Plan Review Details - Permit 08070134
Plan Review Stops For Permit 08070134
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-06 Cont ID  
Sent By shill Date 2009-01-06 Time 11:11 Rev Time 0.00
Received By shill Date 2009-01-06 Time 11:11 Sent To  
Notes
2009-01-06 11:12:50WIND LOAD CALCS FOR ROOFTOP UNIT, LENNOX L SERIES DATED
 12/23/8 PREPARED BY SALAM BLANEY, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-12-19 Cont ID  
Sent By shill Date 2008-12-19 Time 14:21 Rev Time 0.00
Received By shill Date 2008-12-19 Time 14:21 Sent To  
Notes
2008-12-19 14:26:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 COMMENT FROM PREVIOUS LIST:
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE
 CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE
 CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109
 PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2,
 SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF?
 IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED
 BY 50%.
  
 DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED,
 PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR
 PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF
 YOU DISAGREE WITH THE COMMENTS.
  
 3RD ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 PER CONVERSATION WITH ENGINEER, THE SCREW HAS A 3.0
 FACTOR OF SAFETY. THEREFORE, THE ENGINEER FELT THAT A
 FACTOR OF SAFETY OF 2 FOR THE UNIT WAS INCLUDED THROUGH
 THE FACTOR OF SAFETY OF 3 IN THE SCREW VALUES. IT IS
 OUR OPINION THAT THIS RATIONALE IS NOT CORRECT; THERE
 IS A FACTOR OF SAFETY ON THE LOAD, AND A FACTOR OF
 SAFETY ON THE MATERIAL, AND THE TWO ARE DIFFERENT. ONE
 CANNOT SUBSTITUTE FOR THE OTHER. IT SEEMS THAT THE
 FACTOR OF SAFETY FOR THE LOAD SHOULD BE APPLIED TO THE
 LOAD VALUE, THEN DEMONSTRATED THAT THE SCREWS PROPOSED
 MEET THAT DESIGN REQUIREMENT. PLEASE EITHER REVISE THE
 CALCULATIONS ACCORDINGLY OR PROVIDE DOCUMENTATION TO
 SUPPORT YOUR ARGUMENT (CODE REFERENCES, PUBLISHED
 DOCUMENTS, NATIONALLY RECOGNIZED STANDARDS, ETC.). YOU
 ARE WELCOME TO SUBSTANTIATE THE CALCULATIONS SUBMITTED;
 ANY DOCUMENTS SUBMITTED WILL BE REVIEWED AND CONSIDERED
 PROMPTLY. DUE TO THE URGENCY, PLEASE SUBMIT VIA EMAIL.
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-12-18 Cont ID  
Sent By shill Date 2008-12-18 Time 08:25 Rev Time 0.00
Received By shill Date 2008-12-18 Time 08:25 Sent To  
Notes
2008-12-18 08:40:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENT FROM PREVIOUS LIST:
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW:
  
 ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE
 CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE
 CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109
 PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2,
 SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF?
 IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED
 BY 50%.
  
 DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED,
 PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR
 PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF
 YOU DISAGREE WITH THE COMMENTS.
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-11-07 Cont ID  
Sent By shill Date 2008-11-07 Time 12:35 Rev Time 0.00
Received By shill Date 2008-11-06 Time 13:39 Sent To  
Notes
2008-11-07 12:35:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TITLE BLOCK REQUIRED IN ACCORDANCE WITH
 FAC61G15-23.002. (COFA MISSING)
  
 2. THE FIRST PAGE OF CALCS STATES THAT A 33% ALLOWABLE
 STRESS INCREASE WAS TAKEN. SEE FBC1605.3.1.1(2) AND
 CLARIFY USE OF STRESS INCREASE.
  
 3. REPORTS ARE TO USE AN INDEX SHEET IN ACCORDANCE WITH
 FAC61G15-23.002. THE CALCULATIONS SUBMITTED DO NOT HAVE
 PAGE NUMBERS AND ARE NOT OTHERWISE IDENTIFIED. PLEASE
 REVISE.
  
 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY
 FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN
 MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM
 CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL
 WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES
 TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE
 EXPLAIN CALCULATION.
  
 5. THE ENGINEER'S SEAL IS TO BE ONE ACCEPTABLE TO THE
 BOARD, FAC61G15. THE SEAL IS TO STATE "LICENSE" RATHER
 THAN "CERTIFICATE".
  
 REVIEW DONE AT REQUEST OF RR (EXPEDITED)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 16:00 Rev Time 1.22
Received By jwitmer Date 2008-09-11 Time 15:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By jwitmer Date 2008-08-21 Time 09:01 Rev Time 0.88
Received By jwitmer Date 2008-08-21 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By jwitmer Date 2008-07-24 Time 13:39 Rev Time 2.22
Received By jwitmer Date 2008-07-24 Time 13:39 Sent To  
Notes
2008-07-24 15:18:38BUILDING PLAN REVIEW
 PERMIT: 08070134
 ADD: 2021 OKEECHOBEE BLVD # A2
 CONT: GERARDI CONSTRUCTION
 TEL: (813)433-3868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) COVER SHEET CVR, CODE REVIEW
 2A) PLEASE UPDATE TO THE 2007 SUPPLEMENTS, BUILDING
 2B) COMMENT# 7 ENERGY CODE COMMONWEALTH OF
 MASSACHUSETTS, PLEASE CORRECT
 2C) COMMENT# 9 THIS IS NOT THE PALM BEACH COUNTY
 PLANNING, ZONING AND BUILDING DEPARTMENTPLEASE CORRECT
 TO THE CORRECT JURISDICTION
 2D) UNDER THE CODE REVIEW PLANS FAIL TO INDICATE THE
 2004 EXISTING BUILDING CODE AND TO WHAT LEVEL OR
 COMBINATION OF LEVELS THE DESIGN PROFESSIONAL OR OWNER
 HAS DESIGNED TO. FBC EXISTING BUILDING
 CODE301.5.
  
 3) SHEET A5 INDICATES A DETAIL 12/ A9.1 WHICH IS A
 SOFFIT DETAIL INDICATING A SINGLE # 12 PAN HEAD SCREW
 2'-0" O.C. IN TENSION TO HOLD THE 5/8" DRYWALL AND WALL
 FRAMING FROM WHAT TYPE OF STRUCTURE ABOVE?
 PLEASE INDICATE WHAT STRUCTURAL MEMBER THIS SOFFIT
 WILL BE HUNG FROM AND PROVIDE CLALCULATIONS ON THE
 FASTENER IN TENTION LISTED ABOVE AND THE DEAD LOADING
 ON THIS SCREW AND SAFETY FACTORS INVOLVED.
 1604.2 STRENGTH.
  
 4) SHEET A7 DETAIL# 4 INDICATES A BREAK ROOM SINK,
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) SHEET A11 INDICATES WOOD BACKING OR BLOCKING, PLEASE
 SEE 603.1 FOR AREAS WHERE FIRE RETARDANT TREATED WOOD
 CAN BE USED.
  
 6) I COULD NOT FIND IN THE PLANS A ACTUAL FINISH
 SCHEDULE, PLEASE COMPLY WITH 1210.2 WALLS WITHIN 2 FEET
 OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON ABSORBANT SURFACE, TO A HEIGHT OF 4'-0".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2008-09-24 Time 14:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-16 Cont ID  
Sent By dpalmer Date 2008-09-16 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2008-09-16 Time 08:28 Sent To PC
Notes
2008-09-16 08:29:36 
 ** DENIED **
  
 1) NOTE: PLANS NEED ADJUSTMENTS FOR FBC
 13-415.1.ABC.1.1, .1.2.
 CLOSET/STORAGE ROOM MISSING LIGHT FIXTURE AND CONTROL.
 MISSING OVER RIDE CONTROLS AT REAR OF STORE FOR
 OCCUPANTS ENTERING RETAIL SPACE(S).
 MISSING OCCUPANCY SENSOR/OVER RIDE FROM HALL TO REAR
 (WEST) STOCK RECEIVING AREA. THE SINGLE DEVICE AS SHOWN
 WOULD NOT PROVIDE COVERAGE WITH THE RACKING SYSTEM AS
 SHOWN ON PLANS.
 SPOKE TO KEN SNARE HE IS GOING TO VERY THE WATTAGE ON
 WALL-PACK FIXTURES AS THE FIXTURE LEGEND AND INPUT DATA
 REPORT SHOW SOME DIFFERENCES.
 MR. SNARE WILL ALSO VERIFY THE *PHOENIX* FIXTURE WHICH
 IS ON FIXTURE LEGEND HOWEVER NOT ON PLANS. THIS FIXTURE
 CAN BE REDLINED AS NOT TO BE USED WITHOUT HAVING TO
 REVISE PLANS.
 SHEET E-2.1 NEEDS TO BE RE-DONE.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-26 Cont ID  
Sent By dpalmer Date 2008-08-26 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2008-08-26 Time 13:36 Sent To  
Notes
2008-08-26 13:37:38 
  
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
  
  
 1) NOTE: PLEASE SEE THE COVER SHEET WHICH STATES
 CHAPTER 13 OF THE FLORIDA BUILDING CODE FOR
 ACCESSIBILITY. THIS NEEDS TO BE CHAPTER 11. IF THIS
 WERE THE ONLY COMMENT THE PLANS COULD BE REDLINED
 HOWEVER THERE ARE OTHER COMMENTS BELOW WHICH ARE IN
 NEED OF ADDRESSING.
  
 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS STILL MISSING FROM ALL
 NOTATIONS OF ENGINEERING FIRM(S). PLEASE SEE COVER
 SHEET WHICH STILL SHOWS HALLBERG ENGINEERING. THIS IS
 SHOWN FOR ELECTRICAL AND OTHER TRADES.
 PLEASE ALSO SEE THE FIRE PROTECTION SHEETS WHICH STILL
 CONTAIN ARCHITECTURAL FIRM INFORMATION WHICH WOULD
 REQUIRE THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 FAC 61G15-23.002, FS 471.023 FOR ENGINEERS
 FAC61G1-16.004, FS 481.219 FOR ARCHITECTS.
  
