time 0.00
Received By kstevens Date 2008-07-16 Time 16:05 Sent To  
Notes
2008-07-16 16:44:41AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLEASE SUBMIT AFFIDAVITS AS REQUIRED IN FS 553.791
 FOR EACH DISCIPLINE.
  
 2. SHT A101C MEN'S AND WOMEN'S TOILET AREAS ARE
 INDICATED BY DETAIL 1/A101 - A111 - A112. SHTS A101,
 A111 & A112 NOT SUBMITTED. PLEASE CORRELATE. SECTIONS
 106.1.1 & 106.1.3. THIS IS INDICATED IN MANY AREAS WITH
 MANY DETAILS AND MANY SHEETS WHERE THE DETAILS DO NOT
 CORRELATE WITH SHEETS SUBMITTED.
  
 3. SHT A105C DETAIL 7 SHOW THE CLEAR FLOOR SPACE FOR
 ACCESSIBLE W/C & LAV. SECTIONS 11-4.16.2 & 11-4.19.3.
  
 4. SHT A105C DETAILS 8 C & D. SHOW CLEARANCES AND
 INDICATE FAUCET TYPES PER SECTIONS 11-4.19.2 &
 11-4.19.5.
  
 5. SHT A111C DETAILS 1, 2, 3 & 4 SHOW THE CLEAR FLOOR
 SPACE FOR ACCESSIBLE W/C'S, LAVS, URINALS & DRINKING
 FOUNTAINS PER SECTIONS 11-4.15.5(1), 11-4.16.2,
 11-4.18.3 & 11-4.19.3.
  
 6. SHT A112C DETAILS 14 & 17 INDICATE THE FAUCET TYPE
 PER SECTIONS 11-4.19.5 & 11-4.24.7.
  
 7. SHT A112C DETAIL 17 SHOW SINK DEPTH PER SECTION
 11-4.24.4. (SHOWS 12" - MAX 6-1/2").
  
 8. MINIMUM 3 SETS OF PLANS REQUIRED TO BE SUBMITTED PER
 SECTION 106.1. ONLY ONE SET OF ARCHITECTURAL,
 STRUCTURAL, LANDSCAPE, IRRIGATION, PLUMBING, ELECTRIC &
 MECHANICAL. SUBMITTED.
  
 9. ALL SHEETS SUBMITTED HAVE NOT BEEN REVIEWED AND
 SIGNED OFF BY THE PRIVATE PROVIDER. SECTION
 553.791(1)(H)(I). (SEE LANDSCAPE, IRRIGATION & FIRE
 PROTECTION).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By kdfreema Date 2008-10-07 Time 14:47 Rev Time 0.00
Received By kdfreema Date 2008-10-07 Time 14:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-30 Cont ID  
Sent By kdfreema Date 2008-07-30 Time 13:34 Rev Time 0.00
Received By kdfreema Date 2008-07-30 Time 13:34 Sent To  
Notes
***NONE***