Plan Review Details - Permit 08070177
Plan Review Stops For Permit 08070177
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By jwitmer Date 2008-07-21 Time 13:32 Rev Time 3.33
Received By jwitmer Date 2008-07-21 Time 12:18 Sent To  
Notes
2008-07-21 14:41:56BUILDING PLAN REVIEW
 PERMIT: 08070177
 ADD: 717 S OLIVE AV
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
 STRUCTURAL DRAWINGS INDICATE THE 2001 FBC AND ASCE
 7-98, PLEASE CORRECT.
  
 2) PLANS FAIL TO INDICATE THE OCCUPANCY CLASSIFICATION
 OF THE DEISEL FUEL STORAGE TANK ROOM. PLEASE SEE 302.1.
 DEISEL FUEL IS CLASSIFIED AS A CLASS II COMBUSTBLE
 LIQUID WITH A FLASH POINT BETWEEN 100-140 TABLE
 307.7(1)FOR STORAGE OR FOR USED AS CLOSED SYSTEMS
 ONLY ALLOWS 120 GALLONS AND FOOTNOTE "D" ONLY ALLOWS
 100% INCREASE FOR FIRE SPRINKLERS. THIS AMOUNT OF FUEL
 WILL CREATE A H-3 OCCUPANCY.
 307.9 EXCEPTION# 5 WILL EXEMPT FROM A H OCCUPANCY BUT
 THE MORE RESTRICTIVE REQUIREMENTS OF NFPA 37 SECTION
 63.6.1 WILL STILL APPLY.
  
 3) PLEASE PROVIDE MANUFACTURERS SPECS ON THE FUEL
 STORAGE TANK, P-1 INDICATE THIS TANK TO BE A DOUBLE
 -WALLED SYSTEM. 415.7.2.3/ 415.7.2.5.
  
 4) PLEASE SEE THE MECHANICAL COMMENT NUMBER 4 IN
 REGARDS TO HOURLY RATING OF WALLS, FLOORS AND DOORS.
 NFPA37-02 SECTION 6.3.6.1
  
 .6.3.6 ROOMS HOUSING ONLY FUEL TANKS WITH AN AGGREGATE
 CAPACITY OF MORE THAN 5000 L (1320 GAL).
  
 6.3.6.1 ROOMS CONTAINING ONLY FUEL TANKS SHALL BE
 CONSTRUCTED OF WALLS, FLOOR, AND CEILING HAVING A FIRE
 RESISTANCE RATING OF NOT LESS THAN 3 HOURS WITH THE
 WALLS BONDED TO THE FLOOR.
  
 6.3.6.1.1 IF THE WALLS OF SUCH ROOMS EXTEND TO AND ARE
 BONDED TO THE UNDERSIDE OF A CONCRETE FLOOR OR ROOF
 ABOVE THAT HAS A FIRE RESISTANCE RATING OF NOT LESS
 THAN 3 HOURS, A SEPARATE CEILING SHALL NOT BE REQUIRED
 FOR THE ROOM.
  
 5) ET P-1 ALSO INDICATES THE EMRGENCY VENTS WITHIN THE
 ROOM, 415.7.2.7 TANK VENTS FOR CLASS II LIQUIDS SHALL
 TERMINATE TO THE OUTDOOR AIR IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 6) SHEET A3 INDICATES TWO NEW EXTERIOR WALL LOUVERS,
 PLEASE SUBMIT 2 COPIES OF FLORIDA PRODUCT APPROVALS AS
 REQUIRED BY RULE 9B-72.PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 09:01 Sent To  
Notes
2008-07-30 09:02:29** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE PROVIDE RUN TIMES FOR THE GENERATOR.
 PLEASE PROVIDE ALL LOADS FED FROM THIS UNIT OR WILL ALL
 WHICH IS ALREADY CONNECTED RUN?
 PLEASE LIST ANY HAZARDOUS LOCATIONS PER NEC 500.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-08-07 Cont ID  
Sent By mawillia Date 2008-08-07 Time 17:28 Rev Time 0.00
Received By mawillia Date 2008-08-07 Time 16:13 Sent To  
Notes
2008-08-07 17:27:57*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REQUIRED MEANS OF EGRESS AND REUIRED FIRE
 PROTECTION FEATURES ARE TO BE IN PLACE AND CONTINUOUSLY
 MAINTAINED.
  
