Plan Review Details - Permit 08070215
Plan Review Stops For Permit 08070215
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-08 Cont ID  
Sent By shill Date 2009-01-08 Time 18:01 Rev Time 0.00
Received By shill Date 2009-01-02 Time 11:20 Sent To  
Notes
2009-01-08 18:02:26****CORRECTIONS****
 ****PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ADDRESSED.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 561-233-5025. THIS MAY BE DONE AS A PART
 OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE
 STRUCTURAL PERMIT WILL BE ISSUED FIRST.
  
 3. ADDRESSED.
  
 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO
 MARCH 1, 2009 TO BE ISSUED UNDER FBC2004 W/2007
 REVISIONS AS GOVERNING CODE. THIS IS A PLAN CHECK ONLY.
 THE PLAN REVIEW WILL REMAIN IN FAILED STATUS UNTIL A
 PERMIT APPLICATION IS SUBMITTED.
  
 5-6. PLEASE INCLUDE A COPY OF THE THRESHOLD INSPECTION
 PLAN AND THE RESIDENT INSPECTOR AGREEMENT IN THE
 RESUBMITTAL OR ADVISE IF IT IS A PART OF THE STRUCTURE
 SHELL PERMIT.
  
 7-12. ADDRESSED.
  
 13. SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS
 WITH DIMENSIONS ON THE PLAN. NOTE THAT EXTENSIONS ARE
 NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN
 ON THE SECTION, A6.
  
 2ND REVIEW, HANDRAIL EXTENSIONS NOT SHOWN AT TOP OF
 STAIR 2, LS1; TOP OF STAIR 1, LS1; FRONT STAIR,
 REMODELED STAIR ENCLOSURE (A2), FIRST FLOOR (A1). IT
 APPEARS THAT THE REQUIRED STAIR EXTENSION AT STAIR 2
 MAY INTERFERE WITH DOOR SWING. REMODELED SECOND FLOOR
 PLAN A2 SHOWS HANDRAIL ON ONE SIDE ONLY (CENTER).
 PLEASE CHECK ALL STAIR PLANS.
  
 3RD REVIEW, COMMENT WAS NOT ADDRESSED. ARCHITECT?S
 RESPONSE WAS: ?ALL STAIR PLANS HAVE BEEN CHECKED AND
 UPDATED TO SHOW THE REQUIREMENTS SET FORTH BY SECTION
 1009.11.5. SEE SHEET LS-1 FOR COMPLIANCE NOTES.?
  
 PLEASE SEE FBC1009.11.5: HANDRAIL EXTENSIONS. HANDRAILS
 SHALL RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR
 SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT
 STAIR FLIGHT. WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP RISER
 AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND
 THE BOTTOM RISER.?
  
 I HAVE HIGHLIGHTED THE AREAS WHERE THE HANDRAIL
 EXTENSIONS ARE MISSING ON THE PLAN (SAME LOCATIONS AS
 PREVIOUS REVIEW). PLEASE REVISE HANDRAILS AT THE
 FOLLOWING LOCATIONS (AND CHECK ALL FOR COMPLIANCE):
  
 A. LS1, PROPOSED STAIR CORRIDOR, TOP LEFT OF FLOOR
 PLAN, ONE HANDRAIL IS MISSING THE EXTENSION AT THE TOP.
  
 B. LS1, PROPOSED ROOF TOP LIFE SAFETY PLAN, TOP LEFT,
 NO EXTENSION ON ONE SIDE OF THE HAND RAIL, TOP. THIS
 EXTENSION WILL BLOCK THE DOOR.
  
 C. LS1, PROPOSED STAIR CORRIDOR, MIDDLE SECTION OF
 STAIR AT LANDING, BY THE 48? DOOR, NO EXTENSION AT
 BOTTOM OF STAIR RUN WHERE THE STAIR CHANGES DIRECTION;
 AS DRAWN, HANDRAIL TO THE INSIDE ENDS BEFORE THE END OF
 THE LAST TREAD.
  
 D. LS1, PROPOSED ROOF TOP LIFE SAFETY PLAN, TOP STAIR
 #2, NO EXTENSION AT THE TOP OF THE STAIR (BY THE DOOR).
 IT APPEARS THAT THIS EXTENSION WILL BLOCK THE DOOR
 (SAME STAIR AREA AS ITEM B).
  
 E. A2, PROPOSED STAIR CIRCULATION PLAN, TOP STAIR #2,
 NO EXTENSION AT THE TOP OF THE STAIR (SAME AS B AND D).
  
 F. SAME STAIR AS (E), A2, PROPOSED STAIR CIRCULATION
 PLAN, INTERMEDIATE LANDING NEAR DOOR 201 MISSING
 HANDRAIL WHERE STAIRS CHANGE DIRECTIONS; ALSO PROPOSED
 STAIR CORRIDOR LIFE SAFETY PLAN LS1.
  
 G. A3 AND LS1, LABELED SOUTH EGRESS STAIR, TOP, BOTH
 SIDES, EXTENSIONS APPEAR LESS THAN THE REQUIRED 12
 INCHES.
  
 14-23. ADDRESSED.
  
 24. CODE COMPLIANCE FOR THIS ITEM (BUILDING TYPE)
 SHOULD BE SHOWN ON THE STRUCTURAL PERMIT, BUT SHOULD BE
 INCLUDED ON THIS PLAN AS WELL. THE NEW PLAN HAS BEEN
 REVISED TO DECLARE TYPE IIIA, RESPONSE LETTER STATES
 THIS IS TYPE IIIB. PLEASE CONFIRM BUILDING TYPE.
  
 25-32. ADDRESSED.
  
 33. PREVIOUS COMMENTS STATED THAT FIRE RESISTANCE IS TO
 BE CONTINUOUS TO THE UNDERSIDE OF THE DECK ABOVE,
 FBC707.4, 707.5. ARCHITECT?S RESPONSE STATED THAT FIRE
 RESISTANCE CONTINUITY REQUIREMENTS WERE STATED ON NTS.
 SEE M2, DUCTWORK SHOWN ABOVE THE STAIRS AND DUCTWORK
 SHOWN IN THE ELEVATOR LOBBY AREA. THE EXIT TERMINATES
 AT THE EXIT DISCHARGE, WHICH WOULD BE THE EXTERIOR
 DOOR, DUCT IS SHOWN AT THE STAIRWAY DOOR.
  
 SHEET A2 SPECIFIES FIRE RATED PARTITIONS FOR THE
 STAIRS. SEE FBC1019.1, FIRE BARRIERS REQUIRED IN
 ACCORDANCE WITH FBC706, NOT FIRE PARTITIONS FBC708. THE
 CONSTRUCTION REQUIREMENTS DIFFER, AND PARTITIONS ARE
 LESS STRINGENT THAN BARRIERS. PLEASE CLARIFY COMPLIANCE
 WITH THE REQUIREMENTS AS A FIRE BARRIER.
  
 FOR INSTANCE, SEE B A12. WALLS W1, W6 SHOW THE WALL
 TERMINATING AT THE CEILING ABOVE RATHER THAN AT THE
 ROOF DECK ABOVE. A A12 ALSO SHOWS THE RATED WALL W6
 ENDING AT A CEILING, RATHER THAN EXTENDING UP TO THE
 BOTTOM OF THE ROOF DECK. IT ALSO SHOWS A 1 HOUR FIRE
 RATED CEILING ABOVE THE STAIR, NOT CLEAR HOW THIS
 COMPLIES WITH THE REQUIREMENT FOR FIRE RATING TO BE
 CONTINUOUS TO THE ROOF DECK OR FLOOR/CEILING ASSEMBLY
 ABOVE. SEE ALSO A14.
  
 AS STRUCTURALS ARE NOT A PART OF THIS PERMIT, AND THE
 RENOVATION IS SOMEWHAT COMPLEX, IT IS DIFFICULT TO
 DETERMINE EXACT CONSTRUCTION BASED ON THE INFORMATION
 PROVIDED. THE WALLS ARE SPECIFIED AS RATED WALLS,
 STRUCTURAL ELEMENTS RATED, BUT NOTE THE REQUIREMENT FOR
 THE SUPPORTING CONSTRUCTION TO BE RATED AS WELL,
 INCLUDING EXISTING CONSTRUCTION (VERTICAL EXITS).
 ARCHITECT?S RESPONSE STATES THAT THE WALLS ARE
 CONTINUOUS, THE PLANS STATE THEY ARE CONTINUOUS, BUT
 THE DETAILS PROVIDED DO NOT SHOW CONTINUOUS WALLS.
 PLEASE REVISE DETAILS TO CLEARLY SHOW COMPLIANCE WITH
 FBC707.4, 707.5, AND REVISE NOTES WHICH SPECIFY FIRE
 PARTITIONS TO SPECIFY FIRE BARRIERS AS REQUIRED BY
 FBC1019.1. ALSO COORDINATE WITH MECHANICAL ENGINEER;
 CLARIFY DUCTS IN THE OPEN SPACE ABOVE STAIRS, WHEN
 STAIR WALLS SHOULD EXTEND TO THE UNDERSIDE OF THE ROOF
 DECK; THERE SHOULD NOT BE AN OPEN SPACE. IF NECESSARY,
 PROVIDE ADDITIONAL SECTION DETAILS TO SHOW COMPLIANCE.
  
 35-36. ADDRESSED.
  
 37. THE STAIR LABELED "FRONT EGRESS STAIR" SHOWS AN
 ELEVATOR LOBBY IN THE STAIR ENCLOSURE ON THE FIRST
 FLOOR. SEE A1. PLEASE SEE FBC1019.1.
  
 3RD REVIEW, RESPONSE LETTER STATES THAT NO MECHANICAL
 EQUIPMENT IS IN THE STAIR ENCLOSURE. SEE SHEET A1,
 BOTTOM LEFT. THIS PLAN SHOWS THE STAIR AND THE ELEVATOR
 IN THE SAME ENCLOSURE. THIS STAIR IS LABELED A "MEANS
 OF EGRESS STAIR". TWO EXITS ARE REQUIRED FROM THIS
 SPACE, FBC1018.1, NOT MEANS OF EGRESS. EXITS SHALL BE
 CONTINUOUS, FBC1018.3. VERTICAL EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS,
 FBC1019.1. SEE ALSO DEFINITION OF EXIT, FBC1002.
  
 NEW COMMENT:
  
 38. FP SHEETS, DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS471. SHEETS SUBMITTED DO NOT INCLUDE
 A SIGNATURE, DATE, AND SEAL AND THE PRINTED NAME AND
 LICENSE NUMBER OF THE PERSON WHO IS RESPONSIBLE FOR THE
 DOCUMENT.
  
 39. SEE M2, DUCTS SHOWN THROUGH THE WALL, BUT ISN?T
 THIS WALL ON THE PROPERTY LINE? SEE FBC TABLE 602,
 FBC704.8, NO OPENINGS ALLOWED FOR A. PREVIOUS COMMENTS
 REQUESTED THAT ALL FIRE RATED WALLS AND OTHER ELEMENTS
 BE NOTED ON THE PLAN.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-10 Cont ID  
Sent By shill Date 2008-10-10 Time 11:45 Rev Time 0.00
Received By shill Date 2008-10-06 Time 08:20 Sent To  
Notes
2008-10-10 11:45:47****CORRECTIONS****
 ****PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ADDRESSED.
  
 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 561-233-5025. THIS MAY BE DONE AS A PART
 OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE
 STRUCTURAL PERMIT WILL BE ISSUED FIRST.
  
 3. ADDRESSED.
  
 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO
 MARCH 1, 2009 TO BE ISSUED UNDER FBC2004 W/2007
 REVISIONS AS GOVERNING CODE. THIS IS A PLAN CHECK ONLY.
 THE PLAN REVIEW WILL REMAIN IN FAILED STATUS UNTIL A
 PERMIT APPLICATION IS SUBMITTED.
  
 5-6. PLEASE INCLUDE A COPY OF THE THRESHOLD INSPECTION
 PLAN AND THE RESIDENT INSPECTOR AGREEMENT IN THE
 RESUBMITTAL.
  
 7-12. ADDRESSED.
  
 13. SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS
 WITH DIMENSIONS ON THE PLAN. NOTE THAT EXTENSIONS ARE
 NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN
 ON THE SECTION, A6.
  
 2ND REVIEW, HANDRAIL EXTENSIONS NOT SHOWN AT TOP OF
 STAIR 2, LS1; TOP OF STAIR 1, LS1; FRONT STAIR,
 REMODELED STAIR ENCLOSURE (A2), FIRST FLOOR (A1). IT
 APPEARS THAT THE REQUIRED STAIR EXTENSION AT STAIR 2
 MAY INTERFERE WITH DOOR SWING. REMODELED SECOND FLOOR
 PLAN A2 SHOWS HANDRAIL ON ONE SIDE ONLY (CENTER).
 PLEASE CHECK ALL STAIR PLANS.
  
 14-19. ADDRESSED.
  
 24. LS1, BUILDING TYPE 5A DECLARED. PLEASE NOTE ALL
 REQUIRED FIRE RESISTANCE ON THE PLAN, BOTH VERTICAL AND
 HORIZONTAL, INCLUDING THE VENTILATION SHAFT. SEE FBC
 TABLE 601 AND 602, ALL EXTERIOR WALLS TO BE A MINIMUM
 OF 1 HOUR. ONE WALL IS SHOWN AS HAVING A 1 HOUR RATING,
 BUT THE OTHER THREE DO NOT. THERE ARE GENERAL NOTES,
 BUT THE PLAN IS TO BE SPECIFIC AS TO REQUIREMENTS
 FBC*106.
  
 SEE OTHER COMMENTS. FOR INSTANCE, SEEA9. RATING NOT
 SHOWN FOR THE ROOFTOP DECK, UL ASSEMBLIES NOTED ON
 ANOTHER PAGE BUT UL ASSEMBLIES NOT NOTED FOR THESE
 DETAILS. PLEASE REVISE TO CLEARLY SHOW WHICH ELEMENTS
 ARE TO FIRE RESISTANCE RATED, AND HOW THEY WILL COMPLY
 WITH THESE REQUIREMENTS. THIS APPLIES TO ALL EXTERIOR
 WALLS (1 HOUR), ALL BEARING WALLS, FLOOR AND ROOF. ANY
 EXCEPTIONS, IF ANY ARE APPLICABLE, SHOULD BE NOTED ON
 THE PLAN.
  
 THE RESPONSE LETTER STATES THAT FIRE RATING FOR BEAMS
 IS NOTED. PLEASE INCLUDE OTHER REQUIRED ELEMENTS.
 PLEASE FEEL FREE TO CONTACT ME IF NECESSARY TO DISCUSS.
  
 25-28. ADDRESSED.
  
 29. PROVIDE PRODUCT APPROVALS FOR THE HARDIPANEL AND
 EXTERIOR DOORS, FAC9B72.
  
 30-31. ADDRESSED.
  
 32. SEE A10, UL ASSEMBLIES ARE SPECIFIED. PLEASE
 PROVIDE A DETAIL OF EACH UL ASSEMBLY ON THE PLAN.
  
 THIS COMMENT WAS NOT INCLUDED IN THE RESPONSE LETTER.
 X629, N609, D784, D935 ARE LISTED BUT SHEET A3 SHOWS
 ONLY TWO UL ASSEMBLIES. ALL FIRE RESISTIVE RATED
 DETAILS SHOULD BE INCLUDED AND DEMONSTRATE EITHER
 CALCULATED FIRE RESISTANCE, PRESCRIPTIVE OR TESTED
 ASSEMBLY FBC703.2. FOR INSTANCE, W4 ON SHEET A3. THIS
 EXTERIOR WALL SHOULD BE RATED FROM BOTH SIDES,
 FBC704.5, BUT THE DETAIL DOES NOT SPECIFY ANY FIRE
 RESISTANCE RATING. FOR EACH WALL TYPE, FIRE RESISTANCE
 SHOULD BE STATED. THERE ARE NOTES REGARDING FIRE
 RESISTANCE RATED WALLS, BUT I WAS UNABLE TO EASILY
 DETERMINE WHICH WALLS AND OTHER COMPONENTS ARE TO BE
 RATED.
  
 33. SEE A10 AND FBC TABLE 601. TYPE 5A REQUIRES THAT
 ALL STRUCTURAL FRAME AND FLOOR BE 1 HOUR RATED, BUT NOT
 ALL STRUCTURAL ELEMENTS ARE SHOWN AS FIRE RESISTIVE
 RATED. PLEASE REVISE.
  
 SHEET A10 WAS ADDED AND SHOWS FIRE RATING FOR BEAMS.
 SEE FBC TABLE 601. 1 HOUR IS REQUIRED FOR BEARING
 WALLS, FLOORS, AND ROOF. THE REQUIRED RATING, INCLUDING
 EXISTING ELEMENTS, SHOULD BE NOTED ON THE PLAN. DETAILS
 FOR EXISTING ELEMENTS ARE NOT NECESSARILY REQUIRED (BUT
 PLEASE CLARIFY HOW 1 HOUR FOR THE EXISTING ROOF WAS
 ACCOMPLISHED), BUT SHOULD BE NOTED ON THE PLAN IN THE
 CASE THAT THESE WALLS ARE PENETRATED BY VARIOUS TRADES.
  
 THE SHAFT ENCLOSURE DETAIL WAS ADDED ON A3; STAIR
 DETAILS ON A12 AND OTHER SHEETS; FIRE RESISTANCE IS TO
 BE CONTINUOUS TO THE UNDERSIDE OF THE DECK. FBC707.4,
 FBC707.5.
  
 34. PROVIDE INFORMATION (SPEC SHEETS) FOR THE
 INTUMESCENT PAINT, FBC7, FBC*106.
  
 35. ENERGY CALCS REQUIRED, FBC13-101.1.2.
  
 36. ADDRESSED.
  
 NEW COMMENT:
  
 37. THE STAIR LABELED ?FRONT EGRESS STAIR? SHOWS AN
 ELEVATOR LOBBY IN THE STAIR ENCLOSURE ON THE FIRST
 FLOOR. SEE A1. PLEASE SEE FBC1019.1. ALSO SEE
 MECHANICAL COMMENTS REGARDING MECHANICAL EQUIPMENT IN
 THE STAIR ENCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-28 Cont ID  
Sent By shill Date 2008-07-28 Time 15:18 Rev Time 0.00
Received By shill Date 2008-07-22 Time 09:32 Sent To  
Notes
2008-07-28 15:19:00****CORRECTIONS****
 ****PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE CERTIFICATE OF AUTHORIZATION IS TO BE PRINTED
 ON EACH SHEET, SMITH ENGINEERING CONSULTANTS, INC.,
 FAC61G15-23.002.
  
 2.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.THE
 PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025.THIS MAY BE DONE AS A PART
 OF THE STRUCTURAL PERMIT, AS IT IS LIKELY THAT THE
 STRUCTURAL PERMIT WILL BE ISSUED FIRST.
  
 3.DECLARE TOTAL SQUARE FOOT AREA, PER FLOOR, EXISTING
 BUILDING.DECLARE TOTAL SQUARE FOOT AREA PER FLOOR,
 PROPOSED NEW.PLEASE INCLUDE THE AREA CALCULATIONS
 PRIOR TO IMPACT FEE ASSESSMENT.FOR THE THIRD FLOOR,
 PLEASE NOTE AREA UNDER ROOF, UNDER AIR AND
 UNCONDITIONED, FBC CHAPTER 5 AND IMPACT FEE
 ASSESSMENT.
  
  
 4. INFORMATIONAL, A PERMIT MUST BE APPLIED FOR PRIOR TO
 DECEMBER 31, 2007 TO BE ISSUED UNDER FBC2004 W/2007
 REVISIONS AS GOVERNING CODE.THIS IS A PLAN CHECK
 ONLY.
  
