| Plan Review Stops For Permit 08070224 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-09-24 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-24 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2008-09-24 13:57:29 | STAMPED PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-09-23 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-23 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2008-09-23 09:23:12 | BUILDING PROVISO | | | | | | SUBMIT ENHANCED FASTENING REQUIREMENTS AT THE ROOF | | | PERIMETER AND CORNER AREAS AS CALCULATED IN COMPLIANCE | | | WITH RAS 117 FOR THE TAMKO MODIFIED ROOF SYSTEM WITH | | | FASTENING OPTION #1 ON PAGE 16 OF NOA 07-0111.03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-08-01 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-08-01 |
Time |
16:12 |
Sent To |
B |
|
| Notes |
| 2008-08-01 16:07:09 | 2004 FBC W/2007 REVISIONS | | | ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. FS 713 | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) SUBMIT 2 COPIES OF ENERGY CALCULATION FORMS AS | | | REQUIRED BY FBC 13-101.2.2. THE OWNER/AGENT IS REQUIRED | | | TO SIGN THE FORMS. | | | | | | 4) SHOW COMPLIANCE WITH FAC RULE 9B-3.0472 FOR CARBON | | | MONOXIDE ALARMS. | | | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND LISTING | | | INFORMATION FOR THE PREFAB FIREPLACE AND CHIMNEY. FBC | | | R1002 AND R1004 | | | | | | 6) PROVIDE BUCK DETAILS FOR THE OVERHEAD GARAGE DOOR. | | | FBC R613.6.1 | | | | | | 7) PROVIDE DETAILS FOR THE ATTACHMENT OF THE NEW | | | FOOTINGS AND TIE BEAMS TO THE EXISTING STRUCTURE. FBC | | | R301.1 | | | | | | 8) DIFFERENT LENGTHS OF TAPCONS FOR ANCHORING THE DOOR | | | BUCKS ARE SPECIFIED ON SHEETS 2 AND 3. PLEASE | | | COORDINATE. | | | | | | 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 10) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED PER | | | FBC 106.1* CITY AMENDMENTS. ONE ONE SET WAS SUBMITTED | | | FOR THE SINGLE HUNG WINDOWS, SWING DOOR AND SLIDING | | | GLASS DOORS. | | | | | | 11) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE | | | DOOR AND ROOFING MATERIAL FOR THE FLAT ROOF AS REQUIRED | | | BY DCA RULE 9B-72. | | | | | | 12) SPECIFY THE FASTENING METHOD THAT WILL BE USED TO | | | INSTALL THE MONIER ROOF TILES. CIRCLE THE APPROPRIATE | | | FASTENING ON THE NOA. FBC R 301.2.1 | | | | | | 13) SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE | | | FOR THE FLAT ROOF SYSTEM THAT WILL BE USED. SUBMIT RAS | | | 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER | | | AND CORNER AREAS. FBC R301.2.1 | | | | | | 14) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND A PRODUCT | | | APPROVAL FOR CASEMENT WINDOWS WAS SUBMITTED. PLEASE | | | CLARIFY. THE PRODUCT APPROVAL FOR THE CASEMENT WINDOWS | | | IS EXPIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-09-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-09-15 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-09-15 |
Time |
15:04 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-07-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-10 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-10 |
Time |
14:26 |
Sent To |
Z |
|
| Notes |
| 2008-07-10 15:23:34 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ALL COMMENTS RELATE TO SHEET #4 UNLESS OTHERWISE NOTED. | | | ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | | PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER | | | 230.72(A)(1)A DISCONNECT IS SHOWN ON THE RISER BUT | | | NOT LOCATED ON THE FLOOR PLAN. | | | | | | 2} THE POOL HEATER AND PUMP IN THE LOAD CALCULATION IS | | | NOT ON THE PANEL SCHEDULE, INDICATE OCP AND CONDUCTOR | | | SIZE. 408.4 NEC. | | | | | | 3} THE 60 AMP OCP FOR THE NEW HEAT LOAD OF 5KW IS TOO | | | LARGE TO PROTECT THE UNIT. 5000/240=20.83 X 