Plan Review Details - Permit 08070224
Plan Review Stops For Permit 08070224
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-24 Cont ID  
Sent By rmcdouga Date 2008-09-24 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2008-09-24 Time 13:56 Sent To  
Notes
2008-09-24 13:57:29STAMPED PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-09-23 Cont ID  
Sent By rmcdouga Date 2008-09-23 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2008-09-23 Time 09:16 Sent To  
Notes
2008-09-23 09:23:12BUILDING PROVISO
  
 SUBMIT ENHANCED FASTENING REQUIREMENTS AT THE ROOF
 PERIMETER AND CORNER AREAS AS CALCULATED IN COMPLIANCE
 WITH RAS 117 FOR THE TAMKO MODIFIED ROOF SYSTEM WITH
 FASTENING OPTION #1 ON PAGE 16 OF NOA 07-0111.03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By rmcdouga Date 2008-08-01 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2008-08-01 Time 16:12 Sent To B
Notes
2008-08-01 16:07:092004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT 2 COPIES OF ENERGY CALCULATION FORMS AS
 REQUIRED BY FBC 13-101.2.2. THE OWNER/AGENT IS REQUIRED
 TO SIGN THE FORMS.
  
 4) SHOW COMPLIANCE WITH FAC RULE 9B-3.0472 FOR CARBON
 MONOXIDE ALARMS.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND LISTING
 INFORMATION FOR THE PREFAB FIREPLACE AND CHIMNEY. FBC
 R1002 AND R1004
  
 6) PROVIDE BUCK DETAILS FOR THE OVERHEAD GARAGE DOOR.
 FBC R613.6.1
  
 7) PROVIDE DETAILS FOR THE ATTACHMENT OF THE NEW
 FOOTINGS AND TIE BEAMS TO THE EXISTING STRUCTURE. FBC
 R301.1
  
 8) DIFFERENT LENGTHS OF TAPCONS FOR ANCHORING THE DOOR
 BUCKS ARE SPECIFIED ON SHEETS 2 AND 3. PLEASE
 COORDINATE.
  
 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED PER
 FBC 106.1* CITY AMENDMENTS. ONE ONE SET WAS SUBMITTED
 FOR THE SINGLE HUNG WINDOWS, SWING DOOR AND SLIDING
 GLASS DOORS.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOOR AND ROOFING MATERIAL FOR THE FLAT ROOF AS REQUIRED
 BY DCA RULE 9B-72.
  
 12) SPECIFY THE FASTENING METHOD THAT WILL BE USED TO
 INSTALL THE MONIER ROOF TILES. CIRCLE THE APPROPRIATE
 FASTENING ON THE NOA. FBC R 301.2.1
  
 13) SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE
 FOR THE FLAT ROOF SYSTEM THAT WILL BE USED. SUBMIT RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER
 AND CORNER AREAS. FBC R301.2.1
  
 14) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND A PRODUCT
 APPROVAL FOR CASEMENT WINDOWS WAS SUBMITTED. PLEASE
 CLARIFY. THE PRODUCT APPROVAL FOR THE CASEMENT WINDOWS
 IS EXPIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-09-15 Cont ID  
Sent By btrobaug Date 2008-09-15 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2008-09-15 Time 15:04 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-10 Time 15:53 Rev Time 0.00
Received By btrobaug Date 2008-07-10 Time 14:26 Sent To Z
Notes
2008-07-10 15:23:34 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET #4 UNLESS OTHERWISE NOTED.
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1)A DISCONNECT IS SHOWN ON THE RISER BUT
 NOT LOCATED ON THE FLOOR PLAN.
  
 2} THE POOL HEATER AND PUMP IN THE LOAD CALCULATION IS
 NOT ON THE PANEL SCHEDULE, INDICATE OCP AND CONDUCTOR
 SIZE. 408.4 NEC.
  
 3} THE 60 AMP OCP FOR THE NEW HEAT LOAD OF 5KW IS TOO
 LARGE TO PROTECT THE UNIT. 5000/240=20.83 X 125%=26
 AMPS.30 AMP BREAKER MAX.
  
 4} 13-606.1.ABC.1.2.4 RECESSED LIGHTING FIXTURES.
 RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT
 ABUT AN ATTIC SPACE SHALL MEET ONE OF THREE
 REQUIREMENTS: INDICATE DESIGNERS INTENTION ON THE
 PLAN.
  
 5} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 6} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.NOTE:
 MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 7} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6)
 GFI, INDICATE ON THE PLAN.
  
 8} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, LABEL THE
 ROOMS ON THE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-26 Cont ID  
Sent By adarroug Date 2009-02-26 Time 09:17 Rev Time 0.00
Received By adarroug Date 2009-02-26 Time 09:17 Sent To M
Notes
2009-02-26 09:17:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-24 Cont ID  
Sent By mmiller Date 2008-09-24 Time 09:50 Rev Time 0.00
Received By mmiller Date 2008-09-24 Time 09:50 Sent To B
Notes
2008-09-24 09:50:52ROUTED TO ROBERT MCDOUGAL'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 16:02 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 16:02 Sent To Z
Notes
2008-08-26 16:03:02TO "ZONING" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 16:44 Sent To P
Notes
2008-07-22 16:44:32TO "SFR" "P"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-01 Cont ID  
Sent By rmcdouga Date 2008-08-01 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2008-07-09 Time 10:37 Sent To  
Notes
2008-07-09 10:37:35TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By rregueir Date 2009-03-06 Time 09:23 Rev Time 0.00
Received By rregueir Date 2009-03-06 Time 09:20 Sent To PC
Notes
2009-03-06 09:22:59**PROVISO**
 RETURN IN MASTER BEDROOM IS NOT SIZED TO MEET THE
 BALANCED RETURN EXCEPTIONS UNDER FBC-R M1602.4. A FIELD
 TEST WILL BE REQUIRED TO VERIFY PRESSURE DIFFERENTIAL
 ACROSS CLOSED DOOR IN ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By tgordon Date 2008-09-09 Time 14:28 Rev Time 0.40
Received By tgordon Date 2008-09-09 Time 14:27 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By tgordon Date 2008-07-09 Time 16:11 Rev Time 0.45
Received By tgordon Date 2008-07-09 Time 16:11 Sent To Z
Notes
2008-07-09 16:36:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMIT MECHANICAL PLANS AS THE AIR HANDLER
 AND CONDENSER UNIT ARE BEING INSTALLED AT THE NEW
 ADDITION, PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE SHOW ON PLANS WERE THE CLOTHES DRYER VENT
 WILL TERMINATE AT, BE INFORMED THE CLOTHES DRYER VENT
 MAY NOT TERMINATE NEAR THE A/C CONDENSER UNIT, PER 2004
 FBC/R R303.4.2.
  
 4) THE EXISTING BATH 2 WILL REQUIRE AN EXHAUST FAN AS
 THE WINDOW IS BEING ENCLOSED, IF THEIR IS AN EXHAUST
 FAN IN THE ROOM, SHOW A EXISTING FAN IF NOT SHOW A NEW
 FAN, PER 2004 FBC/R303.3 EXCEPT.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 PREFAB FIREPLACE, PER 2004 FBC/R R1004.
  