 ** THESE ARE REQUIRED FOR ALL TRADES AND FOR ALL
 LOCATIONS ON PLANS WHETHER OR NOT COMMENT IS MADE BY
 THOSE OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR LIGHTING
 CONTROLS REQUIRED PER FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3. PLEASE SEE PLANS AS THERE ARE LOCATIONS IN WHICH
 ARE CONSIDERED SEPARATE SPACES AND ONLY STANDARD SINGLE
 POLE DEVICES ARE SHOWN. THESE ARE NOT ACCEPTABLE AND
 REQUIRE SOME SORT OF AUTOMATED MEANS FOR CONTROLLING
 LIGHTING. IF A SYSTEM IS PROVIDED THEN SEPARATE
 CONTROLS OF OVER RIDING THAT SYSTEM IS REQUIRED.
 PLEASE SEE OTHER AREAS SUCH AS STAGING AREA WHICH ONLY
 SEEMS TO SHOW ONE OCCUPANCY SENSOR TYPE DEVICE. PLEASE
 PROVIDE SPECS ON THIS PROPOSED DEVICE WHICH WILL
 PROVIDE COMPLETE COVERAGE OF THE OVER RIDE FUNCTION.
  
 4) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CLEARLY INDICATE EACH FIXTURE. FOR EXAMPLE
 SOME FIXTURES SUCH AS THE CORELIGHT BRAND DOES NOT
 INDICATE ANY CLEAR DELINEATION OF THE FIXTURE. THE
 FIXTURE LEGEND NOTES A CERTAIN LENGTH HOWEVER BASED ON
 PLANS AND SCALE SHOWN THE LINEAR FEET OF FIXTURES IS
 SUBSTANTIALLY MORE THAN WHAT IS LISTED ON LEGEND. THIS
 IS ALSO NOTED FOR OTHER FIXTURES SUCH AS THE TRACK
 FIXTURE.
 PLEASE SEE THE INPUT DATA REPORT SUBMITTED DOES NOT
 COORDINATE WITH PLANS. IN FACT THERE ARE FIXTURES SHOWN
 ON PLANS WHICH ARE NOT IN THE INPUT DATA REPORT AT ALL.
  
 ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING SHOWN IN
 THE IDR. THE LAST REVIEW OF THESE DOCUMENTS DID NOT
 INDICATE ANY FIXTURES AND NOW THE FIXTURE WHICH ARE
 SHOWN IN THE IDR ARE NOT THE SAME AS FIXTURES ON PLANS.
 IN FACT THERE ARE 250WATT FIXTURES AND 300WATT
 FIXTURE(S) WHICH ARE NOT IN THE IDR AT ALL AND YET
 THESE ARE ON PLANS.
  
 ANOTHER EXAMPLE IS THE INTERIOR LIGHTS WHICH NEED TO
 COORDINATE ALL ZONES AND SPACES. ONE OF THESE IS THE
 DESIGNATIONS OF *OFFICES*. THE IDR SHOWS 23 FIXTURES IN
 OFFICES AND BASED ON THE SHEET A-2, THERE ARE ONLY TWO
 OFFICES AND BOTH OF THEM TOGETHER DO NOT CONTAIN 23
 FIXTURES.
 HOW ARE THESE THINGS POSSIBLE?
 PLEASE COORDINATE ALL LIGHTING FIXTURES ON PLANS WITH
 THE ALLOWANCES. PLEASE SEE TABLE *C* IN 13-415.2.C. IF
 *C* METHOD IS CHOSEN THEN THE LIGHTING WATTAGE PER SQ
 FT OF THE ENTIRE SPACE MAY NOT EXCEED THE LEVEL OF 1.5
 WATTS PER SQUARE FOOT.
 THIS IS NOT AN EXHAUSTED LIST AS THERE ARE OTHER
 INCONSISTENCIES. PLEASE BE SURE TO COORDINATE ALL AND
 CALL TO GO OVER HOW TO SHOW COMPLIANCE.
  
 *** PLEASE SEE 13-415.2.ABC.1.1,.1.2,.1.3, 13-415.2.B,
 13-415.2.C ETC.
  
 5) NOTE: PLEASE COORDINATE AND COMPLETE ALL ROOM AND
 AREA DESIGNATIONS AS SHOWN ON A-2 WITH THAT OF
 ELECTRICAL PLANS. ONE EXAMPLE OF THIS IS ROOM 114 WHICH
 ON THE A2 SHEET IS SHOWN AS AN ELECTRICAL ROOM AND
 NOTES EQUIPMENT ETC. HOWEVER BASED ON THE ELECTRICAL
 PLANS THIS SAME ROOM DOES NOT SHOW ANY ELECTRICAL
 EQUIPMENT.
  