125%=26 | | | AMPS.30 AMP BREAKER MAX. | | | | | | 4} 13-606.1.ABC.1.2.4 RECESSED LIGHTING FIXTURES. | | | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT | | | ABUT AN ATTIC SPACE SHALL MEET ONE OF THREE | | | REQUIREMENTS: INDICATE DESIGNERS INTENTION ON THE | | | PLAN. | | | | | | 5} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 | | | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE | | | LOCATIONS OF THE SOUNDING DEVICES. | | | | | | 6} 9B-3.0472 CARBON MONOXIDE PROTECTION. | | | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A | | | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, | | | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. | | | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR | | | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING | | | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS | | | SHALL HAVE BATTERY BACK UP. | | | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE | | | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED | | | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. | | | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.NOTE: | | | MAY BE COMBINATION SMOKE/CARBON MONOXIDE. | | | | | | 7} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6) | | | GFI, INDICATE ON THE PLAN. | | | | | | 8} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, LABEL THE | | | ROOMS ON THE ELECTRICAL PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-02-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-26 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-26 |
Time |
09:17 |
Sent To |
M |
|
| Notes |
| 2009-02-26 09:17:23 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2008-09-24 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-09-24 |
Time |
09:50 |
Sent To |
B |
|
| Notes |
| 2008-09-24 09:50:52 | ROUTED TO ROBERT MCDOUGAL'S DESK MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-26 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-26 |
Time |
16:02 |
Sent To |
Z |
|
| Notes |
| 2008-08-26 16:03:02 | TO "ZONING" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-22 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-22 |
Time |
16:44 |
Sent To |
P |
|
| Notes |
| 2008-07-22 16:44:32 | TO "SFR" "P" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-08-01 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-07-09 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2008-07-09 10:37:35 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-06 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-06 |
Time |
09:20 |
Sent To |
PC |
|
| Notes |
| 2009-03-06 09:22:59 | **PROVISO** | | | RETURN IN MASTER BEDROOM IS NOT SIZED TO MEET THE | | | BALANCED RETURN EXCEPTIONS UNDER FBC-R M1602.4. A FIELD | | | TEST WILL BE REQUIRED TO VERIFY PRESSURE DIFFERENTIAL | | | ACROSS CLOSED DOOR IN ACCORDANCE WITH THIS SECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-09 |
Time |
14:28 |
Rev Time |
0.40 |
| Received By |
tgordon |
Date |
2008-09-09 |
Time |
14:27 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-09 |
Time |
16:11 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-07-09 |
Time |
16:11 |
Sent To |
Z |
|
| Notes |
| 2008-07-09 16:36:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.2.2. | | | | | | 2) PLEASE SUBMIT MECHANICAL PLANS AS THE AIR HANDLER | | | AND CONDENSER UNIT ARE BEING INSTALLED AT THE NEW | | | ADDITION, PER 2004 WPB AMEND. 106.3.5.4 (10). | | | | | | 3) PLEASE SHOW ON PLANS WERE THE CLOTHES DRYER VENT | | | WILL TERMINATE AT, BE INFORMED THE CLOTHES DRYER VENT | | | MAY NOT TERMINATE NEAR THE A/C CONDENSER UNIT, PER 2004 | | | FBC/R R303.4.2. | | | | | | 4) THE EXISTING BATH 2 WILL REQUIRE AN EXHAUST FAN AS | | | THE WINDOW IS BEING ENCLOSED, IF THEIR IS AN EXHAUST | | | FAN IN THE ROOM, SHOW A EXISTING FAN IF NOT SHOW A NEW | | | FAN, PER 2004 FBC/R303.3 EXCEPT. | | | | | | 5) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | PREFAB FIREPLACE, PER 2004 FBC/R R1004. | | | | | | 6) PER FS 553.885CARBON MONOXIDE ALARM REQUIRED.