Plan Review Details - Permit 08070254
Plan Review Stops For Permit 08070254
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-01 Cont ID  
Sent By shill Date 2008-10-01 Time 12:12 Rev Time 0.00
Received By shill Date 2008-10-01 Time 12:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-18 Cont ID  
Sent By shill Date 2008-09-18 Time 09:04 Rev Time 0.00
Received By shill Date 2008-09-18 Time 09:04 Sent To  
Notes
2008-09-18 09:14:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE THE ROOF TILE NOA; THE ONLY FOAM ADHESIVE
 APPROVED FOR THIS PRODUCT IS POLYPRO. TITE-SET
 INSULATION ADHESIVE EVALUATION REPORT WAS SUBMITTED;
 THIS IS AN INSULATION ADHESIVE, NOT A TILE ADHESIVE.
 THIS IS A COMPONENT IN A ROOF ASSEMBLY, AND IS NOT
 INCLUDED IN THE ROOF TILE NOA SUBMITTED. PLEASE PROVIDE
 MORE INFORMATION; SPECIFY AN ASSEMBLY AND PROVIDE
 PRODUCT APPROVALS WHICH INCLUDE THESE COMPONENTS.
  
 IF YOUR INTENTION IS TO INSTALL THE TILE OVER A WOOD
 DECK WITH ROOF TILE ADHESIVE, PROVIDE THE POLYPRO
 PRODUCT APPROVAL (AS THIS IS THE ONLY PRODUCT INCLUDED
 IN THE NOA SUBMITTED). IF YOU WISH TO USE A DIFFERENT
 ROOF TILE ADHESIVE, ADDITIONAL INFORMATION (INCLUDING
 ENGINEERING) WILL BE REQUIRED. PLEASE CONTACT ME BY
 TELEPHONE IF YOU WISH TO USE A TILE FOAM ADHESIVE OTHER
 THAN THE ONE INCLUDED IN THE NOA (POLYPRO).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-22 Cont ID  
Sent By shill Date 2008-08-22 Time 15:19 Rev Time 0.00
Received By shill Date 2008-08-22 Time 15:19 Sent To  
Notes
2008-08-22 15:20:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By kconrad Date 2008-07-22 Time 15:17 Rev Time 0.00
Received By kconrad Date 2008-07-22 Time 15:17 Sent To  
Notes
2008-07-22 15:31:46THIS PREINSPECT WAS PERFORMED BY DR. THE ROOF REPAIR IS
 GREATER THAN 25% AND SHALL COMPLY WITH THE FLORIDA
 EXISTING BUILDING CODE, SECTION 511.1:
  
 511.1.2
 NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF
 SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.