 110.26, 240.24, 408.17 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 6) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW THE
 WORST CASE VOLTAGE DROP NEEDS TO BE SHOWN FOR BRANCH
 CIRCUIT(S). THE PLANS ONLY CHANGED TO QUOTE THE
 REQUIREMENT AND DID NOT PROVIDE THE INFORMATION.
 RESPONSE LETTER MENTIONS THIS WAS DONE AND COULD BE
 FOUND ON E-2 HOWEVER NO VOLTAGE DROP CALCULATION WAS
 PLACED ON PLANS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-29 Cont ID  
Sent By dpalmer Date 2008-07-29 Time 09:52 Rev Time 0.00
Received By dpalmer Date 2008-07-29 Time 09:52 Sent To  
Notes
2008-07-29 09:52:49 
 ** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THE JURISDICTION IN WHICH THIS
 SCOPE OF WORK HAS BEEN APPLIED IN LOCATED IN THE CITY
 OF WEST PALM BEACH, FLORIDA. THERE ARE REFERENCES ON
 PLANS TO PALM BEACH COUNTY BUILDING DEPARTMENT. PLEASE
 ADJUST.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS INCLUSIVE OF ARCHITECTURAL PLANS AS WELL AS
 ELECTRICAL SHEETS.
 SOME CODES LISTED SUCH AS THE 2004 ELECTRICAL CODE AND
 2002 LIFE SAFETY CODE DO NOT EXIST. PLEASE SEE THE
 PLANS ALSO INDICATE THE *COMMONWEALTH OF MASSACHUSETTS*
 FOR THE ENERGY CODE. THE FLORIDA BUILDING CODE CHAPTER
 13 IS THE STATE OF FLORIDA ENERGY CODE.
 PLEASE ADJUST.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2004 FBC W/2007 REVISIONS.
  
 3) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE
 TITLE BLOCKS ON FIRE ALARM PLANS. THE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 REQUIRES THE PRINTED
 NAME, PRINTED LICENSE NUMBER OF THE ENGINEER ALONG WITH
 THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA STATUTES 471.023 FOR THE REQUIREMENT
 OF LICENSING FOR FIRM.
  
 4) NOTE: PLEASE SEE COMMENT #3 ABOVE THE MEP PLANS ARE
 ALSO MISSING THE REQUIRED INFORMATION TO BE COMPLETED
 ON TITLE BLOCKS.
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER IS ALSO
 REQUIRED.
 FAC 61G15-23.002, FS 471.023.
  
 5) NOTE: PLEASE SUBMIT THE COMPLETE PERFORMANCE
 CALCULATIONS AS REQUIRED PER 13-415.2.ABC.1.1, .1.2,
 .1.3, 13-415.2.
 PLEASE SEE THE SQUARE FOOTAGE SHOWN ON THE CALCULATIONS
 AS SUBMITTED ARE LESS THAN THE SQ FT SHOWN ON
 ARCHITECTURAL PLANS.
 PLEASE SEE THE SUBMITTED CALCULATIONS ALONG WITH THE
 INPUT DATA REPORT DO NOT COORDINATE WITH PLANS. ALL
 FIXTURE WATTAGES, FIXTURE COUNTS ETC NEED TO MATCH WITH
 PLANS.
 IN FACT PLEASE SEE THE INPUT DATA REPORT. SOME ITEMS IN
 THE IDR ARE BLANK. HOW IS THIS POSSIBLE WHEN THESE
 ITEMS ARE IN FACT ON PLANS.
 JUST ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING ON
 THE IDR. THIS IS BLANK WITH NO INPUT.
 ** THIS IS ONE EXAMPLE ONLY.
  
 **PLEASE NOTE: THE PERSON AS SIGNED ON THE
 CERTIFICATION SHEET OF THE ENERGY CALCULATIONS AS THE
 *PREPARER* IS NOT LISTED AS ONE OF THE ENGINEERS OF
 RECORD. AS THE SCOPE OF WORK FALLS UNDER THE
 REQUIREMENTS OF AN ENGINEER THIS PERSON MUST BE
 LICENSED IN THE STATE OF FLORIDA AS SUCH.
 PLEASE PROVIDE LICENSE INFORMATION FOR SAID PREPARER
 MR. TREVOR GILBERTSON.
 13-103.1, FS 471.003
  
 6) NOTE: PLEASE SUBMIT PLANS COMPLYING WITH THE FBC
 CHAPTER 13 FOR LIGHTING CONTROLS. THE EMS SYSTEM AS
 SUBMITTED DOES NOT COMPLETELY COMPLY WITH THE FOLLOWING
 SECTIONS. 13-415.1.ABC.1.1,.1.2, .1.3.
 PLEASE SEE NO OVER RIDES FOR OCCUPANTS COULD BE LOCATED
 ON PLANS.
 PLEASE SUBMIT ALL MAXIMUM TIMES ON OVER RIDES AND SPACE
 CONTROLS.
 PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN ON
 PLANS. THE STANDARD DEVICES AS SHOWN DO NOT COMPLY WITH
 13-415.1.ABC.1.2.
 PLEASE COMPLETE LIGHTING CONTROLS AND CIRCUITING FOR
 CONTACTOR SCHEDULES. PLEASE KNOW THIS MAY CHANGE BASED
 ON THE NOTES ABOVE WITH THE SYSTEM DESIGN AT PRESENT.
 ** AS A COMPLETE SYSTEM AND MANY DEVICES ARE NOT SHOWN
 THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 7) NOTE: PLEASE INCLUDE NOTES ON PLANS PER
 13-413.1.ABC.2.1
 DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED
 TO THE BUILDING OWNER, INCLUDING:
 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL
 DISTRIBUTION SYSTEM AND
 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR
 ALL DISTRIBUTION.
 13-413.1.ABC.2.2 MANUALS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING
 MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE
 BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A
 MINIMUM, THE FOLLOWING:
 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED
 OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
 MAINTENANCE.
 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
 PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
 ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
 IDENTIFIED.
 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
 SERVICE AGENCY.
  