 3.WHEN/IF FIRE PROTECTION SYSTEMS ARE TO BE SHUT
 DOWN, THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 4.PROVIDE PRECAUTIONARY MEASURES TO BE TAKEN TO
 PREVENT IGNITION OF FLAMMABLE VAPORS AND/OR LIQUIDS FOR
 LIFE SAFETY, FOR MINIMIZING PROPERTY LOSS, AND FOR
 REDUCING FIRE EXPOSURE TO ADJOINING FACILITIES FROM
 FIRE AND EXPLOSION.
  
 5.ON SHEET E-1 IN THE SHOP DRAWING NOTE, REFERENCE IS
 MADE TO THE CITY OF MIAMI BEACH.PLEASE BE ADVISED
 THAT THE CORRECT AHJ IS THE CITY OF WEST PALM BEACH.
  
 6.HOW WILL THE FUEL TANK BE REFILLED?
  
 7.PROVIDE SPEC/CUT SHEETS FOR THE PROPOSED FUEL
 TANK.
  
 8.SINCE THE WALLS ARE REQUIRED TO BE FIRE RATED, ANY
 WALL OPENING SHALL HAVE FIRE PROTECTION RATING IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80, STANDARD
 FOR FIRE DOORS AND WINDOWS.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-850-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-07 Cont ID  
Sent By mawillia Date 2008-08-07 Time 16:13 Rev Time 0.00
Received By mawillia Date 2008-07-09 Time 09:09 Sent To  
Notes
2008-07-09 09:11:49TO "COMM" BD#20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By rregueir Date 2008-07-21 Time 11:05 Rev Time 0.00
Received By rregueir Date 2008-07-18 Time 09:41 Sent To  
Notes
2008-07-21 11:05:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 NFPA 37-02 AND NFPA 30-00
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A-1: NOTE #3 UNDER SCOPE OF WORK CALLS FOR FUEL
 TANK SHOP DRAWINGS TO BE PROVIDED. NO SHOP DRAWINGS
 WERE INCLUDED IN THIS PLAN SUBMITTAL. PLEASE PROVIDE
 INFORMATION, INCLUDING SHOP DRAWINGS WHICH ARE APPROVED
 BY THE DESIGNER OF RECORD (SHOP DRAWING REVIEW).
  
 2. ABOVE-GROUND FUEL TANKS IN EXCESS OF 550 GALLONS
 SHALL BE SUBMITTED AND APPROVED BY PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT PRIOR T
 PERMIT ISSUANCE. PLANS SHALL BE APPROVED BY PALM BEACH
 COUNTY DERM AND THEN BE SUBMITTED TO THIS DEPARTMENT
 FOR PERMIT. FOR MORE INFORMATION PLEASE CONTACT PBC
 DERM AT HTTP://WWW.PBCGOV.COM/ERM/ OR 561-233-2400.
  
 3. PG P-1 GENERAL NOTE: DIESEL GENERATORS AND RELATED
 FUEL TANKS SHALL BE IN COMPLIANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL 2004; NFP 30-00 AND NFPA
 37-02 IN ACCORDANCE WITH FBCM 915.1. THE FLORIDA
 BUILDING CODE, FUEL GAS IS NOT APPLICABLE. PLEASE
 ADJUST NOTES ACCORDINGLY. ALSO, WHEN RESUBMITTING,
 PLEASE RESUBMIT PAGES P-1 AND M-1 AS PAGES M-1 AND M-2
 SINCE THERE WILL BE NO PLUMBING REVIEW OF THESE PLANS.
  
 4. PG A-1 CALLS FOR THE FUEL TANK ROOM TO BE 2-HOUR
 RATED. ROOMS CONTAINING ONLY FUEL TANKS SHALL BE
 CONSTRUCTED OF WALLS, FLOOR, AND CEILING HAVING A FIRE
 RESISTANCE RATING OF NOT LESS THAN 3 HOURS WITH THE
 WALLS BONDED TO THE FLOOR IN ACCORDANCE WITH NFPA 37-02
 SECTION 6.3.6.1. ALSO, ANY OPENING OF A TANK ROOM SHALL
 BE PROTECTED BY A SELF-CLOSING 3-HOUR FIRE-RATED DOOR
 OR DAMPER ASSEMBLY AS APPLICABLE IN ACCORDANCE WITH
 FFPA 37-02 SECTION 6.3.6.2. THIS INCLUDES THE FIRE
 DAMPERS PROTECTING DUCT PENETRATIONS OF THE 3-HOUR
 RATED WALLS.
  
 5. PROVIDE INFORMATION ON THE DOUBLE-WALL FUEL TANK
 SHOWING IT MEETS THE SPILL CONTAINMENT SYSTEM
 REQUIREMENTS OF NFPA 37-02 SECTION 6.3.6.3.
  