 5.THREE SETS OF PLANS REQUIRED FOR A THRESHOLD
 BUILDING, FS553.71(7), TWO SETS IF IT IS NOT A
 THRESHOLD BUILDING.ALTHOUGH THIS IS A PLAN REVIEW,
 ALL SETS ARE REQUIRED TO BE SUBMITTED AS ALL CITY
 STAMPS ARE PLACED ON EACH SHEET WITH THE EXCEPTION OF
 THE DATE STAMP WHEN EACH TRADE PASSES REVIEW.REVIEWS
 REMAIN IN FAILED STATUS. AFTER A PERMIT IS APPLIED FOR,
 THE REVIEWS ARE CHANGED TO PASS AND, AS ALL STAMPS ARE
 ALREADY ON EACH SHEET, NO ADDITIONAL PLAN REVIEWS ARE
 REQUIRED.FAILURE TO INCLUDE ALL REQUIRED SETS WILL
 RESULT IN A DELAY OF ISSUANCE.
  
 6. THRESHOLD INSPECTOR, FBC*105.13.6 AND FS 553.79(5);
 PLEASE CONTACT KEN CONRAD, 561-805-6666.A
 PRECONSTRUCTION MEETING BETWEEN THE CITY, OWNER,
 CONTRACTOR, SPECIAL INSPECTOR, AND DESIGNER IS
 REQUIRED.APPROVAL OF THE SPECIAL INSPECTOR AND THE
 PRECONSTRUCTION MEETING IS REQUIRED PRIOR TO PERMIT
 ISSUANCE.
  
 7.SEE FBC105.13.4.4 AND FS553.79, THE STATEMENT
 REGARDING CODE COMPLIANCE IS REQUIRED ON THE PLAN FOR
 THRESHOLD BUILDINGS.
  
 8.CS, DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
  
 9.PLANS SHOW REMODELED RESTROOM ON 2ND FLOOR.IT IS
 NOT CLEAR; IS THIS PART OF THIS PERMIT?SPECIFICATIONS
 NOT PROVIDED.
  
 10. A8 SHOWS CABANA TBD, OTHER PLACES SHOW CANVAS
 AWNING.PLEASE CLARIFY.NOTE THAT SEPARATE PERMITS
 WILL BE REQUIRED FOR CANVAS AWNINGS.
  
 11.CS, GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 12. SEE FBC TABLE 503, 50 FEET MAXIMUM FOR A2, TYPE VA
 (NOT 55 FEET AS STATED ON PLAN).
  
 13.SEE FBC1009.11.5, PLEASE SHOW HANDRAIL EXTENSIONS
 WITH DIMENSIONS ON THE PLAN.NOTE THAT EXTENSIONS ARE
 NOT SHOWN ON THE PLAN A3, OTHER PLACES, BUT ARE SHOWN
 ON THE SECTION, A6.
  
 14.SEE FBC11-4.10, ACCESSIBLE ELEVATORS, PLEASE NOTE
 REQUIREMENTS ON THE PLAN.ALSO SEE FBC11-4.10.6, A
 SWING DOOR IS SHOWN A1, BUT ELEVATOR DOOR IS REQUIRED
 TO OPEN AUTOMATICALLY.
  
 15.A1, BOTTOM LEFT, DOES THE NEW DOOR LEAD TO THE
 OUTSIDE?THIS AREA, BETWEEN THE DOOR AND THE OUTSIDE,
 SHOULD HAVE THE SAME LEVEL OF FIRE RESISTANCE AS THE
 STAIRS, FBC1002, FBC1018.3.PLEASE NOTE ON THE PLAN.
  
 16.FBC1003.6, FBC1005.2, THE NEW DOOR (SHEET A1,
 BOTTOM LEFT) ALONG WITH THE DOOR FOR THE EMPLOYEE
 LOCKERS BLOCKS THE EGRESS FOR THE EXISTING EXIT AT THE
 END OF THE CORRIDOR.
  
 17.A DOOR HARDWARE SCHEDULE WAS NOT PROVIDED.PLEASE
 SEE FBC1008.1.8.7 AND NOTE ALL PROPOSED LOCKS AND EXIT
 HARDWARE FBC1008.1.9.
  
 18.A2, PLEASE PROVIDE STAIR DIMENSIONS; WIDTH, TREAD,
 RISER, AND LANDING DIMENSIONS FBC1009.3, FBC1009.4.
 NOTE THAT LANDINGS DO NOT APPEAR TO COMPLY WITH
 FBC1009.4, WIDTH OF LANDINGS SHALL NOT BE LESS THAN THE
 WIDTH OF THE STAIRWAYS THEY SERVE.
  
 19. A1, SEE FBC1008.1.8.8, DOOR SHOULD NOT PROJECT MORE
 THAN 7 INCHES INTO THE REQUIRED WIDTH OF A CORRIDOR
 WHEN FULLY OPEN.THE NEW PLANTER OBSTRUCTS THE DOOR
 SWING.SHOW COMPLIANCE WITH FNC1008.1.8.8.
  
 20.A1, DECLARE OCCUPANT LOAD FOR EXISTING FIRST
 FLOOR; REQUIRED TO DETERMINE REQUIRED EGRESS WIDTH, SEE
 OTHER COMMENTS.
  
 21. A2, PROPOSED STAIR CIRCULATION PLAN, SEE DOUBLE
 DOORS ON LEFT SIDE.SHOW THE DIMENSION OF CLEAR FLOOR
 SPACE ON THE LANDING WITH THE DOORS IN THE OPEN
 POSITION FBC1005.2.SHOW THE REQUIRED WIDTH; APPEARS
 TO BE
  
 22.A2 SHOWS LIQUOR STORAGE.PLEASE SEE TABLE
 FBC307.7(1), AND NOTE MAXIMUMS WHICH WILL BE STORED ON
 THE PLAN. PLEASE ALSO SEE FOOTNOTES.
  
 23. INFORMATIONAL, AS THE STRUCTURAL SHEETS PREPARED BY
 CUTCHER AND GINSBURG WERE SUBMITTED SEPARATELY, THERE
 MAY BE SOME DUPLICATION REQUIRED FOR INFORMATION.BOTH
 PERMITS WILL BE REQUIRED TO SHOW CODE COMPLIANCE
 INDEPENDENTLY.
  
 24.LS1, BUILDING TYPE 5A DECLARED.PLEASE NOTE ALL
 REQUIRED FIRE RESISTANCE ON THE PLAN, BOTH VERTICAL AND
 HORIZONTAL, INCLUDING THE VENTILATION SHAFT.SEE FBC
 TABLE 601 AND 602, ALL EXTERIOR WALLS TO BE A MINIMUM
 OF 1 HOUR.ONE WALL IS SHOWN AS HAVING A 1 HOUR
 RATING, BUT THE OTHER THREE DO NOT.THERE ARE GENERAL
 NOTES, BUT THE PLAN IS TO BE SPECIFIC AS TO
 REQUIREMENTS FBC*106.
  
 25.FBC903.2.1.2, 903.3.1.1, PLEASE CLARIFY SHEET FP3,
 ROOF FIRE PROTECTION PLAN; IS THIS THE OLD ROOF AREA?
 FIRE SPRINKLERS REQUIRED IN THIS CONCEALED SPACE, AND
 IT APPEARS THAT A SPRINKLER PLAN WAS SUBMITTED BUT THE
 TITLE OF THE PLAN IS CONFUSING AS THIS AREA IS NO
 LONGER A ROOF.
  
 26. PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH
 FIRE RESISTIVE RATED ASSEMBLIES, FBC712.
  
 27.PLANS SHOW FIRE RATED DOORS.SEE FBC TABLE 715.3,
 SPECIFY REQUIREMENT.
  
 28. THERE IS A DOOR BETWEEN THE GAZEBO AND STAIR 2 AT
 THE TABLE SEATING AREA.HOW MANY OCCUPANTS DOES THAT
 DOOR SERVE?IT IS CLOSEST TO STAIR 2, SEE FBC1008.1.2
 REGARDING DOOR SWING.
  
 29.PROVIDE PRODUCT APPROVALS FOR THE HARDIPANEL AND
 EXTERIOR DOORS, FAC9B72.
  
 30. A2 SHOWS A RAISED PLATFORM NOTING THAT THIS WILL BE
 ADJUSTED.IS THIS NEW OR EXISTING?STAIRS APPEAR TO
 BE SHOWN BUT NO RAMP, FBC11-4.3.2(3), FBC11-5.7.
  
 31. SHOW ACCESSIBLE SEATING AT FIXED TABLES, FBC11-5.1,
 FBC 11 FIGURE 45.
  
 32. SEE A10, UL ASSEMBLIES ARE SPECIFIED.PLEASE
 PROVIDE A DETAIL OF EACH UL ASSEMBLY ON THE PLAN.
  
 33. SEE A10 AND FBC TABLE 601.TYPE 5A REQUIRES THAT
 ALL STRUCTURAL FRAME AND FLOOR BE 1 HOUR RATED, BUT NOT
 ALL STRUCTURAL ELEMENTS ARE SHOWN AS FIRE RESISTIVE
 RATED.PLEASE REVISE.
  
 34.PROVIDE INFORMATION (SPEC SHEETS) FOR THE
 INTUMESCENT PAINT, FBC7, FBC*106.
  
 35.ENERGY CALCS REQUIRED, FBC13-101.1.2.
  
 36.PROVIDE DETAILS, INCLUDING ALL DIMENSIONS, FOR
 ACCESSIBLE BATHROOMS; TOILET, LAVATORY, GRAB BARS,
 TURNING RADIUS, CLEAR FLOOR SPACE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 16:41 Rev Time 0.00
Received By btrobaug Date 2008-12-18 Time 16:01 Sent To  
Notes
2008-12-18 16:35:00 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE SAME COMMENT AS THE PREVIOUS TWO REVIEWS
  
 3} INDICATE COMPLIANCE WITH LIGHTING POWER
 DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.***THE WATTAGES FOR THE FIXTURES WAS ON
 SHEET E-4, BUT NO COUNTS, TOTAL WATTAGES, ALLOWED
 WATTAGES ETC***FORM A CANNOT BE USED FOR AN EXISTING
 BUILDING, SEE REFERENCED SECTIONS GIVEN IN THE PREVIOUS
 REVIEWS.
  
 NEW COMMENT:
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.***
 THE ELECTRICAL ENGINEER USED A RUBBER STAMP INSTEAD OF
 HIS SIGNATURE IN VIOLATION OF THE FAC. THE ELECTRICAL
 PLANS ARE BEING RETAINED TO SEND TO THE BOARD OF
 ENGINEERS FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-19 Cont ID  
Sent By btrobaug Date 2008-09-19 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2008-09-19 Time 15:54 Sent To  
Notes
2008-09-19 16:06:21 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE SAME COMMENT AS THE PREVIOUS REVIEW
  
 3} INDICATE COMPLIANCE WITH LIGHTING POWER
 DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.***THE WATTAGES FOR THE FIXTURES WAS ON
 SHEET E-4, BUT NO COUNTS, TOTAL WATTAGES, ALLOWED
 WATTAGES ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By btrobaug Date 2008-07-21 Time 09:52 Rev Time 0.00
Received By btrobaug Date 2008-07-18 Time 14:13 Sent To  
Notes
2008-07-18 14:35:29 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ADDRESS OF THE PROJECT IS INCORRECT ON THE
 ELECTRICAL SHEETS 106.1.1 FBC AS AMENDED.
  
 2} SUBMIT THREE SETS OF PLANS FOR REVIEW PER 106 FBC AS
 AMENDED.
  
 3} INDICATE COMPLIANCE WITH LIGHING POWER
 DENSITIES.13-415.2B OR 13-415.2.C.1. FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-04-20 Cont ID  
Sent By mcarsill Date 2009-04-20 Time 16:46 Rev Time 0.00
Received By mcarsill Date 2009-04-20 Time 16:46 Sent To  
Notes
2009-04-20 16:47:36PER THE REQUEST OF ROBERT BROWN, ASSISTANT BUILDING
 OFFICIAL, REVIEWED ELECTRICAL DRAWINGS FOR ROXY'S, 309
 CLEMATIS STREET.
  
 ELECTRICAL SHEETS APPEARED TO BE SATISFACTORY.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-01-26 Cont ID  
Sent By mcarsill Date 2009-01-26 Time 16:12 Rev Time 0.00
Received By mcarsill Date 2009-01-26 Time 16:09 Sent To  
Notes
2009-01-26 16:12:401. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL.
  
 2. COULD NOT LOCATE ANY ELECTRICAL SHEETS EXCEPT FOR
 EP-1.
  
 3. LIFE SAFETY PLAN ONLY INDICATES TWO ILLUMINATED EXIT
 SIGNS WHICH CANNOT BE SEEN FROM ALL AREAS OF THE
 ROOFTOP. THE TWO SIGNS ARE BLOCKED BY ARCHITECTURAL
 FEATURES.
  
 4. PLEASE SUBMIT A COMPLETE SET OF PLANS FOR APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-15 Cont ID  
Sent By mcarsill Date 2008-09-15 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2008-09-15 Time 14:44 Sent To  
Notes
2008-09-15 15:02:331. ANY REQUIRED FIRE AND LIFE SAFETY SYSTEMS WHICH
 INCLUDES THE FIRE SPRINKLER OR FIRE ALARM SYSTEM THAT
 IS SHUT DOWN FOR MORE THAN 4 HOURS IN A TWENTY FOUR
 HOUR PERIOD WILL REQUIRE A FIRE WATCH. ALL FIRE WATCH
 ACTIVITIES SHALL BE REQUESTED IN WRITING TO THE
 BATTALION CHIEF OF FIRE PREVENTION OR HIS DESIGNEE.
 PERSONNEL PERFORMING FIRE WATCH ACTIVITIES SHALL HAVE
 NO OTHER DUTIES EXCEPT TO PATROL ALL AREAS OF THE
 BUILDING. THESE PERSONNEL ARE REQUIRED TO MAINTAIN A
 LOG OF ACTIVITIES AND BE ABLE TO REPORT EMERGENCIES
 IMMEDIATELY.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER OR FIRE ALARM REMODELING ACTIVITIES.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLEASE ENSURE THAT ALL EXISTING EMERGENCY LIGHTING
 EQUIPMENT WITHIN THE STAIRWELLS AND IN OTHER LOCATIONS
 ARE OPERATING CORRECTLY.
  
 5. ON PAGE FP-3 STANDPIPE CONNECTIONS ARE SHOWN. THE
 BUILDING DOES NOT HAVE A STANDPIPE SYSTEM SO THE
 STANDPIPE SYSTEM ILLUSTRATED ON THE ROOF ARE NOT
 REQUIRED.
  
 6. FIRE LINE BACKFLOW DEVICE SHALL BE EQUIPPED WITH
 TAMPER SWITCHES, CHAIN AND LOCK.
  
 7. COULD NOT LOCATE NOTES ON ON NOTES PAGE RELATING TO
 CUTTING OR WELDING OPERATIONS OR TO THE FIRE CODE, NFPA
 51B, THAT RELATES TO THIS ACTIVITY.
  
 8. ON PAGE M-2 AIR CONDITIONING EQUIPMENT APPEARS TO BE
 LOCATED IN STAIRWELLS. NFPA 101, THE LIFE SAFETY CODE,
 SECTION 7.1.3.2.1 (6) STIPULATES EQUIPMENT THAT CAN BE
 CONTAINED IN STAIRWELLS. PLEASE REVIEW.
  
 9. EMERGENCY PLAN FOR THE BUILDING NEEDS TO BE PREPARED
 AND SUBMITTED TO THIS OFFICE FOR REVIEW.
  
 10. PLEASE EXPLAIN THE NON RATED DOOR FOR THE PROPOSED
 DRY STORAGE GOODS AREA DIRECTLY ADJACENT TO THE TWO
 RATED FIRE DOORS. IT APPEARS THAT PERSONS WILL HAVE TO
 PASS THIS NON RATED DOOR IN AN EXIT ACCESS AREA TO
 REACH THE RATED FIRE DOORS.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By mcarsill Date 2008-07-14 Time 11:31 Rev Time 0.00
Received By mcarsill Date 2008-07-14 Time 11:31 Sent To  
Notes
2008-07-14 12:21:371. ALL CONSTRUCTION, ALTERATION, AND DEMOLITION WORK
 SHALL COMPLY WITH NFPA 241, THE STANDARD FOR THE
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM ADDITIONS. NO FIRE SPRINKLER
 PLANS SUBMITTED WITH DRAWINGS.
  
 3. NO INFORMATION PROVIDED THAT INDICATES THE FACILITY
 WILL BE OPEN OR CLOSED DURING THE CONSTRUCTION WORK
 REQUIRED FOR THE ROOFTOP AREA. PROPER SEPARATION
 BETWEEN CONSTRUCTION AND NONCONSTRUCTION AREAS SHALL BE
 PROVIDED. ALL EXITS ARE TO REMAIN CLEAR AND UNBSTRUCTED
 DURING CONSTRUCTION ACTIVITIES.
  
 4. THE EXIT SIGN DIRECTING PERSONS TO STAIR # 2 MAY NOT
 BE READILY VISIBLE. AN ADDITIONAL EXIT SIGN MAY BE
 NEEDED TO DIRECT PERSONS TO STAIR # 2.
  
 5. ANY CANVAS MATERIAL PLANNED TO BE USED SHALL BE FIRE
 RETARDANT SINCE THE CANVAS WILL BE OVER PERSONS HEADS.
  
 6. THE PROPOSED SOUTH ELEVATION DOES NOT DISPLAY THE
 BUILDING ADDRESS. THE ADDRESS IS REQUIRED TO BE
 INSTALLED ON THE PROPER ELEVATION OF THE BUILDING. THE
 ADDRESS SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT
 LEAST 1" WIDE NUMBERS.
  
 7. ALL ELECTRICAL SHEETS DSIPLAY THE WRONG ADDRESS, 311
 CLEMATIS STREET. THE OTHER SHEETS OF THE DRAWINGS
 DISPLAY 309 CLEMATIS STREET.
  
 8. MORE DETAILS NEEDED ON THE GAS LIGHT FIXTURES
 DISPLAYED ON THE PLANS.
  
 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 10. THE PROPOSED THRID FLOOR ROOFTOP DECK PLANS DOES
 NOT ILLUSTRATE PORTABLE FIRE EXTINGUIHSER LOCATIONS.
  
 11. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR
 SCHEDULE LISTING THE APPROPRIATE FIRE RATINGS AND DOOR
 HARDWARE. ALL FIRE RATED DOORS TO COMPLY WITH NFPA 80,
 THE STANDARD FOR FIRE DOORS AND WINDOWS AND SHALL BE
 EQUIPPED WITH SELF-CLOSING DEVICES TO CAUSE THE DOORS
 TO POSITIVELY LATCH WHEN CLOSED.
  
 12. SOME MODIFICATIONS MAY BE NECESSARY TO THE SECOND
 FLOOR AREA DUE TO THE PROPOSED REMODEL AREA.
  
 13. PLEASE PROVIDE STAIR DETAILS FOR THE NEW STAIRS
 THAT ARE BEING PROVIDED. THESE DETAILS SHALL INCLUDE
 STAIR RISE, RUN, AND TREAD DIMENSIONS.
  
 14. PLEASE INDICATE HANDICAP SEATING LOCATIONS ON THE
 PROPOSED ROOF TOP FLOOR PLAN.
  
 15. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 16. PLEASE PROVIDE PRODUCT INFORMATION FOR THE
 INTUMESCENT PAINT DESCRIBED ON SHEET A-10.
  