 8) NOTE: PLEASE INCLUDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1 AND .1.2.
  
 9) NOTE: PLEASE INCLUDE REQUIRED MINIMUM FOR ADA
 COMPLIANCE FOR FIRE ALARM DEVICES INCLUSIVE OF ALL
 LEVELS LISTED IN 11-4.28.1, .2 AND .3 OF THE FLORIDA
 BUILDING CODE.
  
 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE
 EMERGENCY LIGHTS AND EXIT LIGHTS TO THE LOCAL LIGHTING
 BRANCH CIRCUITS. THE PLANS CALL FOR A LOCK OFF BREAKER
 TO MEET THE EXCEPTION IN THE NEC. PLEASE KNOW THE LOCK
 OFF BREAKER SHALL HAVE THE LOCK OFF MECHANISM PART OF
 THE BREAKER. THE *SNAP* ON OR *CLIP* ON TYPE LOCK OFF
 DEVICES ARE NOT ACCEPTABLE. PLEASE BE SURE TO CHECK THE
 LISTING OF THE UNIT IN DESIGN FOR *PERMANENT*
 INSTALLATION.110.3
 NOT CIRCUITING TO LOCAL BRANCH CIRCUIT IS THE EXCEPTION
 TO THE CODE.
  
 11) NOTE: PLEASE SEE THE RISER AS THIS NOTES *FEEDERS*
 BEFORE THE FIRST MEANS OF DISCONNECT. PLEASE SEE
 DEFINITIONS IN THE NEC AS THESE ARE THE SERVICE
 ENTRANCE CONDUCTORS.
 NEC 100.
  
 12) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE MAIN
 ON PLANS.
 110.26, 240.24, 230.70, 230.71 ETC
  
 13) NOTE: PLEASE SEE RISER AS THIS SHOWS THE
 TRANSFORMER BEING FED FROM THE RENAMED PANEL *A* YET
 THE PANEL *A* SCHEDULE DOES NOT INDICATE ANY OVER
 CURRENT PROTECTION OR FEED TO THIS TRANSFORMER. NEED TO
 VERIFY LOADS, OVER CURRENT PROTECTION, FEEDERS,
 EQUIPMENT GROUNDING ETC. 250.110,240.4,450.3,310.16,
 215.5 ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 14) NOTE: AS THE CIRCUITING FOR EXTERIOR LIGHTS THROUGH
 THE TIME CLOCKS FOR ANY OUTSIDE LIGHTING IS NOT SHOWN
 COMPLIANCE WITH FBC 13-415.1.ABC.1.4 CAN NOT BE
 VERIFIED AS CODE COMPLIANT.
  
 15) NOTE: PLEASE BE SUR EOT INLCUDE THE ADDRESS
 LOCATION AS APPLIED ON TITLE BLOCKS. THE ADDRESS
 LOCATION AS APPLIED IS 2021 OKEECHOBEE BLVD.
 FAC 61G1-16.004, 61G15-23.002
  
 **
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-07 Cont ID  
Sent By mawillia Date 2008-10-07 Time 17:39 Rev Time 0.00
Received By mawillia Date 2008-10-07 Time 16:51 Sent To  
Notes
2008-10-07 17:38:55*****REVISION # 2, DATED 10/01/08, APPROVED*****
  
 REVISED PLAN SHEETS PLAN SHEETS FP1, FP2, AND FP3WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-10 Cont ID  
Sent By mawillia Date 2008-09-10 Time 14:26 Rev Time 0.00
Received By mawillia Date 2008-09-10 Time 13:49 Sent To  
Notes
2008-09-10 14:26:23*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS IND, A1,A5, A8, FP1, FP2,
 FP3, E2, AND E2.1 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-08-25 Cont ID  
Sent By mawillia Date 2008-08-25 Time 19:19 Rev Time 0.00
Received By mawillia Date 2008-08-25 Time 17:50 Sent To  
Notes
2008-08-25 19:13:17*****UNSAT*****
  
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED. THE HIGHLIGHTED
 RESPONSES BY THE PLAN EXAMINER SUGGEST HOW EACH COMMENT
 CAN BE ADDRESSED:
  
  
 01. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SINCE
 THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO POWER
 NOTE #32 (SHEET E2) .
  
 02 FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL
 STATION SEVICE. SINCE THERE ARE NO FIRE ALARM SHEETS,
 ADD COMMENT TO POWER NOTE #7 (SHEET E2) .
  
 03. FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE.
 SINCE THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO
 POWER NOTES (SHEET E2) .
  
