| Plan Review Stops For Permit 08070182 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-07-08 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-07-08 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2008-07-08 14:17:09 | 2004 FBC W/2007 REVISIONS | | | INSTALL ACCORDION SHUTTERS | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) THE ACCORDIONS ARE BEING INSTALLED ON A HIGH RISE | | | BUILDING WITH A MEAN ROOF HEIGHT OF MORE THAN 60 FEET. | | | SUBMIT SIGNED AND SEALED ENGINEERING FOR THE OPENING | | | PRESSURES. FBC 1609.1.1 | | | | | | 3) THE WALL PRESSURES SPECIFIED 0N THE INSTALLATION | | | SCHEDULE ARE INCORRECT. USE PRESSURES DETERMINED BY | | | ENGINEERED CALCULATIONS. FBC 1609.1.1 | | | | | | 4) THE FASTENER SPACINGS IN THE TABLES ARE FOR 3-1/2" | | | EDGE DISTANCE. THE ANCHOR SPACINGS ARE REQUIRED TO BE | | | REDUCED IF EDGE DISTANCE IS LESS. SEE SHEET 11 OF | | | DRAWINGS. NOTE: 2" EDGE DISTANCE IS NOT ALLOWED FOR ALL | | | POINTS SOLID SET ANCHORS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|