 17. ALL PROPOSED WALKING SURFACES SHALL BE SLIP
 RESISTANT.
  
 18. THE STORAGE ROOMS AND THE MECHANICAL, ELECTRICAL
 ROOM ON THE ROOF MAY NEED TO BE ONE HOUR FIRE RATED
 DEPENDING ON THE TYPE OF STORAGE AND EQUIPMENT
 CONTAINED WITHIN THEM. PLEASE PROVIDE DETAILS.
  
 19. NO MECHANICAL OR PLUMBING SHEETS PROVIDED WITH
 DRAWINGS.
  
 20. ANY CUTTING AND WELDING ACTIVITIES SHALL CONFORM TO
 THE REQUIREMENTS OF 51B, THE STANDARD FOR CUTTING AND
 WELDING OPERATIONS. A SEPARATION DISTANCE OF AT LEAST
 THIRTY FIVE (35) FEET SHALL BE PROVIDED FROM THESE
 OPERATIONS TO ANY COMBUSTIBLE MATERIALS. IF THIS
 DISTANCE CANNOT BE ACHEIVED, FIRE RATED TARPS ARE TO BE
 USED TO COVER THESE MATERIALS AND A FIRE WATCH BE
 IMPLEMENTED.
  
 21. PLEASE IDENTIFY EXIT DISCHARGE LOCATIONS AND
 IDENTIFY THE MAIN INGRESS/EGRESS ARE FOR THE FACILITY.
  
  
 22. NO INFORMATION PROVIDED REGARDING THE STANDPIPE
 SYSTEM.
  
 23. NO INFORMATION RELATED TO ELEVATOR WARNING SIGNS
 FOR THE ROOFTOP AREA.
  
 24. PLEASE PROVIDE INFORMATION ON EMERGENCY PLANNING
 SHOULD AN EMERGENCY DEVELOP WHILE THE ROOFTOP AREA IS
 IN OPERATION.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-09-08 Cont ID  
Sent By kstevens Date 2008-09-08 Time 10:14 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 12:00 Sent To  
Notes
2008-09-08 10:14:58GAS DELETED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-09-08 Cont ID  
Sent By kstevens Date 2008-08-01 Time 10:13 Rev Time 0.00
Received By kstevens Date 2008-08-01 Time 10:12 Sent To  
Notes
2008-09-08 10:14:27DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. (SEE SHT A-5 KEY
 NOTE 6). SUBMIT THE FOLLOWING INFORMATION FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-01 Cont ID  
Sent By adarroug Date 2008-12-01 Time 08:49 Rev Time 0.00
Received By adarroug Date 2008-12-01 Time 08:49 Sent To  
Notes
2008-12-01 08:54:13TO "COMM" BD#34/PLANS ON RACK--1 ROLL, AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-04 Cont ID  
Sent By adarroug Date 2008-09-04 Time 11:52 Rev Time 0.00
Received By adarroug Date 2008-09-04 Time 11:52 Sent To  
Notes
2008-09-04 11:53:12TO "COMM" BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-10 Cont ID  
Sent By shill Date 2008-08-04 Time 11:33 Rev Time 0.00
Received By shill Date 2008-07-09 Time 15:15 Sent To  
Notes
2008-07-09 15:16:07TO "COMM" BD#51

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2009-06-01 Cont ID  
Sent By rregueir Date 2009-06-01 Time 10:17 Rev Time 0.00
Received By rregueir Date 2009-06-01 Time 10:09 Sent To  
Notes
2009-06-01 10:17:39**TEMP FAIL**
 REVIEW IS IN TEMPORARY FAIL STATUS PENDING RECEIPT OF
 SIGNED PERMIT APPLICATION FROM THE CONTRACTOR.
  
 NOTE: EXTENSION AND RELOCATION OF EXISTING KITCHEN
 EXHAUST SHALL BE UNDER SEPARATE PERMIT AND EXCLUDED
 FROM THIS SCOPE OF WORK.
  
 NOTE FOR YOUR INFORMATION: MECHANICAL PLAN SHOWS THE
 KITCHEN EXHAUST FAN AT A MINIMUM HEIGHT OF 40" ABOVE
 THE ROOD SURFACE. ARCHITECTURAL PLANS SHOW THE FAN
 SURROUNDED ON 3 SIDES BY A 42" HIGH PARAPET. IF FAN IS
 TO BE LOCATED IN CLOSE PROXIMITY TO PARAPET (MIN. 2'
 SEPARATION) THE DISCHARGE OPENING OF THE FAN MUST BE
 HIGHER THAN THE PARAPET IN ACCORDANCE WITH FBC-M
 506.5.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-01-11 Cont ID  
Sent By rregueir Date 2009-01-11 Time 09:46 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 08:38 Sent To  
Notes
2009-01-11 08:44:30REVIEW #: 3RD **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE ONLY OUTSTANDING COMMENT LEFT FROM PREVIOUS REVIEW
 IS COMMENT #2. ALL OTHER COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED. PLEASE SEE THE HISTORY OF COMMENT #2
 PROVIDED BELOW, FOLLOWED BY A DESCRIPTION OF WHICH
 ASPECTS OF THIS COMMENT REMAIN UNADDRESSED.
  
 **FROM FIRST REVIEW**
 2. PG M-1 AND M-2: PLAN CALLS FOR EXTENSION OF KITCHEN
 EXHAUST DUCT FROM EXISTING ROOF TO NEW ROOF. THERE IS
 NO DETAIL FOR THE INSTALLATION OF (ASSUMED TO BE)
 GREASE EXHAUST DUCT AND EXHAUST FAN ON NEW ROOF SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 - FBCM 301.13 FOR WIND RESISTANCE.
 - FBCM 506.3.12.1, 506.3.12.3 AND ALL PORTIONS OF 506.5
 FOR CLEARANCES, LOCATION AND HEIGHT ABOVE ROOF.
 - FBCM 401.5 FOR INTAKE AND EXHAUST LOCATIONS.
 - FBCM 304.10 IF LESS THAN 10 FEET FROM THE ROOF EDGE.
 - FBCM 306.5 FOR SERVICE ACCESS.
 - FBCM 301.4.4 EQUIPMENT, APPLIANCES AND DEVICES SHALL
 NOT BE REUSED UNLESS SUCH ELEMENTS HAVE BEEN
 RECONDITIONED, TESTED AND PLACED IN GOOD AND PROPER
 WORKING CONDITION AND APPROVED.
 NOTE: ONCE THE EXISTING KITCHEN EXHAUST SYSTEM IS
 MODIFIED IN ANY WAY, THE SYSTEM WILL NEED TO BE TESTED,
 BALANCED AND RE-CERTIFIED TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENTS OF THE KITCHEN HOOD LISTING
 AND/OR THE REQUIREMENTS OF FBCM 506 AND 507.
  
 **FROM 2ND REVIEW**
 2. NOT FULLY ADDRESSED. NO INFORMATION IS SHOWN ON
 PLANS REGARDING CODE REQUIREMENTS FOR THE KITCHEN HOOD
 EXHAUST FAN SUCH AS WIND RESISTANCE, CLEARANCES,
 HEIGHTS, SERVICE ACCESS, GUARDS, ETC. SEE PREVIOUS
 COMMENT #2 FOR ALL CODE REQUIREMENTS WHICH NEED TO BE
 ADDRESSED. PROVIDE SUFFICIENT DETAIL TO DEMONSTRATE
 COMPLIANCE WITH ALL OF THESE REQUIREMENTS. ONE OR MORE
 ELEVATION VIEWS MAY BE HELPFUL.
  
 **3RD REVIEW** PLEASE ADDREESS EACH OF THESE SPECIFIC
 CODE REQUIREMENTS AS LISTED BELOW:
 A. FBCM 301.13 FOR WIND RESISTANCE. AN INSTALLATION
 DETAIL HAS BEEN ADDED TO PAGE M2 FOR THE ROOFTOP
 EXHAUST FAN. HOWEVER, THE EF SCHEDULE ON M1 LISTS A FAN
 WITH A MIAMI-DADE NOA TO DEMONSTRATE COMPLIANCE WITH
 THIS SECTION. THIS INSTALLATION OF THE EXHAUST FAN AND
 ASSOCIATED ROOF CURB SHALL BE IN ACCORDANCE WITH THE
 REFERENCED NOA. PLEASE PROVIDE 3 COPIES OF THE PRODUCT
 APPROVAL FOR THIS SYSTEM APPROVED IN WRITING BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH FBCB 106.3.3.
  
 B. FBCM 506.3.12.1 TERMINATION ABOVE THE ROOF. EXHAUST
 OUTLETS THAT TERMINATE ABOVE THE ROOF SHALL HAVE THE
 DISCHARGE OPENING LOCATED NOT LESS THAN 40 INCHES ABOVE
 THE ROOF SURFACE.
  
 C. FBCM 506.3.12.3 TERMINATION LOCATION. EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET
 HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS, ADJACENT PROPERTY LINES AND AIR INTAKE
 OPENINGS INTO ANY BUILDING. PLEASE SHOW DISTANCES FROM
 PARTS OF THE SAME OR CONTIGUOUS BUILDINGS. WILL THERE
 BE PARAPETS AROUND THIS FAN? IF SO, WHAT IS THE HEIGHT
 OF THE PARAPETS AROUND THE FAN? THE MINIMUM HORIZONTAL
 DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND
 PARAPET-TYPE BUILDING STRUCTURES MAY BE 2 FEET PROVIDED
 THAT SUCH STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE
 FAN DISCHARGE OPENING IN ACCORDANCE WITH FBCM 506.5.5.
 SEE ALSO FBCM 401.5 OPENING LOCATION. OUTDOOR AIR
 EXHAUST OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET
 FROM LOT LINES OR BUILDINGS ON THE SAME LOT. PLEASE
 SHOW THE MINIMUM DISTANCE FROM ADJACENT PROPERTY LINES.
  