 6) PER FS 553.885CARBON MONOXIDE ALARM REQUIRED.--
 EVERY BUILDING FOR WHICH A BUILDING PERMIT IS ISSUED
 FOR NEW CONSTRUCTION ON OR AFTER JULY 1, 2008, AND
 HAVING A FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A
 FIREPLACE, OR AN ATTACHED GARAGE SHALL HAVE AN APPROVED
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. PLEASE
 COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-09-16 Cont ID  
Sent By mperson Date 2008-09-16 Time 08:28 Rev Time 0.00
Received By mperson Date 2008-09-16 Time 08:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By btrobaug Date 2008-07-11 Time 13:20 Rev Time 0.00
Received By mperson Date 2008-07-25 Time 11:48 Sent To B
Notes
2008-07-25 12:14:20PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 4, SANITARY PLUMBING RISER DIAGRAM: PLEASE
 CORRECT THE FOLLOWING ON THE RISER DIAGRAM PER FBC-2004
 PLUMBING SECTIONS
 A} THE BRANCH DRAIN AND STACK TO THE WASHING MACHINE
 SHALL BE 3 INCH (3"). PER SECTION 406.3 WASTE
 CONNECTIONS.
 B} A CLEANOUT IS REQUIRED FOR THE WASHING MACHINE
 STACK AND IT SHALL BE ACCESSIBLE. PLEASE LOCATE THE
 CLEANOUT TO THE EXTERIOR OR LOCATE IT AT 4' A.F.F.. PER
 SECTION 708.3.5 BASE OF STACK AND SECTION 708.9
 ACCESS.
 C} THE KITCHEN SINK MUST DRAIN DOWNSTREAM OF WET
 VENTED BATHROOM 2. PER SECTION 909.1 WET VENT
 PERMITTED.
 D} THE DEMO OF THE OLD WASHING MACHINE BRANCH DRAIN
 CAN NOT HAVE ANY DEAD ENDS.THE BRANCH DRAIN MUST BE
 TERMINATED WITHIN 2 FEET OF THE MAIN, AND PLEASE
 CLEARLY INDICATE THIS ON THE RESUBMITTAL . PER SECTION
 704.5 DEAD ENDS.
 E} A CLEANOUT IS REQUIRED AT THE BASE OF THE LAV STACK
 IN THE MASTER BATH. PER SECTION 708.3.5 BASE OF STACK.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-24 Cont ID  
Sent By bpowell Date 2008-09-24 Time 09:37 Rev Time 0.00
Received By bpowell Date 2008-09-24 Time 09:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-08 Cont ID  
Sent By bpowell Date 2008-09-08 Time 22:53 Rev Time 0.00
Received By bpowell Date 2008-09-08 Time 22:56 Sent To  
Notes
2008-09-08 22:55:521. ALTHOUGH THERE IS A NOTE STATING THAT THE TRUSS
 LAYOUT CONFORMS TO THE BUILDING STRUCTURE THE TRUSS
 LAYOUT PLAN DOES NOT MATCH THE ROOF FRAMING PLAN.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE CONTACT:
 BOBBY POWELL JR., PLANNER, [email protected], (561)
 822-1401

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By bpowell Date 2008-07-22 Time 15:29 Rev Time 0.00
Received By bpowell Date 2008-07-22 Time 15:29 Sent To  
Notes
2008-07-22 15:45:301.PLEASE INCLUDE A LANDSCAPE PLAN PURSUANT TO SECTION
 94-441 OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS AS THE VALUE OF THE PROPOSED WORK EXCEEDS
 50 PERCENT OF THE VALUE OF THE STRUCTURE.
  
 2.PLEASE MAKE SURE THAT ALL PLANS ARE CONSISTENT. THE
 ROOF FRAMING PLAN DOES NOT MATCH THE TRUSS PLAN.
  
 3.PLEASE SHOW THE LOCATION OF ALL MECHANICAL
 EQUIPMENT.THE AIR CONDITIONER SHOWN ON THE ELECTRICAL
 PLAN MUST BE SHOWN ON THE SITE PLAN AND CAN NOT PROJECT
 MORE THAN FOUR (4) FEET INTOSETBACKS.
  
 4.PLEASE INCLUDE DIMENSION LINES SHOWING THE HEIGHT
 OF THE BUILDING.THE HEIGHT SHALL BE MEASURED FROM THE
 FINISHED GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR A GABLE ROOF.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE CONTACT:
 BOBBY POWELL JR., PLANNER, [email protected], (561)
 822-1401