Plan Review Details - Permit 08070305
Plan Review Stops For Permit 08070305
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-02 Cont ID  
Sent By shill Date 2008-09-02 Time 08:58 Rev Time 0.00
Received By shill Date 2008-09-02 Time 08:58 Sent To  
Notes
2008-09-02 08:59:04BLDG REVISION #1 DATED 7/17/8
  
 ROUTED TO ZONING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-26 Cont ID  
Sent By shill Date 2008-08-26 Time 09:52 Rev Time 0.00
Received By shill Date 2008-08-26 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By shill Date 2008-08-05 Time 15:32 Rev Time 0.00
Received By shill Date 2008-08-05 Time 15:32 Sent To  
Notes
2008-08-05 15:34:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ASCE REFERENCE INCORRECT, SEE FBC35.
  
 2.DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS481.
  
 3. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE.THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 4.PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER.THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 5.CITY PLACE APPROVAL STAMP REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 09:12 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 09:12 Sent To B
Notes
2008-08-27 09:12:56TO "BUILD" SAMANTHA H.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 10:10 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 10:10 Sent To Z
Notes
2008-08-08 10:10:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 14:08 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 14:08 Sent To B
Notes
2008-07-23 14:08:42TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 15:19 Sent To  
Notes
2008-07-10 15:20:58TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-04 Cont ID  
Sent By eschneid Date 2008-09-04 Time 17:03 Rev Time 0.00
Received By eschneid Date 2008-09-04 Time 17:03 Sent To  
Notes
2008-09-04 17:03:47CANOPY REVISION - STAMPED SHEET.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-12 Cont ID  
Sent By eschneid Date 2008-08-12 Time 10:55 Rev Time 0.00
Received By eschneid Date 2008-08-12 Time 10:55 Sent To B
Notes
2008-08-12 10:56:44ANY SIGNAGE ON THE AWNINGS WILL REQUIRE A SEPARATE
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By eschneid Date 2008-07-23 Time 10:44 Rev Time 0.00
Received By eschneid Date 2008-07-23 Time 10:44 Sent To I
Notes
2008-07-23 12:11:30FAILED
  
 1) THE CITYPLACE STAMP IS NOT ON THE RENDERINGS OR
 SHEET B-A4.07.
  
 2) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 MUST PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE
 BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING.
 THE AWNING SHOWN ON SHEET 1 DOES NOT INCLUDE A HEIGHT,
 THE AWNING ON SHEET 2 IS LISTED AS 7' 6", AND THE
 AWNING SHOWN ON SHEET 3, WHILE LISTED AS MINIMUM OF 7'
 6" IS ON THE SECOND STORY SO IT NEEDS TO GIVE TRUE
 HEIGHT.
  
 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 ON THE SECOND FLOOR SHALL PROJECT THREE (3) FEET FROM
 THE BUILDING FACADE.THE AWNING SHOWN ON SHEET 1
 PROJECTS 8' 3" FROM THE BUILDING FACADE, THE AWNING ON
 SHEET 2 PROJECTS 10' FROM THE BUILDING FACADE, AND THE
 AWNING SHOWN ON SHEET 3 PROJECTS 3' FROM NOT THE
 BUILDING FACADE, BUT FROM THE OUTER EDGE OF THE
 ARCADE.
  
 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT BOTH
 SIDES OF A SHED AWNING MUST BE OPEN.THE SHED AWNING
 ON SHEET 3 ARE NOT OPEN.
  
 5) THE CITYPLACE MASTER SIGN PLAN DOES NOT ALLOW
 VALANCES ON SECOND STORY AWNINGS.ALL AWNINGS SHOWN
 HAVE VALANCES.
  
 6) THE CITYPLACE MASTER SIGN PLAN ALLOWS VARIANCES FROM
 THE PROVISIONS OF 2, 3, 4 & 5 ABOVE.PROVIDE A
 NOTARIZED LETTER FROM CITYPLACE THAT THEY HAVE GRANTED
 THE SPECIFIC VARIANCES NEEDED TO CONSTRUCT THE PROPOSED
 AWNINGS OR REVISE AWNINGS TO ADHERE TO THE CITYPLACE
 MASTER SIGN PLAN REQUIREMENTS.
  
 7) THE TAVERNA OPA COPY SHOWN ON THE RENDERINGS
 REQUIRES APPROVAL THROUGH A SIGN PERMIT.NOTE THAT THE
 SQUARE FOOTAGE OF SIGNAGE ON THE WESTERN ELEVATION
 VALANCES (PROVIDED THE VARIANCE TO 5 ABOVE IS GRANTED
 IN WRITING BY CITYPLACE) IS REQUIRED TO BE INCLUDED
 WITH THE AMOUNT OF SIGNAGE SQUARE FOOTAGE PROPOSED BY
 THE TAVERNA OPA SIGN PERMIT NUMBER 08070155.REMEMBER
 1 SQUARE FOOT OF SIGNAGE IS ALLOWED FOR 1 LINEAR FOOT
 OF FRONTAGE, UNLESS CITYPLACE GRANTS A VARIANCE IN
 WRITING.
  
 8) THE POSTS TO CONTACT THE AWNING TO THE "RED STEEL
 BEAM" ARE SHOWN ON SHEET 3 AS 8' IN LENGTH.A REVIEW
 OF THE AWNING LOCATIONS ON THE RENDERINGS SEEMS TO
 CONTRADICT THAT AN 8' TALL POST WILL FIT UNDER AN EVE
 ON THE SLOPED ARCADE ROOF THAT APPEARS TO BE
 APPROXIMATELY 1' IN HEIGHT.
  
 9) PROVIDE DIMENSIONS ON THE RENDERINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.