 D. FBCM 506.5.3 EXHAUST FAN MOUNTING.AN UPBLAST FAN
 SHALL BE HINGED AND SUPPLIED WITH A FLEXIBLE
 WEATHERPROOF ELECTRICAL CABLE TO PERMIT INSPECTION AND
 CLEANING. THE DUCTWORK SHALL EXTEND A MINIMUM OF 18
 INCHES ABOVE THE ROOF SURFACE. NONE OF THIS INFORMATION
 IS SHOWN ON THE INSTALLATION DETAIL ON PLANS. THIS
 INFORMATION MIGHT BE PROVIDED WITH THE NOA REFERENCED
 IN COMMENT A ABOVE. PLEASE PROVIDE THE PRODUCT APPROVAL
 AND REMOVE ANY INSTALLATION DETAIL WHICH MAY BE IN
 CONFLICT WITH THE PRODUCT APPROVAL'S INSTALLTION
 INSTRUCTIONS.
  
 E. FBCM 304.10 GUARDS. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES ABOVE
 THE FLOOR, ROOF OR GRADE BELOW. PAGE A-8 SHOWS A DETAIL
 FOR A "ROOF MAINTENANCE ANCHOR." IS THIS INTENDED TO BE
 AN ALTERNATE TO THE GUARD REQUIREMENTS? IF SO, THIS
 MUST BE SUBMITTED TO THE BUILDING OFFICIAL IN WRITING
 AS A REQUEST FOR ALTERNATE MATERIALS OR METHODS UNDER
 THE PROVISIONS OF FBCB 104.11.
  
 F. FBCM 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH ACCESS
 SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF
 ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH. PLEASE
 SHOW ON PLANS HOW THIS APPLIANCE IS TO BE ACCESSED FOR
 SERVICE, CLEANING, MAINTENANCE OR REPLACEMENT.
  
 G. FBCM 301.4.4 EQUIPMENT, APPLIANCES AND DEVICES SHALL
 NOT BE REUSED UNLESS SUCH ELEMENTS HAVE BEEN
 RECONDITIONED, TESTED AND PLACED IN GOOD AND PROPER
 WORKING CONDITION AND APPROVED.
 NOTE: ONCE THE EXISTING KITCHEN EXHAUST SYSTEM IS
 MODIFIED IN ANY WAY, THE SYSTEM WILL NEED TO BE TESTED,
 BALANCED AND RE-CERTIFIED TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENTS OF THE KITCHEN HOOD LISTING
 AND/OR THE REQUIREMENTS OF FBCM 506 AND 507. PLEASE
 PLACE A NOTE ON PLANS REQUIRING A TEST AND BALANCE OF
 THE KITCHEN HOOD SYSTEM WITH A T & B REPORT TO BE
 PROVIDED TO THE BUILDING OFFICIAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By rregueir Date 2008-09-10 Time 16:27 Rev Time 0.00
Received By rregueir Date 2008-09-10 Time 10:45 Sent To  
Notes
2008-09-10 16:27:24REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. NOT FULLY ADDRESSED. NO INFORMATION IS SHOWN ON
 PLANS REGARDING CODE REQUIREMENTS FOR THE KITCHEN HOOD
 EXHAUST FAN SUCH AS WIND RESISTANCE, CLEARANCES,
 HEIGHTS, SERVICE ACCESS, GUARDS, ETC. SEE PREVIOUS
 COMMENT #2 FOR ALL CODE REQUIREMENTS WHICH NEED TO BE
 ADDRESSED. PROVIDE SUFFICIENT DETAIL TO DEMONSTRATE
 COMPLIANCE WITH ALL OF THESE REQUIREMENTS. ONE OR MORE
 ELEVATION VIEWS MAY BE HELPFUL.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. THE WRITTEN RESPONSE FROM SEC STATES THAT A
 SPECIFICATION SHEET FOR THE EXHAUST FAN IS ATTACHED. NO
 SUCH DOCUMENTATION COULD BE FOUND WITH THIS SUBMISSION.
 PLEASE ENSURE ALL REFERENCED DOCUMENTATION IS PROVIDED
 WHEN THIS INFORMATION IS BEING USED TO DEMONSTRATE CODE
 COMPLIANCE.
  
 7. OK
  
 8. THE WRITTEN RESPONSE FROM SEC STATES THAT A
 SPECIFICATION SHEET FOR THE REMOTE CONDENSING UNIT IS
 ATTACHED. NO SUCH DOCUMENTATION COULD BE FOUND WITH
 THIS SUBMISSION. PLEASE ENSURE ALL REFERENCED
 DOCUMENTATION IS PROVIDED WHEN THIS INFORMATION IS
 BEING USED TO DEMONSTRATE CODE COMPLIANCE.
  
  
 9. OK. PLEASE FOLLOW-UP WITH SUPPORTING DOCUMENTATIONS.
  
 10. THE WRITTEN RESPONSE FROM SEC STATES THAT ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS ARE
 ATTACHED. NO SUCH DOCUMENTATION COULD BE FOUND WITH
 THIS SUBMISSION. PLEASE ENSURE ALL REFERENCED
 DOCUMENTATION IS PROVIDED WHEN THIS INFORMATION IS USED
 TO DEMONSTRATE CODE COMPLIANCE. CODE COMPLIANCE FOR ALL
 BUILDINGS SHALL BE CERTIFIED BY USE OF APPROVED FORMS
 FOR THE COMPLIANCE METHOD CHOSEN IN ACCORDANCE WITH
 FBCB 13-103.0. ADDITIONS TO EXISTING COMMERCIAL
 BUILDINGS ARE CONSIDERED NEW BUILDING CONSTRUCTION AND
 SHALL COMPLY WITH FBCB SUBCHAPTER 13-4 OF THIS CODE AS
 ALLOWED IN SECTION 101.1.1 IN ACCORDANCE WITH FBCB
 13-101.1.2. COOLING LOAD CALCULATIONS SHALL BE APPENDED
 TO THE ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH
 FBCB 13-407.1.ABC.1.
  
 NEW: DURING THE PREVIOUS REVIEW, I WAS NOT AWARE OF THE
 FACT THAT THE MINI-SPLIT UNITS WERE IN A FIRE-RATED
 STAIR ENCLOSURE. PLEASE SHOW HOW THESE A/C UNITS CAN BE
 INSTALLED IN AN EXIT ENCLOSURE AND BE IN COMPLIANCE
 WITH THE PENETRATION REQUIREMENTS OF FBCB 1019.1.2.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION IN ACCORDANCE WITH THIS SECTION. IT
 WOULD APPEAR THE PENETRATIONS FOR ELECTRICAL,
 REFRIGERANT AND CONDENSATE LINES WOULD BE NECESSARY FOR
 THESE UNITS. ALL OF THESE PENETRATIONS WOULD BE
 PROHIBITED PER 1019.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By rregueir Date 2008-08-04 Time 14:58 Rev Time 0.00
Received By rregueir Date 2008-08-04 Time 08:14 Sent To  
Notes
2008-08-04 14:58:18REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A-3: PROPOSED THIRD FLOOR/ROOFTOP DECK PLAN CALLS
 FOR ONE OR POSSIBLY MORE MECHANICAL VENTILATION SHAFTS
 WITH A NOTE TO ?SEE MECHANICAL PLANS.? NO INFORMATION
 COULD BE FOUND ON MECHANICAL PLANS REGARDING SIZE,
 ROUTING OR DESIGN OF THE DUCTS IN THESE SHAFTS. PROVIDE
 MISSING INFORMATION AS TO THE FUNCTION AND DESIGN OF
 THESE SHAFTS IN ACCORDANCE WITH FBCM 501.1 AND FBCB
 106.1.1. THE ROOFTOP UNITS BEING SERVED BY THESE SHAFTS
 ARE DESIGNED FOR OUTDOOR INSTALLATION AND FREE AIRFLOW.
 PROVIDE DATA FROM THE MANUFACTURER SHOWING THAT THESE
 MODIFICATIONS (ADDITION OF DUCTWORK TO THE DISCHARGE
 SIDE OF THE CONDENSING FANS FOR THE PURPOSE OF
 AIR-COOLING THE CONDENSING COILS) TO THE DESIGN AND
 LISTING OF THESE APPLIANCES WILL NOT ADVERSELY AFFECT
 THE FUNCTIONALITY OR THE EFFICIENCY OF THESE APPLIANCES
 IN ACCORDANCE WITH FBCM 304.1 AND FBCM 301.2.
  
 2. PG M-1 AND M-2: PLAN CALLS FOR EXTENSION OF KITCHEN
 EXHAUST DUCT FROM EXISTING ROOF TO NEW ROOF. THERE IS
 NO DETAIL FOR THE INSTALLATION OF (ASSUMED TO BE)
 GREASE EXHAUST DUCT AND EXHAUST FAN ON NEW ROOF SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 - FBCM 301.13 FOR WIND RESISTANCE.
 - FBCM 506.3.12.1, 506.3.12.3 AND ALL PORTIONS OF 506.5
 FOR CLEARANCES, LOCATION AND HEIGHT ABOVE ROOF.
 - FBCM 401.5 FOR INTAKE AND EXHAUST LOCATIONS.
 - FBCM 304.10 IF LESS THAN 10 FEET FROM THE ROOF EDGE.
 - FBCM 306.5 FOR SERVICE ACCESS.
 - FBCM 301.4.4 EQUIPMENT, APPLIANCES AND DEVICES SHALL
 NOT BE REUSED UNLESS SUCH ELEMENTS HAVE BEEN
 RECONDITIONED, TESTED AND PLACED IN GOOD AND PROPER
 WORKING CONDITION AND APPROVED.
 NOTE: ONCE THE EXISTING KITCHEN EXHAUST SYSTEM IS
 MODIFIED IN ANY WAY, THE SYSTEM WILL NEED TO BE TESTED,
 BALANCED AND RE-CERTIFIED TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENTS OF THE KITCHEN HOOD LISTING
 AND/OR THE REQUIREMENTS OF FBCM 506 AND 507.
  
 3. PG M-1: PLAN INDICATES OUTSIDE AIR CALCULATIONS ARE
 BASED ON ASHRAE 62-1999. THIS IS NOT THE CURRENT
 STANDARD ADOPTED UNDER THE 2004 FBCM. SHOW OUTSIDE AIR
 CALCULATIONS FOR THE INDOOR CONDITIONED SPACE TO BE
 CALCULATED BASED ON FBCM TABLE 403.3 OR ASHRAE
 62.1-2004. PROVIDE OCCUPANCY CLASSIFICATION, OCCUPANT
 LOAD, OUTSIDE AIR REQUIRED AND OUTSIDE AIR PROVIDED IN
 ACCORDANCE WITH THE METHOD TO BE DECLARED ON THE PLANS.
  
  
 4. PG M-1: THE O.A. INTAKE FOR THE NEW AHU #1 SHALL BE
 EQUIPPED WITH A MOTORIZED DAMPER THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEM OR SPACE SERVED IS
 NOT IN USE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3 FOR
 SHUTOFF DAMPER CONTROLS.
  
 5. PG M-1: AHU-1 APPEARS TO BE LOCATED ABOVE A GYPSUM
 BOARD CEILING. APPLIANCES SHALL BE ACCESSIBLE TO ALLOW
 INSPECTIONS, SERVICE, REPAIR OR REPLACEMENT WITHOUT
 REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1. SHOW HOW THIS APPLIANCE IS
 TO BE ACCESSED FOR SERVICE OR REPLACEMENT IN ACCORDANCE
 WITH THIS SECTION.
  
 6. PG M-1: BATHROOM EXHAUST DUCTS ARE SHOWN ON PLANS TO
 BE 3? X 10. THE FAN FOR THIS SYSTEM IS CALLING FOR 300
 CFM OF EXHAUST. IS THIS DUCT PROPERLY SIZED TO MOVE 300
 CFM OF EXHAUST? PLEASE VERIFY, VIA DUCT SIZING
 CALCULATOR OR SOME STANDARD ENGINEERING PRACTICE. DUCT
 SYSTEMS SHALL BE DESIGNED TO PROVIDE THE REQUIRED
 VOLUME OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 7. PG M-2: THE EXISTING ROOFTOP PACKAGE UNITS HAVE
 OUTSIDE AIR INTAKES TO PROVIDE VENTILATION FOR THE
 SPACES SERVED BY THESE SYSTEMS. WITH THE ADDITION OF A
 NEW FLOOR ABOVE THESE UNITS, THE INTAKES ARE NO LONGER
 LOCATED OUTSIDE THE BUILDING. THEREFORE, THE OUTSIDE
 AIR INTAKES SHALL BE DUCTED TO THE EXTERIOR OF THE
 BUILDING. ANY EXHAUST FANS OR OUTLETS IN THIS AREA
 SHALL ALSO DISCHARGE DIRECTLY TO THE EXTERIOR OF THE
 BUILDING. SHOW COMPLIANCE WITH ALL PARTS OF FBCM 401.5
 FOR INTAKE AND EXHAUST LOCATIONS.
  
 8. PG M-2: PROVIDE MANUFACTURER?S DATA FOR THE PROPOSED
 NEW CONDENSING UNITS FOR THE SPLIT SYSTEMS SHOWING THE
 INSTALLATION IN A LOCATION OTHER THAN OUTDOORS TO BE IN
 ACCORDANCE WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBCM 304.1.
  
  
 9. PG M-2: PROVIDE DETAILED INSTALLATION INSTRUCTIONS
 FOR THE RELOCATED RTU IN ACCORDANCE WITH FBCM 304.1.
 ALSO, EQUIPMENT AND APPLIANCES SHALL NOT BE REUSED
 UNLESS SUCH ELEMENTS HAVE BEEN RECONDITIONED, TESTED
 AND PLACED IN GOOD AND PROPER WORKING CONDITION AND
 APPROVED BY THE BUILDING OFFICIAL IN ACCORDANCE WITH
 FBCM 301.4.4.
  
 10. PROVIDE AN ENERGY CODE COMPLIANCE FORM WITH
 APPENDED COOLING LOAD CALCULATIONS FOR REVIEW. CODE
 COMPLIANCE FOR ALL BUILDINGS SHALL BE CERTIFIED BY USE
 OF APPROVED FORMS FOR THE COMPLIANCE METHOD CHOSEN THAT
 ARE SPECIFIC TO THE CLIMATE ZONE IN WHICH THE BUILDING
 WILL BE LOCATED IN ACCORDANCE WITH FBCB 13-103.0.
 ADDITIONS TO EXISTING COMMERCIAL BUILDINGS ARE
 CONSIDERED NEW BUILDING CONSTRUCTION AND SHALL COMPLY
 WITH FBCB SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED IN
 SECTION 101.1.1 IN ACCORDANCE WITH FBCB 13-101.1.2.
 COOLING LOAD CALCULATIONS SHALL BE APPENDED TO THE
 ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCB
 13-407.1.ABC.1.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DETAILED DESCRIPTION OF HOW EACH COMMENT WAS ADDRESSED
 AS WELL AS WHERE THE RELEVANT INFORMATION CAN BE FOUND.
 ALSO, PLEASE PROVIDE ONE SET OF OLD/VOIDED PLANS FOR
 REFERENCE. THESE STEPS WILL AID IN PROVIDING A TIMELY
 REVIEW OF THE RESUBMISSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 13:49 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 13:49 Sent To  
Notes
2009-01-22 11:44:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE COMMENT RESPONSE DID NOT
 INDICATE THE TOTAL SQUARE FOOTAGE BEING DRAINED BY THE
 GUTTER AND DOWNSPOUT. PLEASE INDICATE THE SQUARE
 FOOTAGE, THE SIZE OF THE GUTTER AND THE SIZE OF THE
 DOWNSPOUT. TABLES 1106.3 & 1106.6.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RESPONSE ONLY ADDRESSED
 THE CONTRIBUTION ADDED TO THE ROOF AREAS OF THE
 BUILDINGS ON THE EAST & WEST SIDES OF THE BUILDING. THE
 INFORMATION REQUIRED IS FOR THE EXISTING ROOF OF
 ROXY'S. INDICATE THE TOTAL SQUARE FOOTAGE BEING
 DRAINED. SUBMIT CALCULATIONS FOR THE AREA OF THE ROOF
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS IN THE
 CALCULATIONS. INDICATE THE SIZE OF THE DOWNSPOUTS, THE
 SIZE OF THE COLLECTOR HEAD FOR THE DOWNSPOUTS AND THE
 SIZE OF THE OVERFLOW SCUPPERS. SUBMIT A DETAIL FOR THE
 OVERFLOW SCUPPERS SHOWING HEIGHT, WIDTH AND DISTANCE
 OFF THE ROOF TO THE FLOW LINE OF THE SCUPPER. SUBMIT A
 DETAIL FOR THE OPENING FOR THE DOWNSPOUTS INDICATING
 THE HEIGH & WIDTH. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES AS WELL AS SECTION 1503.4.3.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. OK
 ___FOR URINAL:
 A. OK
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED.
 C. OK
 ___FOR LAVS:
 A. OK
 ___FOR TOILET ROOM:
 A. 1OK
  
 7. OK
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
 ****RESPONSE NOTED, BUT THE VOIDED SHEETS HAVE NOT BEEN
 SUBMITTED FOR COMPARISON. PLEASE SUBMIT ONE SET OF
 PREVIOUSLY REVIEWED SHEETS.
 ******RESPONSE NOTED, BUT THE PIPE SIZE IS STILL SHOWN
 AS 4" DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER IN THE
 COMBINATION WASTE & VENT SYSTEM.
  
 9. OK
  
 10. OK (GAS DELETED)
  
 ***********NEW COMMENTS***********
  
 1B. SHT A-2 SHOW TABLES AND CHAIRS ON 2ND FLOOR AS 15
 NET IS INDICATED FOR MAXIMUM FLOOR AREA ALLOWANCES PER
 OCCUPANT AND 2 W/C'S HAVE BEEN DELETED. SECTION 106.1.1
 AND TABLES 1004.1.2 & 403.1.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2B. SHT P-3 MAXIMUM 20 FIXTURE UNITS ALLOWED ON 4"
 COMBINATION WASTE & VENT SYSTEM. INDICATE PIPE SIZE AND
 TRAP SIZE FOR FLOOR SINK AT 3 COMPARTMENT SINK. IF 3"
 THEN 5" IS REQUIRED DOWNSTREAM OF FLOOR SINK AT BEER
 COOLER/FLOOR DRAIN. TABLE 912.3. PLEASE SHOW DRAINAGE
 FIXTURE UNITS AS THEY ACCUMULATE IN THE SYSTEM ON THE
 SANITARY RISER DIAGRAM. TABLES 710.1(1) & 710.1(2).
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED AS 1 COPY
 OF VOIDED SHEETS HAS NOT BEEN SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-05 Cont ID  
Sent By kstevens Date 2008-09-05 Time 17:21 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 12:01 Sent To  
Notes
2008-09-05 17:44:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A-3 SHOWS A WATER TROUGH & WATER FEATURE. PLEASE
 INDICATE IF THERE WILL BE A WATER SUPPLY, DRAIN AND
 OVERFLOW FOR THE WATER FEATURE. INDICATE BACKFLOW
 METHOD IF CONNECTING TO THE POTABLE WATER SUPPLY.
 SECTION 608. SHOW THE TERMINATION OF THE DRAIN AND
 OVERFLOWS FOR THE FOUNTAIN. ARTICLE III SECTIONS 90-124
 & 90-125.
 ****RESPONSE NOTED, BUT THE WATER FEATURES INDICATED AS
 3 STEP WATERFALL FEATURE INTO WATER TROUGH 30" A.F.F.
 BELOW W/RECIRC PUMP (TYPICAL) STILL INDICATED ON SHT
 A-3. COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
 ****RESPONSE NOTED, BUT NO RESPONSE FROM THE ARCHITECT.
 COMMENT NOT ADDRESSED.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 ___FOR URINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 ___FOR TOILET ROOM:
 A. 11-4.22.3 TURNING AREA IN TOILET ROOM, NOT IN STALL
  
 7. OK
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
 ****RESPONSE NOTED, BUT THE VOIDED SHEETS HAVE NOT BEEN
 SUBMITTED FOR COMPARISON. PLEASE SUBMIT ONE SET OF
 PREVIOUSLY REVIEWED SHEETS.
  