-- | | | EVERY BUILDING FOR WHICH A BUILDING PERMIT IS ISSUED | | | FOR NEW CONSTRUCTION ON OR AFTER JULY 1, 2008, AND | | | HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A | | | FIREPLACE, OR AN ATTACHED GARAGE SHALL HAVE AN APPROVED | | | OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 | | | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. PLEASE | | | COMPLY. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-16 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-16 |
Time |
08:28 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-11 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-25 |
Time |
11:48 |
Sent To |
B |
|
| Notes |
| 2008-07-25 12:14:20 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET 4, SANITARY PLUMBING RISER DIAGRAM: PLEASE | | | CORRECT THE FOLLOWING ON THE RISER DIAGRAM PER FBC-2004 | | | PLUMBING SECTIONS | | | A} THE BRANCH DRAIN AND STACK TO THE WASHING MACHINE | | | SHALL BE 3 INCH (3"). PER SECTION 406.3 WASTE | | | CONNECTIONS. | | | B} A CLEANOUT IS REQUIRED FOR THE WASHING MACHINE | | | STACK AND IT SHALL BE ACCESSIBLE. PLEASE LOCATE THE | | | CLEANOUT TO THE EXTERIOR OR LOCATE IT AT 4' A.F.F.. PER | | | SECTION 708.3.5 BASE OF STACK AND SECTION 708.9 | | | ACCESS. | | | C} THE KITCHEN SINK MUST DRAIN DOWNSTREAM OF WET | | | VENTED BATHROOM 2. PER SECTION 909.1 WET VENT | | | PERMITTED. | | | D} THE DEMO OF THE OLD WASHING MACHINE BRANCH DRAIN | | | CAN NOT HAVE ANY DEAD ENDS.THE BRANCH DRAIN MUST BE | | | TERMINATED WITHIN 2 FEET OF THE MAIN, AND PLEASE | | | CLEARLY INDICATE THIS ON THE RESUBMITTAL . PER SECTION | | | 704.5 DEAD ENDS. | | | E} A CLEANOUT IS REQUIRED AT THE BASE OF THE LAV STACK | | | IN THE MASTER BATH. PER SECTION 708.3.5 BASE OF STACK. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-09-24 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-09-24 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-09-08 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-09-08 |
Time |
22:53 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-09-08 |
Time |
22:56 |
Sent To |
|
|
| Notes |
| 2008-09-08 22:55:52 | 1. ALTHOUGH THERE IS A NOTE STATING THAT THE TRUSS | | | LAYOUT CONFORMS TO THE BUILDING STRUCTURE THE TRUSS | | | LAYOUT PLAN DOES NOT MATCH THE ROOF FRAMING PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE CONTACT: | | | BOBBY POWELL JR., PLANNER, [email protected], (561) | | | 822-1401 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2008-07-22 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2008-07-22 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2008-07-22 15:45:30 | 1.PLEASE INCLUDE A LANDSCAPE PLAN PURSUANT TO SECTION | | | 94-441 OF THE CITY'S ZONING AND LAND DEVELOPMENT | | | REGULATIONS AS THE VALUE OF THE PROPOSED WORK EXCEEDS | | | 50 PERCENT OF THE VALUE OF THE STRUCTURE. | | | | | | 2.PLEASE MAKE SURE THAT ALL PLANS ARE CONSISTENT. THE | | | ROOF FRAMING PLAN DOES NOT MATCH THE TRUSS PLAN. | | | | | | 3.PLEASE SHOW THE LOCATION OF ALL MECHANICAL | | | EQUIPMENT.THE AIR CONDITIONER SHOWN ON THE ELECTRICAL | | | PLAN MUST BE SHOWN ON THE SITE PLAN AND CAN NOT PROJECT | | | MORE THAN FOUR (4) FEET INTOSETBACKS. | | | | | | 4.PLEASE INCLUDE DIMENSION LINES SHOWING THE HEIGHT | | | OF THE BUILDING.THE HEIGHT SHALL BE MEASURED FROM THE | | | FINISHED GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL | | | BETWEEN EAVES AND RIDGE FOR A GABLE ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE CONTACT: | | | BOBBY POWELL JR., PLANNER, [email protected], (561) | | | 822-1401 |
|
|