 06. PHYSICAL ADDRESS REQUIRED ON EACH SHEET. ADD
 ADDRESS TO THE TITLE BLOCK OF SHEET FP-1, FP-2, & FP-3
  
 11. ADDRESS REQUIRED ON BUILDING SHALL BE A MINIMUM OF
 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING WITH THE
 BACKGROUND FOR COMMERCIAL BUILDINGS. ON SHEET A8,
 DISPLAY/SHOW THE ACTUAL ADDRESS NUMBERS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE
 BOULEVARD
  
 12. KNOX BOX IS REQUIRED ON THE BUILDING FOR AFTER
 NORMAL BUSINESS HOURS EMERGENCY ACCESS. ON SHEET A8,
 DISPLAY/SHOW THE LOCATION OF THE KNOX BOX ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE
 BOULEVARD
  
 13. PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW
 TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY. PLAN
 EXAMINER TO VERIFY FINDINGS REFERRING TO RESULTS
 OBTAINED FROM WEST PALM BEACH WATER AUTHORITY ON 3/08
 OR 18/2008
  
 14. IF THE FIRE DEPARTMENT CONNECTION FOR THE PROJECT
 IS NEW, KNOX LOCKING CAPS ARE REQUIRED. ADD COMMENT TO
 AN APPROPIATE FP SHEET
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
 FIRE INSPECTIONS
 561-804-4751

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-31 Cont ID  
Sent By mwennerg Date 2008-07-31 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2008-07-31 Time 13:56 Sent To  
Notes
2008-07-31 14:14:16***DENIED***
  
 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET FA-1
 NOTE C-1
  
 2) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE. PROVIDE NOTE WITH SPECIFIC LANGUAGE ON
 FA SHEET.
  
 3) FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE.
  
 4) DUCT SMOKE DETECTORS REQUIRED IN SUPPLY DUCT WHERE
 UNIT IS GREATER THAN 2000 CFM UNLESS REQUIRED IN SUPPLY
 AND RETURN FOR LARGER UNITS. FA-1 NOTE 22.
  
 5) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. CONSTRUCTION,
 ALTERATION AND DEMOLITION TO COMPLY WITH NFPA 241.
 PLEASE ADD TO CODE REVIEW ON SHEET CVR.
  
 6) PHYSICAL ADDRESS REQUIRED ON EACH SHEET.
  
 7) PHONE NUMBER FOR WEST PALM BEACH FIRE RESCUE IS
 INCORRECT. THE CORRECT NUMBER IS (561) 804-4700. SHEET
 CVR
  
 8) PROVIDE LIFE SAFETY PLAN ILLUSTRATING REQUIRED MEANS
 OF EGRESS AND TRAVEL DISTANCES.
  
 9) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING THAT COMPLIES WITH NFPA 101,
 CHAPTER-10.
  
 10) INDICATE ANY DOORS THAT ARE FIRE RATED AND PROVIDE
 RATING IN MINUTES IN DOOR SCHEDULE. IN ADDITION, RATED
 DOORS SHALL BE PROVIDED WITH UL LISTED DOOR CLOSERS.
  
 11) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM
 OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND FOR COMMERCIAL BUILDINGS.
  
 12) KNOX BOX IS REQUIRED ON BUILDING FOR AFTER NORMAL
 BUSINESS HOURS EMERGENCY ACCESS. CONTACT WPBFR BUREAU
 OF FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 13) PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW
 TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY?
  
 14) IF FIRE DEPARTMENT CONNECTION FOR PROJECT IS NEW,
 KNOX LOCKING CAPS ARE REQUIRED.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS
 COMMENTS HAVE BEEN ADDRESSED WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
2008-07-31 13:46:50 
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:51 Sent To  
Notes
2008-10-03 16:51:44TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 09:26 Sent To E
Notes
2008-09-18 09:27:23TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 11:38 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 11:38 Sent To  
Notes
2008-09-02 11:41:08TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 09:17 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 09:17 Sent To  
Notes
2008-08-06 09:20:09TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-31 Cont ID  
Sent By mwennerg Date 2008-07-31 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 16:36 Sent To  
Notes
2008-07-03 16:36:59TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-08-25 Cont ID  
Sent By rregueir Date 2008-08-25 Time 13:51 Rev Time 0.00
Received By rregueir Date 2008-08-21 Time 14:19 Sent To  
Notes
2008-08-25 13:51:52*************PROVISO**************
  
 DOCUMENTATION FROM APPLIANCE MANUFACTURER SHALL BE
 PROVIDED SHOWING ALL OUTDOOR APPLIANCES WHICH ARE
 EXPOSED TO WIND ARE DESIGNED TO RESSIST WIND PRESSURES
 IN ACCORDANCE WITH FBCM SECTION 301.13. THIS
 INFORMATION SHALL BE SUBMITTED FOR PLAN REVIEW PRIOR TO
 INSTALLATION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By rregueir Date 2008-07-21 Time 16:28 Rev Time 0.00
Received By rregueir Date 2008-07-18 Time 13:57 Sent To  
Notes
2008-07-21 16:27:58REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ADMINISTRATIVE COMMENTS:
  