 9. OK
  
 10. OK (GAS DELETED)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED AS 1 COPY
 OF VOIDED SHEETS HAS NOT BEEN SUBMITTED FOR COMPARISON.
  
 ***********NEW COMMENTS***********
  
 1B. SHT A-2 SHOW TABLES AND CHAIRS ON 2ND FLOOR AS 15
 NET IS INDICATED FOR MAXIMUM FLOOR AREA ALLOWANCES PER
 OCCUPANT AND 2 W/C'S HAVE BEEN DELETED. SECTION 106.1.1
 AND TABLES 1004.1.2 & 403.1.
  
 2B. SHT P-3 MAXIMUM 20 FIXTURE UNITS ALLOWED ON 4"
 COMBINATION WASTE & VENT SYSTEM. INDICATE PIPE SIZE AND
 TRAP SIZE FOR FLOOR SINK AT 3 COMPARTMENT SINK. IF 3"
 THEN 5" IS REQUIRED DOWNSTREAM OF FLOOR SINK AT BEER
 COOLER/FLOOR DRAIN. TABLE 912.3. PLEASE SHOW DRAINAGE
 FIXTURE UNITS AS THEY ACCUMULATE IN THE SYSTEM ON THE
 SANITARY RISER DIAGRAM. TABLES 710.1(1) & 710.1(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-08-01 Cont ID  
Sent By kstevens Date 2008-08-01 Time 08:42 Rev Time 0.00
Received By kstevens Date 2008-07-31 Time 15:56 Sent To  
Notes
2008-08-01 16:36:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA STATUTES
  
 1. SHT A-2 INDICATES A REMODEL OF THE WOMEN'S TOILET
 ROOM. PLEASE SUBMIT AN EXISTING FLOOR PLAN FOR THE
 TOILET ROOM TO DETERMINE THE EXTENT OF THE REMODEL.
  
 2. SHT A-3 SHOWS A WATER TROUGH & WATER FEATURE. PLEASE
 INDICATE IF THERE WILL BE A WATER SUPPLY, DRAIN AND
 OVERFLOW FOR THE WATER FEATURE. INDICATE BACKFLOW
 METHOD IF CONNECTING TO THE POTABLE WATER SUPPLY.
 SECTION 608. SHOW THE TERMINATION OF THE DRAIN AND
 OVERFLOWS FOR THE FOUNTAIN. ARTICLE III SECTIONS 90-124
 & 90-125.
  
 3. SHT A-3 SHOWS PLANTERS. WILL THERE BE IRRIGATION
 AND/OR DRAINAGE TO/FROM THE PLANTERS. PLEASE CLAIRFY.
 SECTIONS 106.1.2, 1101 & FS 373.62.
  
 4. SHT A-5 SUBMIT CALCULATIONS FOR THE VERTICAL
 CONTRIBUTION OF THE STORM WATER ON TO ADJACENT EXISTING
 NEIGHBORING BUILDINGS TO THE EAST & WEST SIDE OF THE
 PROPOSED WORK. PLEASE VERIFY ON THE PLANS OR IN A
 SIGNED, SEALED LETTER THAT THE ADJACENT ROOFS WILL BE
 ABLE TO ACCEPT AND DRAIN THE ADDED VERTICAL
 CONTRIBUTION WITH THE EXISTING SYSTEMS PER SECTIONS
 1106 & 1107.
  
 5. SHT A-8 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS SHOWING THE SQUARE FOOTAGE BEING
 DRAINED FOR EACH ROOF DRAIN. (SEE ADDED VERTICAL
 CONTRIBUTION ABOVE THE EXISTING ROOF. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUB SECTIONS AND
 TABLES. SHOW THE LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS.
  
 6. SUBMIT DETAILS FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 7. SHT LS-1 PLUMBING FIXTURE REQUIREMENTS. WATER
 CLOSETS REQUIRED FOR MEN & WOMEN IS 3 EACH. (340/2
 EQUALS 170 EACH MEN/WOMEN). REQUIRED IS INDICATED AS 2.
 1 PER 75 REQUIRES 3 WATER CLOSETS. TABLE 403.1. PLEASE
 CORRECT AMOUNT REQUIRED.
  
 8. SHT P-3 SANITARY RISER DIAGRAM. SANITARY COMBINATION
 WASTE & VENT SYSTEM DOWNSTREAM OF WOMENS TOILET
 REQUIRES 4" DOWNSTREAM OF CLEANOUT & MINIMUM 5" IS
 REQUIRED DOWNSTREAM OF THE FLOOR DRAIN/BEER COOLER.
 TABLE 912.3. -- MINIMUM 5" PIPE IS REQUIRED DOWNSTREAM
 OF THE COMBINATION WASTE & VENT INDICATED. SECTION
 704.2.
  
 9. SHT P-3 WATER RISER DIAGRAM. SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY PIPES TO THE HOSE BIBBS. SECTION
 606.2(2). -- SHOW ALL PIPE SIZES AND SHOW THE POINT OF
 CONNECTION ON THE RISER DIAGRAM. SECTION 604.
  
 10. A SEPARATE GAS PERMIT IS REQUIRED. (SEE SHT A-5 KEY
 NOTE 6). SUBMIT THE FOLLOWING INFORMATION FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-09 Cont ID  
Sent By mflis Date 2008-12-09 Time 09:27 Rev Time 0.00
Received By mflis Date 2008-12-09 Time 09:27 Sent To  
Notes
2008-12-09 09:36:25ZONING REVIEW: PASSED FOR MAJOR WORKING DRAWINGS REVIEW
 ONLY
  
 ** :LANDSCAPE PERMITS SHALL BE SUBMITTED SEPARATELY TO
 INCLUDE ANY "OWNER-PROVIDED" ITEMS AS INDICATED ON THIS
 SET
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By mflis Date 2008-09-11 Time 10:26 Rev Time 0.00
Received By mflis Date 2008-09-11 Time 10:25 Sent To  
Notes
2008-09-11 10:28:44ZONING REVIEW: FAILED
  
 ** REVISED PERMIT INDICATED THAT PLANTERS WILL BE
 PROVIDED BY OWNER; PLEASE CONFIRM THIS IS CORRECT AND
 PROVIDE ANY DETAILS FOR INSTALLATION OF MATERIALS ON
 DECK (WILL THESE BE ATTACHED TO THE BUILDING?)
 ** PLANT MATERIALS SHOULD BE INDICATED IN LANDSCAPE
 PLAN
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By mflis Date 2008-07-31 Time 08:20 Rev Time 0.00
Received By mflis Date 2008-07-31 Time 08:20 Sent To  
Notes
2008-07-31 08:35:20ZONING REVIEW: FAILED
  
 ZONING COMMENTS:
  
  
 1) AIR RIGHTS EASEMENT SHALL BE REQUIRED FOR AN PORTION
 OF BUILDING OR STRUCTURE WHICH INTRUDES INTO PUBLIC
 RIGHT-OF-WAY. (APPLICATION IN-PROGRESS WITH ENGINEERING
 SERVICES).
  
 2) LANDSCAPE PLANS SHALL BE REQUIRED FOR ALL PLANT
 MATERIAL TO BE INSTALLED ON ROOF LEVEL, INCLUDING
 DETAILS FOR PLANTER BOXES/BED.
  
 3) ARCHITECTURAL TREATMENT, SUCH AS SCORING OR REVEAL
 LINES, SHALL BE PROVIDED FOR THOSE PORTIONS OF EAST AND
 WEST ELEVATIONS WHICH ABUT ADJACENT PROPERTIES.
 ARCHITECTURAL TREATMENT SHALL BE UTILIZED TO BREAK UP
 BLANK WALLS.
  
 4) STORAGE AREAS ARE NOT DETAILED. PLESAE CONFIRM IF IT
 INTENDED THAT THESE WILL BE CONVERTED TO KITCHEN OR
 PREP AREAS.
  
  
 ARCHITECTURAL DESIGN COMMENTS FOR CONSIDERATION:
  
 4) RAILING AND BALUSTRADE AT TOP OF FRONT ELEVATION SEE
 HEAVY AND OVERLY DETAILED FOR ARCHITECTURE OF BUILDING.
 GIVEN BALCONY PORTION WILL HANG OVER STREET, ARCHITECT
 MAY WISH TO CONSIDER LIGHTER FEATURES WHICH DO NOT
 CONFLICT WITH EXISTING ARCHITECTURE OR PROPOSED
 ARCHITECTURE OF GAZEBO.
  
 5) GAZEBO ELEMENT SEEMS PROPORTIONATELY OUT OF SCALE
 WITH THE REST OF THE BUILDING. I CANNOT TELL WHAT THE
 EXTRA HEIGHT IS PROVIDING IN TERMS OF THE BAR AREA.
 PLEASE LOOK AT THE PROPORTIONS OF THE SPACE AND CONFIRM
 THE SCALE IS CORRECT.
  
 6) PLEASE CONFIRM ARCHITECTURE OF GAZEBO IS CORRECT.
 WITH VARYING HEIGHTS AND ARCHITECTURAL STYLES, THE
 ELEMENTS SEEM TO BE COMPETING WITH EACH OTHER (FLORIDA
 VERNACULAR, ITALIANATE, AND TRADITIONAL MAIN STREET).
  
  
 MATT FLIS - 822-1445
  
  
  
  
  
  