 6. VALVES SHALL BE PROVIDED TO CONTROL THE FLOW OF
 LIQUID FUEL IN NORMAL OPERATION AND TO SHUT OFF THE
 FLOW OF FUEL IN THE EVENT OF A PIPE BREAK IN ACCORDANCE
 WITH NFPA 37-02 SECTION 6.8.3. SEE SECTION A.6.8.3 FOR
 COMPLIANCE METHODS. VALVES SHALL BE IN COMPLIANCE WITH
 NFPA 30-00 SECTION 3.3.3.
  
 7. PG P-1: PLAN CALLS FOR VENT LINES TO COMPLY WITH
 NFPA 30 SECTION A.5.7.1.4. THIS SECTION IS RELATED TO
 EXTENSION OF EMERGENCY VENTS. THE VENT PIPE SHOWN ON
 PLANS APPEARS TO BE THE NORMAL VENT PIPE FOR THE TANK,
 NOT THE EMERGENCY VENT. NORMAL VENTS SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 30-00 SECTION 2.2.5.1 AND
 DESIGNED IN ACCORDANCE WITH CHAPTER 3. WILL THE
 EMERGENCY VENTS BE EXTENDED TO THE OUTDOORS AS WELL?
 PLEASE CLARIFY.
  
 8. PG P-1: PROVIDE INFORMATION ON PLANS FOR REQUIRED
 SPACING OF PIPE SUPPORTS FOR FUEL AND VENT PIPING IN
 ACCORDANCE WITH NFPA 30-00 CHAPTER 3.
  
 9. PG M-1: PLAN SHOWS AN 18X10 INTAKE/MAKEUP AIR DUCT
 FOR THE EXHAUST FAN. THE GRILL IN THE TANK ROOM IS
 SHOWN AS 10X10. IT IS UNCLEAR WHY AN 18X10 DUCT WOULD
 ONLY HAVE A 10X10 GRILL. PLEASE CLARIFY, SHOWING THIS
 SYSTEM TO BE DESIGNED TO PROVIDE THE REQUIRED AIRFLOW
 IN ACCORDANCE WITH FBCM 603.1.
  
 10. PG M-1: PLAN CALLS FOR TWO NEW WALL LOUVERS TO BE
 INSTALLED. EXTERIOR WALL LOUVERS ARE DEFINED AS PANEL
 WALLS BY FAC RULE 9B-72. AS SUCH, PRODUCT APPROVAL IS
 REQUIRED. PROVIDE PRODUCT APPROVAL DOCUMENTATION
 SHOWING COMPLIANCE WITH FBCB 1609. ALSO, PRODUCT
 APPROVALS SHALL BE APPROVED IN WRITING (SHOP DRAWING
 REVIEW) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO
 THIS JURISDICTION IN ACCORDANCE WITH FBCB 106.3.3.
 PRODUCT APPROVALS WILL BE REVIEWED BY THE BUILDING PLAN
 REVIEWER.
  
 11. PG M-1: RELOCATED HPU IS SHOWN ON PLANS TO BE
 ADJACENT TO A NEW CBS WALL. PLEASE VERIFY AND SHOW ON
 PLANS THAT THIS APPLIANCE WILL BE ACCESSIBLE FOR
 SERVICE IN ACCORDANCE WITH FBCM 306.1.
  
 12. THIS PROPOSED WORK IS SUBMITTED AS AN ALTERATION TO
 AN EXISTING BUILDING. THIS BUILDING IS CURRENTLY UNDER
 CONSTRUCTION AND HAS NOT BEEN GRANTED A CERTIFICATE OF
 OCCUPANCY (C.O.). THIS WORK, ONCE PERMITTED MAY NOT
 COMMENCE PRIOR TO ISSUANCE OF THE C.O. BY THE BUILDING
 OFFICIAL AS THIS BUILDING CAN NOT BE CLASSIFIED AS
 ?EXISTING? UNTIL THAT TIME. ANY WORK RELATED TO THIS
 SCOPE WHICH IS STARTED PRIOR TO C.O. WILL NEED TO BE
 INCORPORATED INTO THE BASE BUILDING PLANS UNDER PERMIT
 #04120353. THIS WORK WILL THEN NEED TO BE COMPLETED
 PRIOR TO ISSUANCE OF THE C.O. FOR THE BUILDING. THIS
 WOULD ALSO CAUSE THE PROPOSED WORK TO BE REVIEWED UNDER
 THE 2001 FBC RATHER THAN THE 2004 FBC.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-23 Cont ID  
Sent By mflis Date 2008-07-23 Time 09:33 Rev Time 0.00
Received By mflis Date 2008-07-23 Time 09:33 Sent To  
Notes
***NONE***