 1. PG CVR: IN THE CODE REVIEW SECTION, PLEASE NOTE THE
 FOLLOWING DISCREPANCIES:
 ITEM #4 SHOULD BE: 2005 NATIONAL ELECTRICAL CODE
 ITEM #5 SHOULD BE: 2003 FLORIDA FIRE PREVENTION CODE?
 ITEM #7 SHOULD BE: 2004 FLORIDA BUILDING CODE, BUILDING
 CHAPTER 13.
 ITEM #9 SHOULD BE: WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT / 561-805-6700
 ITEM #11 SHOULD BE: WEST PALM BEACH FIRE DEPARTMENT /
 561-804-4724
  
 2. PAGES CVR, IND AND ALL A PAGES: THESE PAGES (ON ONE
 OF THE TWO SETS SUBMITTED) DO NOT CONTAIN ORIGINAL
 SIGNATURE AND RAISED SEAL OF THE ARCHITECT. RATHER THEY
 CONTAIN WHAT APPEARS TO BE A PRINTED SEAL AND
 PHOTOCOPIED SIGNATURE. PLANS AND SPECIFICATIONS SHALL
 BE SIGNED AND SEALED BY THE DESIGNER OF RECORD IN
 ACCORDANCE WIT FBCB 106.1, FS 481 AND FAC RULE
 61G1-16.
  
 3. PAGE CVR: THIS IS AN EXISTING BUILDING. THE DESIGN
 PROFESSIONAL MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION IN ACCORDANCE WITH FBCEB 301.5.
  
 4. PAGES MP, E AND FP: A TITLE BLOCK SHALL BE USED ON
 EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND
 LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS IN ACCORDANCE WITH FAC RULE
 61G15-23.002(2).
  
 CODE COMMENTS:
  
 5. PG MP-1: THE AIR DISTRIBUTION DEVICE SCHEDULE
 REMARKS FOR SD1 AND SD2 REFER TO A DETAIL ON PAGE
 MP-1.3. PAGE MP-1.3 IS NOT INCLUDED IN THE SUBMITTED
 PLANS. PLEASE SHOW WHERE THIS INFORMATION CAN BE FOUND.
 FBCM 603.1, FBCM 106.1.1.
  
 6. PG MP-1: PROVIDE OUTSIDE AIR CALCULATIONS SHOWING
 OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, REQUIRED
 VENTILATION RATES AND AMOUNTS PROVIDED IN ACCORDANCE
 WITH FBCM 403.3 OR 403.4.
  
 7. PG MP-1: EF SCHEDULE NOTE #1 CALLS FOR EF-1 TO BE
 INTELOCKED WITH LIGHT SWITCH IN BATHROOMS. THIS FAN
 NEEDS TO RUN WHENEVER RTU-2 IS RUNNING (WHETHER OR NOT
 LIGHT SWITCH IS ON) AS RECIRCULATION OF AIR FROM THESE
 SPACES IS PROHIBITED AND ALL AIR SUPPLIED TO THE
 BATHROOMS SHALL BE EXHAUSTED IN ACCORDANCE WITH FBCM
 403.2.1(3).
  
 8. PG MP-1.1: FLOOR PLAN SHOWS A 20X14 SUPPLY DUCT AND
 AN 18X12 RETURN DUCT, BOTH FROM RTU-5, PENETRATING A
 2-HOUR FIRE RESISTANCE RATED WALL. THESE PENETRATIONS
 ARE REQUIRED TO BE PROTECTED WITH FIRE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5. SHOW HOW THESE DUCT
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 THIS SECTION. THE RATED DUCT PENETRATION DETAIL #6 ON
 PAGE MP-1.2 IS NOT APPLICABLE AS IT IS RATED FOR 1-HOUR
 (THE WALL IS 2-HOUR) AND THE SIZES OF THE PENETRATING
 DUCTS EXCEED THE MAXIMUM ALLOWED IN THE INSTRUCTIONS
 WHICH ACCOMPANY THE THROUGH-PENETRATION DETAIL.
  
 9. PG MP-1.1: SEVERAL DUCT BRANCHES DO NOT HAVE SIZES
 SHOWN ON FLOOR PLAN. SOME OF THESE BRANCH SISZES CAN BE
 DETERMINED BASED ON THE NECK SIZE SHOWN ON THE AIR
 DISTRIBUTION SCHEDULE BUT SOME CAN NOT. EXAMPLE: PLEASE
 SHOW ON PLANS THE SIZES OF THE TRANSFER DUCTS AT
 RESTROOM VESTIBULE 114. PLEASE CHECK PLANS FOR ALL
 DUCTS WHICH ARE MISSING SIZES ON PLANS AND PROVIDE THE
 MISSING INFORMATION. AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
  
 10. PG MP-1.2: CURB AND HURRICANE STRAP DETAILS CONTAIN
 CONFLICTING INFORMATION. PLEASE COORDINATE DETAILS AND
 CLARIFY THE WIND RESISTANCE METHOD TO BE USED FOR CURB,
 RTU AND EXHAUST FANS. PROVIDE WIND LOAD CALCULATIONS
 FOR OVERTURN AND UPLIFT FOR ALL ROOFTOP APPLIANCES FOR
 BUILDING REVIEW IN ACCORDANCE WITH FBCM 301.13.
  
 11. PG MP-1.2: IN ADDITION TO THE COMMENTS ABOVE,
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBCM 301.13. PROVIDE SUPPORTING
 DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING
 THESE RTU?S AND EXHAUST FANS ARE DESIGNED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH THIS SECTION. PLEASE
 NOTE THAT THIS REQUIREMENT APPLIES TO THE CONSTRUCTION
 OF THE APPLIANCES THEMSELVES AND NOT JUST THE
 ATTACHMENT TO THE BUILDING STRUCTURE.
  
 12. PG MP-2.1 CONDENSATE DRAIN DETAIL: AUXILIARY OR
 SECONDARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE
 WITH FBCM 307.2.3. A FLOAT SWITCH MAY BE INSTALLED
 INSIDE THE RTU ON THE PRIMARY DRAIN PAN TO COMPLY WITH
 THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 09:03 Rev Time 0.00
Received By kstevens Date 2008-08-11 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By mperson Date 2008-07-22 Time 13:50 Rev Time 0.00
Received By mperson Date 2008-07-22 Time 13:50 Sent To  
Notes
2008-07-22 13:57:11PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A0 DEMOLITION PLAN, KEYED NOTES #3 STATES
 "REMOVE EXISTING RESTROOM FIXTURES", HOWEVER SHEET A2
 FLOOR PLAN IN WOMENS #111 AND MENS #112 BATHROOM
 HANDICAP STALLS THE LAVATORIES ARE NOT BEING
 REINSTALLED. PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTION 11-4.17.3 EXCEPTIONS
 (1)(2).
  
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 2. SHEET A7 DETAIL 1, ENLARGED RESTROOM: CLEARLY
 INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING
 SPACE FOR THE FOLLOWING FIXTURES ON THE DETAIL
 COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE THE FOLLOWING SECTIONS.
 A} SECTION 11-4.15.5 CLEARANCES, DRINKING FOUNTAIN
 (30"X48").
 B} SECTION 11-4.16.2 CLEAR FLOOR SPACE, WATER CLOSETS
 (SEE FIGURE 28).
 C} SECTION 11-4.18.3 CLEAR FLOOR SPACE, URINALS
 (30"X48").
 D} SECTION 11-4.19.3 CLEAR FLOOR SPACE, LAVATORIES
 (30"X48" AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE LAVATORY).
 E} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR
 TURNING SPACE SHALL BE 180-DEGREE WITH A MINIMUM 60"
 CLEAR FLOOR SPACE. (CLEARLY INDICATE TURNING SPACE IN
 BATHROOM, BATHROOM ACCESSIBLE STALLS, AND DRINKING
 FOUNTAIN ROOM)
  
 3. SHEET A7 DETAIL 4, ENLARGED OFFICE/BREAKROON PLAN:
 CLEARLY INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR
 TURNING SPACE FOR THE BREAKROOM SINK ON THE DETAIL
 COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE THE FOLLOWING SECTIONS.
 A} SECTION 11-4.24.5 CLEAR FLOOR SPACE, SINK (30"X48"
 AND CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19"
 UNDERNEATH THE SINK).
 B} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR
 TURNING SPACE SHALL BE 180-DEGREE WITH A MAIMUM 60"
 CLEAR FLOOR SPACE.
  
 4. SHEET MP-1 NOTES LOCATED BELOW PLUMBING FIXTURE
 SCHEDULE: PLEASE ADD THE FOLLOWING FOR THE HC
 ACCESSIBLE URINAL COMPLIANT WITH FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTION 11-4.18.4 FLUSH
 CONTROL FOR THE URINAL MAXIMUM 44" A.F.F.
  
 5. SHEET MP-2 DETAIL 3, WATER RISER DIAGRAM: THE 12"
 AIR CHAMBERS SPECIFIED IN THE DETAIL ARE NOT COMPLIANT
 WITH THE FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER.
 PER 604.9, A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK CLOSING VALVES ARE UTILIZED. PLEASE DELETE
 THE 12" AIR CHAMBERS ON THE RESUBMITTAL.
  
 6. SHEET MP-2 DETAIL 5, WATER HEATER DETAIL: CLEARLY
 INDICATE THE FOLLOWING ON THE WATER HEATER DETAIL
 COMPLIANT WITH THE FBC-2004 PLUMBING SECTIONS.
 A} SECTION 504.4 RELEIF VALVE.
 B} SECTION 504.5 RELIEF VALVE APPROVAL.
 C} SECTION 504.6 RELIEF OUTLET WASTE.
 D} SECTION 504.6.1 DISCHARGE.
 E} SECTION 607.3 THERMAL EXPANSION CONTROL.
  
 7. ALL MP SHEETS FROM MP-1 THRU MP2.1 REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER ON THESE SHEETS.
 PER FAC 61G15-23.002(2).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By kdfreema Date 2008-07-22 Time 09:24 Rev Time 0.00
Received By kdfreema Date 2008-07-22 Time 09:24 Sent To  
Notes
2008-07-22 09:27:11NOT REQUIRED: NO EXTERIOR WORK FALLING UNDER THE
 PURVIEW OF ZONING IS PROPOSED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved