 |
Plan Review Details - Permit 08070147
| Plan Review Stops For Permit 08070147 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-07-22 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-07-22 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2008-07-22 14:22:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS481. | | | | | | 2.PROVIDE A STRUCTURAL DETAIL FOR THE SLAB.PREFAB | | | SLABS REQUIRE ENGINEERING TO SHOW HOW IT WILL RESIST | | | WIND AND GRAVITY LOADS. | | | | | | 3.DECLARE GOVERNING CODE INCLUDING 2007 | | | REVISIONS/SUPPLEMENTS. | | | | | | 4.DECLARE WIND DESIGN CRITERIA (WIND SPEED AND | | | EXPOSURE), FBC R 301. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-08 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-08 |
Time |
11:33 |
Sent To |
P |
|
| Notes |
| 2008-07-08 12:01:27 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | PROVIDE THE FOLLOWING FOR REVIEW | | | | | | 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED | | | LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM | | | PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY | | | EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE | | | THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST | | | CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE | | | RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR | | | DETAILS REGARDING SETBACKS. | | | | | | 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE | | | THE FOLLOWING: | | | | | | A) GENERATOR AND TRANSFER SWITCH MANUFACTURER | | | SPECIFICATIONS. | | | | | | | | | B) RISER DIAGRAM SHOWING LOCATIONS OF ALL | | | EQUIPMENT ELECTRICALLY. | | | | | | C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE | | | EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE | | | STRUCTURES. | | | | | | D) MANUFACTURER SETBACK RECOMMENDATIONS FROM | | | STRUCTURES | | | | | | G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS | | | INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL | | | BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND | | | TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-07-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-11 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-11 |
Time |
08:03 |
Sent To |
B |
|
| Notes |
| 2008-07-11 08:44:11 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE PERMIT APPLICATION WHERE THE PLUMBING | | | CONTRACTOR IS SIGNED ON THE DATE IS INDICATED AS | | | 9/23/08. THIS DATE IS INCORRECT, PLEASE CORRECT. ALSO | | | THE STATE LICENSE OF CERT. OF COMPETENCY FOR THE | | | PLUMBING CONTRACTOR IS REQUIRED. PLEASE REFERENCE A | | | COPY OF THE PLUMBING CONTRACTORS STATE LICENSE NUMBER | | | ATTACHED TO THESE COMMENTS AND CORRECT THE PERMIT | | | APPLCATION. PER FLORIDA STATUTES SECTION 713.135(5) AND | | | (6) ALSO (W.P.B. AS AMENDED) SECTION 105 PERMITS. | | | | | | 2. TWO COPIES OF REVISED GAS ISOMETRIC RISER DIAGRAM | | | PLANS WITH REVISION FEES PAID DESIGNATING THE GENERATOR | | | "NEW" REQUIRED. PER FBC- FUEL GAS CODE SECTION 401.1 | | | SCOPE. | | | | | | 3. TWO COPIES OF A OF A SITE PLAN OR SURVEY CLEARLY | | | INDICATING THE LOCATION OF THE GENERATOR, DIMENSIONS | | | FROM PROPERTY LINES AND DISTANCES FROM ADJACENT | | | STRUCTURES REQUIRED. PER FBC- FUEL GAS CODE SECTION | | | 401.1 SCOPE. | | | | | | 4. TWO COPIES OF MANUFACTURER'S SPECIFICATIONS OF THE | | | GENERATOR CLEARLY INDICATING THE MAKE, MODEL NUMBER, | | | BTU LOAD CAPACITY, SETBACK RECOMMENDATIONS FROM | | | STRUCTURES, AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY ARE REQUIRED. PER FBC- FUEL GAS CODE | | | SECTION 402.2 MAXIMUM GAS DEMAND, ALSO NFPA 54 AND 58 | | | STANDARDS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2008-07-03 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2008-07-03 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:25:07 | HISTORIC APPROVED BY GJUDGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-03 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2008-07-03 17:40:35 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-08 |
Time |
14:21 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-07-08 |
Time |
14:21 |
Sent To |
G |
|
| Notes |
| 2008-07-08 14:24:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | GENERATOR. | | | | | | 2) SUBMIT SITE PLAN SHOWING GENERATOR LOCATION AND ANY | | | BUILDING OPENINGS WITH IN 10 FEET. | | | | | | 3) PLEASE INDICATE FLUE TYPE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-07-08 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-07-08 |
Time |
08:35 |
Sent To |
E |
|
| Notes |
| 2008-07-08 08:45:02 | ***FAILED*** | | | | | | | | | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY?S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED | | | GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER | | | SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT | | | MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED | | | SETBACK. | | | | | | NOTE:REQUIRED SETBACKS FOR POR ZONING DISTRICT: | | | | | | MINIMUM SETBACKS: | | | A.FRONT: 25 FEET. | | | B.CORNER SIDE (IF APPLICABLE): 15 FEET. | | | C.SIDE: TEN FEET. | | | D.INTERIOR SIDE: TEN FEET. | | | E.REAR: 15 FEET. | | | | | | 3) SCREENING REQUIRED.PURSUANT TO SECTION | | | 94-444(B) OF THE ZLDRS: | | | | | | OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY | | | USES; STORAGE AND DISPOSAL FACILITIES.OUTDOOR | | | INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR | | | PROPANE TANKS, AND MECHANICAL EQUIPMENT SHALL NOT BE | | | PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED. | | | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE | | | CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY | | | DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH | | | SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. | | | | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | [email protected] | | | | | | | | | | | | | | | SENT TO "E" - GENRES BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |