Plan Review Details - Permit 08070288
Plan Review Stops For Permit 08070288
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-30 Cont ID  
Sent By mjacobs Date 2008-07-30 Time 16:58 Rev Time 0.00
Received By mjacobs Date 2008-07-30 Time 14:52 Sent To PC
Notes
2008-07-30 16:58:52 
 BUILDING PLAN REVIEW
 PERMIT: 08070288
 ADD: 7620 S. DIXIE HWY
 CONT: RIDDLE CONSTRUCTION COMPANY INC,
 TEL: (561)616-9179
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)PROVIDE ARCHITECTURAL DRAWINGS SHOWING
 ACCESSIBILITY TO THE MACHINE FOR PERSONS IN WHEELCHAIRS
 AS STATED ON PAGE #1 OF THE DRAWINGS. INDICATE THE
 FOUNDATION AND TIE-DOWN INFORMATION FOR THE STRUCTURE.
 PROVIDE CLEAR DETAIL DIMENSION DRAWINGS PERTAINING TO
 THE FOUNDATION AND ANCHORING OF THE STRUCTURE. NOTE: IF
 THE STRUCTURE WHICH SUPPORTS THE ICE MACHINE IS
 DESIGNED BY OTHERS, THE DRAWINGS SHALL BE SIGNED DATED
 AND SEALED BY THAT PERSON PER FLORIDA STATUTES 481 AND
 471. FBC 106
  
 5) INDICATE ON THE DRAWINGS THE DISTANCE FROM ANY DOOR,
 WINDOWS OR GLAZING THE STRUCTURE WILL BE INSTALLED. SEE
 NOTE #3 IN THE GENERAL NOTES SECTION. WHAT TYPE OF
 BUSINESS WILL BE MACHINE BE USE FOR. ADDITIONAL
 INFORMATION REQUIRED 106.2*
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-16 Cont ID  
Sent By btrobaug Date 2008-07-16 Time 08:25 Rev Time 0.00
Received By btrobaug Date 2008-07-16 Time 06:52 Sent To  
Notes
2008-07-16 08:25:56 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE THE PANEL DESIGNATION, CIRCUIT NUMBERS FOR
 THE FEED, LOCATION AND LOAD CALCULATION FOR THE
 PANEL/SERVICE FEEDING THE 200 AMP ICE MACHINE PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By mawillia Date 2008-07-24 Time 11:16 Rev Time 0.00
Received By mawillia Date 2008-07-24 Time 10:50 Sent To  
Notes
2008-07-24 11:34:40*****DENIED******
  
  
 1.THE ADDRESS LOCATION FOR THE SCOPE OF WORK SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.PLEASE LIST OCCUPANCY TYPE FOR BUILDING IN WHICH
 THE MACHINERY IS TO BE INSTALLED.
  
 3.IN REFERENCE TO THE SUBMITTED PLOT PLAN, UNABLE TO
 DETERMINE THE MACHINERY'S PROXIMITY TO WINDOWS AND/OR
 DOORS IN THE BUILDING.
  
 4.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TOTHE PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS ALLEYS, FIRE LANES, ETC.) .
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-30 Time   Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 16:43 Sent To  
Notes
2008-07-15 09:00:27TO "BOB"#2
2008-07-10 16:48:16WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-16 Cont ID  
Sent By tgordon Date 2008-07-16 Time 09:14 Rev Time 0.20
Received By tgordon Date 2008-07-16 Time 09:14 Sent To  
Notes
2008-07-16 09:20:19PRE-MANUFACTURED ICE MACHINE MODULAR STRUCTURE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-16 Cont ID  
Sent By mperson Date 2008-07-16 Time 11:43 Rev Time 0.00
Received By mperson Date 2008-07-16 Time 11:43 Sent To  
Notes
2008-07-16 11:57:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1, STATES THE FOLLOWING, "BUILDING SITE
 INSTALLATION REQUIREMENTS LOCAL INSPECTIONS DEPARTMENT:
 SPECIAL CONDITIONS/LIMITATIONS, THE FOLLOWING ITEMS
 HAVE NOT BEEN COMPLETED BY THE MANUFACTURER, HAVE NOT
 BEEN INSPECTED BY A THIRD PARTY INSPECTION AGENCY AND
 ARE NOT CERTIFIED BY THE STATE MODULAR LABEL AND/OR
 CERTIFICATION. CODE COMPLIANCE FOR THESE ITEMS MUST BE
 DETERMINED AT A LOCAL LEVEL: 3) BUILDING DRAINS,
 CLEANOUTS AND HOOK-UPS TO PLUMBING SYSTEMS, AND FINNISH
 PLUMBING." WITH THAT BEING INDICATED ON THE PLANS AND
 MOST ICE MACHINES HAVING POTABLE WATER AND DRAINS,
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER
 SPECIFICATIONS OF THE ICE MACHINE CLEARLY INDICATING
 THE MAKE, MODEL NUMBER, PLUMBING REQUIREMENTS (POTABLE
 WATER AND DRAINAGE), AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY. ALSO PLEASE PROVIDE THE
 INFORMATION THAT IS REQUSTED IN COMMENTS #2 AND #3. PER
 FBC- PLUMBING SECTIONS 401.1, 601.1 AND 701.1 SCOPE.
  
 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (4)(6)(13) AND FBC-PLUMBING SECTION 701.1 AND
 901.1 SCOPE: PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS FOR THE ICE
 MACHINE DRAIN.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(8)(10)(13) AND FBC-PLUMBING SECTION 601.1
 SCOPE: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED ICE MACHINE WORK FOR THE COLD
 WATER INDICATING THE PIPE SIZE, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By lfranco Date 2008-07-25 Time 19:16 Rev Time 0.00
Received By lfranco Date 2008-07-25 Time 19:09 Sent To  
Notes
2008-07-25 19:23:56PLANNING AND ZONING: **** FAILED ****
  
 1.PROVIDE RESPONSES IN WRITING.
  
 2. PLEASE CLARIFY TOTAL DIMENSIONS OF ENCLOSURE OF THE
 ICE MACHINE.PROVIDE DIMENSIONS ON SITE PLAN FROM THE
 PROPERTY LINE AND DRAW TO SCALE OF THE EXISTING
 BUILDING.WHAT IS THE TOTAL HEIGHT OF THE ICE MACHINE
 ENCLOSURE? PROVIDE INFORMATION ACCORDINGLY.
  
 3.PURSUANT TO SECTION 94-444(C)(1) - OUTDOOR STORAGE
 OF GOODS, MERCHANDISE AND MATERIALS SHALL NOT BE
 PERMITTED UNLESS ENCLOSED ON ALL SIDES BY A WALL OF
 ADEQUATE HEIGHT CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY OR COMPARABLY
 DURABLE WOOD OR STEEL... SEE ZONING LAND AND
 DEVELOPMENT REGULATIONS.IS ANY SCREENING OF
 LANDSCAPING PROVIDED?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 TEL. (561) 822-1443
 EMAIL: [email protected]