 |
Plan Review Details - Permit 08070134
| Plan Review Stops For Permit 08070134 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2009-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-01-06 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-01-06 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2009-01-06 11:12:50 | WIND LOAD CALCS FOR ROOFTOP UNIT, LENNOX L SERIES DATED | | | 12/23/8 PREPARED BY SALAM BLANEY, PE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2008-12-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-19 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-19 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2008-12-19 14:26:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | | | | COMMENT FROM PREVIOUS LIST: | | | | | | 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY | | | FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN | | | MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM | | | CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL | | | WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES | | | TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE | | | EXPLAIN CALCULATION. | | | | | | 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW: | | | | | | ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE | | | CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE | | | CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109 | | | PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2, | | | SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF? | | | IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED | | | BY 50%. | | | | | | DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED, | | | PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR | | | PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF | | | YOU DISAGREE WITH THE COMMENTS. | | | | | | 3RD ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW: | | | | | | PER CONVERSATION WITH ENGINEER, THE SCREW HAS A 3.0 | | | FACTOR OF SAFETY. THEREFORE, THE ENGINEER FELT THAT A | | | FACTOR OF SAFETY OF 2 FOR THE UNIT WAS INCLUDED THROUGH | | | THE FACTOR OF SAFETY OF 3 IN THE SCREW VALUES. IT IS | | | OUR OPINION THAT THIS RATIONALE IS NOT CORRECT; THERE | | | IS A FACTOR OF SAFETY ON THE LOAD, AND A FACTOR OF | | | SAFETY ON THE MATERIAL, AND THE TWO ARE DIFFERENT. ONE | | | CANNOT SUBSTITUTE FOR THE OTHER. IT SEEMS THAT THE | | | FACTOR OF SAFETY FOR THE LOAD SHOULD BE APPLIED TO THE | | | LOAD VALUE, THEN DEMONSTRATED THAT THE SCREWS PROPOSED | | | MEET THAT DESIGN REQUIREMENT. PLEASE EITHER REVISE THE | | | CALCULATIONS ACCORDINGLY OR PROVIDE DOCUMENTATION TO | | | SUPPORT YOUR ARGUMENT (CODE REFERENCES, PUBLISHED | | | DOCUMENTS, NATIONALLY RECOGNIZED STANDARDS, ETC.). YOU | | | ARE WELCOME TO SUBSTANTIATE THE CALCULATIONS SUBMITTED; | | | ANY DOCUMENTS SUBMITTED WILL BE REVIEWED AND CONSIDERED | | | PROMPTLY. DUE TO THE URGENCY, PLEASE SUBMIT VIA EMAIL. | | | | | | REVIEW DONE AT REQUEST OF RR (EXPEDITED) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-18 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-18 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2008-12-18 08:40:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | COMMENT FROM PREVIOUS LIST: | | | | | | 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY | | | FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN | | | MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM | | | CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL | | | WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES | | | TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE | | | EXPLAIN CALCULATION. | | | | | | 2ND ROOFTOP EQUIPMENT WIND LOAD CALC REVIEW: | | | | | | ALL COMMENTS WERE ADDRESSED EXCEPT FOR ITEM 4. PLEASE | | | CONTACT ME TO EXPLAIN RATIONALE. IT APPEARS THAT THE | | | CAPACITY OF THE SCRE HAS BEEN INCREASED BY 3/2 (109 | | | PULLOUT TIMES 3/2). FOR A FACTOR OF SAFETY OF 2, | | | SHOULDN'T IT BE MULTIPLIED BY 1/2, REDUCING IT BY HALF? | | | IT APPEARS THAT THE SCREW CAPACITY HAS BEEN INCREASED | | | BY 50%. | | | | | | DUE TO THE URGENCY OF GETTING THIS MATTER RESOLVED, | | | PLEASE SUBMIT THE CALCULATIONS VIA EMAIL FOR | | | PRELIMINARY REVIEW. PLEASE FEEL FREE TO CONTACT ME IF | | | YOU DISAGREE WITH THE COMMENTS. | | | | | | REVIEW DONE AT REQUEST OF RR (EXPEDITED) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-11-07 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-11-06 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2008-11-07 12:35:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. TITLE BLOCK REQUIRED IN ACCORDANCE WITH | | | FAC61G15-23.002. (COFA MISSING) | | | | | | 2. THE FIRST PAGE OF CALCS STATES THAT A 33% ALLOWABLE | | | STRESS INCREASE WAS TAKEN. SEE FBC1605.3.1.1(2) AND | | | CLARIFY USE OF STRESS INCREASE. | | | | | | 3. REPORTS ARE TO USE AN INDEX SHEET IN ACCORDANCE WITH | | | FAC61G15-23.002. THE CALCULATIONS SUBMITTED DO NOT HAVE | | | PAGE NUMBERS AND ARE NOT OTHERWISE IDENTIFIED. PLEASE | | | REVISE. | | | | | | 4. IF PULLOUT VALUE FOR #10 SCREW IS 109, WITH A SAFETY | | | FACTOR OF 2, SHOULDN'T IT BE DIVIDED BY TWO RATHER THAN | | | MULTIPLIED BY TWO? CAPACITY WITH STRESS INCREASE FROM | | | CALCULATIONS PROVIDED IS 290; IT DOES NOT SEEM LOGICAL | | | WHEN PRODUCT DATA STATES 109. THIS COMMENT ALSO APPLIES | | | TO SHEAR FOR #10 AND PULLOUT AND SHEAR FOR #12. PLEASE | | | EXPLAIN CALCULATION. | | | | | | 5. THE ENGINEER'S SEAL IS TO BE ONE ACCEPTABLE TO THE | | | BOARD, FAC61G15. THE SEAL IS TO STATE "LICENSE" RATHER | | | THAN "CERTIFICATE". | | | | | | REVIEW DONE AT REQUEST OF RR (EXPEDITED) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-09-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-11 |
Time |
16:00 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-09-11 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-08-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-21 |
Time |
09:01 |
Rev Time |
0.88 |
| Received By |
jwitmer |
Date |
2008-08-21 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-07-24 |
Time |
13:39 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-07-24 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2008-07-24 15:18:38 | BUILDING PLAN REVIEW | | | PERMIT: 08070134 | | | ADD: 2021 OKEECHOBEE BLVD # A2 | | | CONT: GERARDI CONSTRUCTION | | | TEL: (813)433-3868 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL FL S S 713.13NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. | | | | | | 2) COVER SHEET CVR, CODE REVIEW | | | 2A) PLEASE UPDATE TO THE 2007 SUPPLEMENTS, BUILDING | | | 2B) COMMENT# 7 ENERGY CODE COMMONWEALTH OF | | | MASSACHUSETTS, PLEASE CORRECT | | | 2C) COMMENT# 9 THIS IS NOT THE PALM BEACH COUNTY | | | PLANNING, ZONING AND BUILDING DEPARTMENTPLEASE CORRECT | | | TO THE CORRECT JURISDICTION | | | 2D) UNDER THE CODE REVIEW PLANS FAIL TO INDICATE THE | | | 2004 EXISTING BUILDING CODE AND TO WHAT LEVEL OR | | | COMBINATION OF LEVELS THE DESIGN PROFESSIONAL OR OWNER | | | HAS DESIGNED TO. FBC EXISTING BUILDING | | | CODE301.5. | | | | | | 3) SHEET A5 INDICATES A DETAIL 12/ A9.1 WHICH IS A | | | SOFFIT DETAIL INDICATING A SINGLE # 12 PAN HEAD SCREW | | | 2'-0" O.C. IN TENSION TO HOLD THE 5/8" DRYWALL AND WALL | | | FRAMING FROM WHAT TYPE OF STRUCTURE ABOVE? | | | PLEASE INDICATE WHAT STRUCTURAL MEMBER THIS SOFFIT | | | WILL BE HUNG FROM AND PROVIDE CLALCULATIONS ON THE | | | FASTENER IN TENTION LISTED ABOVE AND THE DEAD LOADING | | | ON THIS SCREW AND SAFETY FACTORS INVOLVED. | | | 1604.2 STRENGTH. | | | | | | 4) SHEET A7 DETAIL# 4 INDICATES A BREAK ROOM SINK, | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE | | | COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH | | | FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" | | | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | | SINK. | | | | | | 5) SHEET A11 INDICATES WOOD BACKING OR BLOCKING, PLEASE | | | SEE 603.1 FOR AREAS WHERE FIRE RETARDANT TREATED WOOD | | | CAN BE USED. | | | | | | 6) I COULD NOT FIND IN THE PLANS A ACTUAL FINISH | | | SCHEDULE, PLEASE COMPLY WITH 1210.2 WALLS WITHIN 2 FEET | | | OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | | NON ABSORBANT SURFACE, TO A HEIGHT OF 4'-0". | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-24 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-24 |
Time |
14:35 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-16 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-16 |
Time |
08:28 |
Sent To |
PC |
|
| Notes |
| 2008-09-16 08:29:36 | | | | ** DENIED ** | | | | | | 1) NOTE: PLANS NEED ADJUSTMENTS FOR FBC | | | 13-415.1.ABC.1.1, .1.2. | | | CLOSET/STORAGE ROOM MISSING LIGHT FIXTURE AND CONTROL. | | | MISSING OVER RIDE CONTROLS AT REAR OF STORE FOR | | | OCCUPANTS ENTERING RETAIL SPACE(S). | | | MISSING OCCUPANCY SENSOR/OVER RIDE FROM HALL TO REAR | | | (WEST) STOCK RECEIVING AREA. THE SINGLE DEVICE AS SHOWN | | | WOULD NOT PROVIDE COVERAGE WITH THE RACKING SYSTEM AS | | | SHOWN ON PLANS. | | | SPOKE TO KEN SNARE HE IS GOING TO VERY THE WATTAGE ON | | | WALL-PACK FIXTURES AS THE FIXTURE LEGEND AND INPUT DATA | | | REPORT SHOW SOME DIFFERENCES. | | | MR. SNARE WILL ALSO VERIFY THE *PHOENIX* FIXTURE WHICH | | | IS ON FIXTURE LEGEND HOWEVER NOT ON PLANS. THIS FIXTURE | | | CAN BE REDLINED AS NOT TO BE USED WITHOUT HAVING TO | | | REVISE PLANS. | | | SHEET E-2.1 NEEDS TO BE RE-DONE. | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-26 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-26 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-08-26 13:37:38 | | | | | | | | | | | | | | | | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | | | | | | | | | | 1) NOTE: PLEASE SEE THE COVER SHEET WHICH STATES | | | CHAPTER 13 OF THE FLORIDA BUILDING CODE FOR | | | ACCESSIBILITY. THIS NEEDS TO BE CHAPTER 11. IF THIS | | | WERE THE ONLY COMMENT THE PLANS COULD BE REDLINED | | | HOWEVER THERE ARE OTHER COMMENTS BELOW WHICH ARE IN | | | NEED OF ADDRESSING. | | | | | | 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER IS STILL MISSING FROM ALL | | | NOTATIONS OF ENGINEERING FIRM(S). PLEASE SEE COVER | | | SHEET WHICH STILL SHOWS HALLBERG ENGINEERING. THIS IS | | | SHOWN FOR ELECTRICAL AND OTHER TRADES. | | | PLEASE ALSO SEE THE FIRE PROTECTION SHEETS WHICH STILL | | | CONTAIN ARCHITECTURAL FIRM INFORMATION WHICH WOULD | | | REQUIRE THE CERTIFICATE OF AUTHORIZATION NUMBER. | | | | | | FAC 61G15-23.002, FS 471.023 FOR ENGINEERS | | | FAC61G1-16.004, FS 481.219 FOR ARCHITECTS. | | | | | | ** THESE ARE REQUIRED FOR ALL TRADES AND FOR ALL | | | LOCATIONS ON PLANS WHETHER OR NOT COMMENT IS MADE BY | | | THOSE OTHER TRADE REVIEWER(S). | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR LIGHTING | | | CONTROLS REQUIRED PER FBC 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. PLEASE SEE PLANS AS THERE ARE LOCATIONS IN WHICH | | | ARE CONSIDERED SEPARATE SPACES AND ONLY STANDARD SINGLE | | | POLE DEVICES ARE SHOWN. THESE ARE NOT ACCEPTABLE AND | | | REQUIRE SOME SORT OF AUTOMATED MEANS FOR CONTROLLING | | | LIGHTING. IF A SYSTEM IS PROVIDED THEN SEPARATE | | | CONTROLS OF OVER RIDING THAT SYSTEM IS REQUIRED. | | | PLEASE SEE OTHER AREAS SUCH AS STAGING AREA WHICH ONLY | | | SEEMS TO SHOW ONE OCCUPANCY SENSOR TYPE DEVICE. PLEASE | | | PROVIDE SPECS ON THIS PROPOSED DEVICE WHICH WILL | | | PROVIDE COMPLETE COVERAGE OF THE OVER RIDE FUNCTION. | | | | | | 4) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON | | | PLANS AND CLEARLY INDICATE EACH FIXTURE. FOR EXAMPLE | | | SOME FIXTURES SUCH AS THE CORELIGHT BRAND DOES NOT | | | INDICATE ANY CLEAR DELINEATION OF THE FIXTURE. THE | | | FIXTURE LEGEND NOTES A CERTAIN LENGTH HOWEVER BASED ON | | | PLANS AND SCALE SHOWN THE LINEAR FEET OF FIXTURES IS | | | SUBSTANTIALLY MORE THAN WHAT IS LISTED ON LEGEND. THIS | | | IS ALSO NOTED FOR OTHER FIXTURES SUCH AS THE TRACK | | | FIXTURE. | | | PLEASE SEE THE INPUT DATA REPORT SUBMITTED DOES NOT | | | COORDINATE WITH PLANS. IN FACT THERE ARE FIXTURES SHOWN | | | ON PLANS WHICH ARE NOT IN THE INPUT DATA REPORT AT ALL. | | | | | | ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING SHOWN IN | | | THE IDR. THE LAST REVIEW OF THESE DOCUMENTS DID NOT | | | INDICATE ANY FIXTURES AND NOW THE FIXTURE WHICH ARE | | | SHOWN IN THE IDR ARE NOT THE SAME AS FIXTURES ON PLANS. | | | IN FACT THERE ARE 250WATT FIXTURES AND 300WATT | | | FIXTURE(S) WHICH ARE NOT IN THE IDR AT ALL AND YET | | | THESE ARE ON PLANS. | | | | | | ANOTHER EXAMPLE IS THE INTERIOR LIGHTS WHICH NEED TO | | | COORDINATE ALL ZONES AND SPACES. ONE OF THESE IS THE | | | DESIGNATIONS OF *OFFICES*. THE IDR SHOWS 23 FIXTURES IN | | | OFFICES AND BASED ON THE SHEET A-2, THERE ARE ONLY TWO | | | OFFICES AND BOTH OF THEM TOGETHER DO NOT CONTAIN 23 | | | FIXTURES. | | | HOW ARE THESE THINGS POSSIBLE? | | | PLEASE COORDINATE ALL LIGHTING FIXTURES ON PLANS WITH | | | THE ALLOWANCES. PLEASE SEE TABLE *C* IN 13-415.2.C. IF | | | *C* METHOD IS CHOSEN THEN THE LIGHTING WATTAGE PER SQ | | | FT OF THE ENTIRE SPACE MAY NOT EXCEED THE LEVEL OF 1.5 | | | WATTS PER SQUARE FOOT. | | | THIS IS NOT AN EXHAUSTED LIST AS THERE ARE OTHER | | | INCONSISTENCIES. PLEASE BE SURE TO COORDINATE ALL AND | | | CALL TO GO OVER HOW TO SHOW COMPLIANCE. | | | | | | *** PLEASE SEE 13-415.2.ABC.1.1,.1.2,.1.3, 13-415.2.B, | | | 13-415.2.C ETC. | | | | | | 5) NOTE: PLEASE COORDINATE AND COMPLETE ALL ROOM AND | | | AREA DESIGNATIONS AS SHOWN ON A-2 WITH THAT OF | | | ELECTRICAL PLANS. ONE EXAMPLE OF THIS IS ROOM 114 WHICH | | | ON THE A2 SHEET IS SHOWN AS AN ELECTRICAL ROOM AND | | | NOTES EQUIPMENT ETC. HOWEVER BASED ON THE ELECTRICAL | | | PLANS THIS SAME ROOM DOES NOT SHOW ANY ELECTRICAL | | | EQUIPMENT. | | | | | | 110.26, 240.24, 408.17 ETC | | | FBC 106.1.1 FOR CLARITY AND COORDINATION. | | | | | | 6) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW THE | | | WORST CASE VOLTAGE DROP NEEDS TO BE SHOWN FOR BRANCH | | | CIRCUIT(S). THE PLANS ONLY CHANGED TO QUOTE THE | | | REQUIREMENT AND DID NOT PROVIDE THE INFORMATION. | | | RESPONSE LETTER MENTIONS THIS WAS DONE AND COULD BE | | | FOUND ON E-2 HOWEVER NO VOLTAGE DROP CALCULATION WAS | | | PLACED ON PLANS. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-29 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-29 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2008-07-29 09:52:49 | | | | ** DENIEDREVIEW ** | | | | | | | | | 1) NOTE:PLEASE SEE THE JURISDICTION IN WHICH THIS | | | SCOPE OF WORK HAS BEEN APPLIED IN LOCATED IN THE CITY | | | OF WEST PALM BEACH, FLORIDA. THERE ARE REFERENCES ON | | | PLANS TO PALM BEACH COUNTY BUILDING DEPARTMENT. PLEASE | | | ADJUST. | | | | | | 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED | | | ON PLANS INCLUSIVE OF ARCHITECTURAL PLANS AS WELL AS | | | ELECTRICAL SHEETS. | | | SOME CODES LISTED SUCH AS THE 2004 ELECTRICAL CODE AND | | | 2002 LIFE SAFETY CODE DO NOT EXIST. PLEASE SEE THE | | | PLANS ALSO INDICATE THE *COMMONWEALTH OF MASSACHUSETTS* | | | FOR THE ENERGY CODE. THE FLORIDA BUILDING CODE CHAPTER | | | 13 IS THE STATE OF FLORIDA ENERGY CODE. | | | PLEASE ADJUST. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | 2004 FBC W/2007 REVISIONS. | | | | | | 3) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE | | | TITLE BLOCKS ON FIRE ALARM PLANS. THE FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.002 REQUIRES THE PRINTED | | | NAME, PRINTED LICENSE NUMBER OF THE ENGINEER ALONG WITH | | | THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. | | | PLEASE SEE FLORIDA STATUTES 471.023 FOR THE REQUIREMENT | | | OF LICENSING FOR FIRM. | | | | | | 4) NOTE: PLEASE SEE COMMENT #3 ABOVE THE MEP PLANS ARE | | | ALSO MISSING THE REQUIRED INFORMATION TO BE COMPLETED | | | ON TITLE BLOCKS. | | | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER IS ALSO | | | REQUIRED. | | | FAC 61G15-23.002, FS 471.023. | | | | | | 5) NOTE: PLEASE SUBMIT THE COMPLETE PERFORMANCE | | | CALCULATIONS AS REQUIRED PER 13-415.2.ABC.1.1, .1.2, | | | .1.3, 13-415.2. | | | PLEASE SEE THE SQUARE FOOTAGE SHOWN ON THE CALCULATIONS | | | AS SUBMITTED ARE LESS THAN THE SQ FT SHOWN ON | | | ARCHITECTURAL PLANS. | | | PLEASE SEE THE SUBMITTED CALCULATIONS ALONG WITH THE | | | INPUT DATA REPORT DO NOT COORDINATE WITH PLANS. ALL | | | FIXTURE WATTAGES, FIXTURE COUNTS ETC NEED TO MATCH WITH | | | PLANS. | | | IN FACT PLEASE SEE THE INPUT DATA REPORT. SOME ITEMS IN | | | THE IDR ARE BLANK. HOW IS THIS POSSIBLE WHEN THESE | | | ITEMS ARE IN FACT ON PLANS. | | | JUST ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING ON | | | THE IDR. THIS IS BLANK WITH NO INPUT. | | | ** THIS IS ONE EXAMPLE ONLY. | | | | | | **PLEASE NOTE: THE PERSON AS SIGNED ON THE | | | CERTIFICATION SHEET OF THE ENERGY CALCULATIONS AS THE | | | *PREPARER* IS NOT LISTED AS ONE OF THE ENGINEERS OF | | | RECORD. AS THE SCOPE OF WORK FALLS UNDER THE | | | REQUIREMENTS OF AN ENGINEER THIS PERSON MUST BE | | | LICENSED IN THE STATE OF FLORIDA AS SUCH. | | | PLEASE PROVIDE LICENSE INFORMATION FOR SAID PREPARER | | | MR. TREVOR GILBERTSON. | | | 13-103.1, FS 471.003 | | | | | | 6) NOTE: PLEASE SUBMIT PLANS COMPLYING WITH THE FBC | | | CHAPTER 13 FOR LIGHTING CONTROLS. THE EMS SYSTEM AS | | | SUBMITTED DOES NOT COMPLETELY COMPLY WITH THE FOLLOWING | | | SECTIONS. 13-415.1.ABC.1.1,.1.2, .1.3. | | | PLEASE SEE NO OVER RIDES FOR OCCUPANTS COULD BE LOCATED | | | ON PLANS. | | | PLEASE SUBMIT ALL MAXIMUM TIMES ON OVER RIDES AND SPACE | | | CONTROLS. | | | PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN ON | | | PLANS. THE STANDARD DEVICES AS SHOWN DO NOT COMPLY WITH | | | 13-415.1.ABC.1.2. | | | PLEASE COMPLETE LIGHTING CONTROLS AND CIRCUITING FOR | | | CONTACTOR SCHEDULES. PLEASE KNOW THIS MAY CHANGE BASED | | | ON THE NOTES ABOVE WITH THE SYSTEM DESIGN AT PRESENT. | | | ** AS A COMPLETE SYSTEM AND MANY DEVICES ARE NOT SHOWN | | | THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING | | | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. | | | | | | 7) NOTE: PLEASE INCLUDE NOTES ON PLANS PER | | | 13-413.1.ABC.2.1 | | | DRAWINGS. | | | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 | | | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD | | | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED | | | TO THE BUILDING OWNER, INCLUDING: | | | 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL | | | DISTRIBUTION SYSTEM AND | | | 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR | | | ALL DISTRIBUTION. | | | 13-413.1.ABC.2.2 MANUALS. | | | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING | | | MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE | | | BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A | | | MINIMUM, THE FOLLOWING: | | | 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED | | | OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING | | | MAINTENANCE. | | | 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH | | | PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED | | | ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY | | | IDENTIFIED. | | | 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED | | | SERVICE AGENCY. | | | | | | 8) NOTE: PLEASE INCLUDE WORST CASE VOLTAGE DROP PER | | | 13-413.1.ABC.1.1 AND .1.2. | | | | | | 9) NOTE: PLEASE INCLUDE REQUIRED MINIMUM FOR ADA | | | COMPLIANCE FOR FIRE ALARM DEVICES INCLUSIVE OF ALL | | | LEVELS LISTED IN 11-4.28.1, .2 AND .3 OF THE FLORIDA | | | BUILDING CODE. | | | | | | 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE | | | EMERGENCY LIGHTS AND EXIT LIGHTS TO THE LOCAL LIGHTING | | | BRANCH CIRCUITS. THE PLANS CALL FOR A LOCK OFF BREAKER | | | TO MEET THE EXCEPTION IN THE NEC. PLEASE KNOW THE LOCK | | | OFF BREAKER SHALL HAVE THE LOCK OFF MECHANISM PART OF | | | THE BREAKER. THE *SNAP* ON OR *CLIP* ON TYPE LOCK OFF | | | DEVICES ARE NOT ACCEPTABLE. PLEASE BE SURE TO CHECK THE | | | LISTING OF THE UNIT IN DESIGN FOR *PERMANENT* | | | INSTALLATION.110.3 | | | NOT CIRCUITING TO LOCAL BRANCH CIRCUIT IS THE EXCEPTION | | | TO THE CODE. | | | | | | 11) NOTE: PLEASE SEE THE RISER AS THIS NOTES *FEEDERS* | | | BEFORE THE FIRST MEANS OF DISCONNECT. PLEASE SEE | | | DEFINITIONS IN THE NEC AS THESE ARE THE SERVICE | | | ENTRANCE CONDUCTORS. | | | NEC 100. | | | | | | 12) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE MAIN | | | ON PLANS. | | | 110.26, 240.24, 230.70, 230.71 ETC | | | | | | 13) NOTE: PLEASE SEE RISER AS THIS SHOWS THE | | | TRANSFORMER BEING FED FROM THE RENAMED PANEL *A* YET | | | THE PANEL *A* SCHEDULE DOES NOT INDICATE ANY OVER | | | CURRENT PROTECTION OR FEED TO THIS TRANSFORMER. NEED TO | | | VERIFY LOADS, OVER CURRENT PROTECTION, FEEDERS, | | | EQUIPMENT GROUNDING ETC. 250.110,240.4,450.3,310.16, | | | 215.5 ETC | | | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND | | | CLARITY. | | | | | | 14) NOTE: AS THE CIRCUITING FOR EXTERIOR LIGHTS THROUGH | | | THE TIME CLOCKS FOR ANY OUTSIDE LIGHTING IS NOT SHOWN | | | COMPLIANCE WITH FBC 13-415.1.ABC.1.4 CAN NOT BE | | | VERIFIED AS CODE COMPLIANT. | | | | | | 15) NOTE: PLEASE BE SUR EOT INLCUDE THE ADDRESS | | | LOCATION AS APPLIED ON TITLE BLOCKS. THE ADDRESS | | | LOCATION AS APPLIED IS 2021 OKEECHOBEE BLVD. | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | ** | | | | | | | | | IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-10-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-07 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-07 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2008-10-07 17:38:55 | *****REVISION # 2, DATED 10/01/08, APPROVED***** | | | | | | REVISED PLAN SHEETS PLAN SHEETS FP1, FP2, AND FP3WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-09-10 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-09-10 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2008-09-10 14:26:23 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEETS IND, A1,A5, A8, FP1, FP2, | | | FP3, E2, AND E2.1 WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-25 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-25 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2008-08-25 19:13:17 | *****UNSAT***** | | | | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED. THE HIGHLIGHTED | | | RESPONSES BY THE PLAN EXAMINER SUGGEST HOW EACH COMMENT | | | CAN BE ADDRESSED: | | | | | | | | | 01. DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SINCE | | | THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO POWER | | | NOTE #32 (SHEET E2) . | | | | | | 02 FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL | | | STATION SEVICE. SINCE THERE ARE NO FIRE ALARM SHEETS, | | | ADD COMMENT TO POWER NOTE #7 (SHEET E2) . | | | | | | 03. FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE. | | | SINCE THERE ARE NO FIRE ALARM SHEETS, ADD COMMENT TO | | | POWER NOTES (SHEET E2) . | | | | | | 06. PHYSICAL ADDRESS REQUIRED ON EACH SHEET. ADD | | | ADDRESS TO THE TITLE BLOCK OF SHEET FP-1, FP-2, & FP-3 | | | | | | 11. ADDRESS REQUIRED ON BUILDING SHALL BE A MINIMUM OF | | | 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING WITH THE | | | BACKGROUND FOR COMMERCIAL BUILDINGS. ON SHEET A8, | | | DISPLAY/SHOW THE ACTUAL ADDRESS NUMBERS ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE | | | BOULEVARD | | | | | | 12. KNOX BOX IS REQUIRED ON THE BUILDING FOR AFTER | | | NORMAL BUSINESS HOURS EMERGENCY ACCESS. ON SHEET A8, | | | DISPLAY/SHOW THE LOCATION OF THE KNOX BOX ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS OKEECHOBEE | | | BOULEVARD | | | | | | 13. PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW | | | TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY. PLAN | | | EXAMINER TO VERIFY FINDINGS REFERRING TO RESULTS | | | OBTAINED FROM WEST PALM BEACH WATER AUTHORITY ON 3/08 | | | OR 18/2008 | | | | | | 14. IF THE FIRE DEPARTMENT CONNECTION FOR THE PROJECT | | | IS NEW, KNOX LOCKING CAPS ARE REQUIRED. ADD COMMENT TO | | | AN APPROPIATE FP SHEET | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | FIRE INSPECTIONS | | | 561-804-4751 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-07-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-31 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-31 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2008-07-31 14:14:16 | ***DENIED*** | | | | | | 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET FA-1 | | | NOTE C-1 | | | | | | 2) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL | | | STATION SERVICE. PROVIDE NOTE WITH SPECIFIC LANGUAGE ON | | | FA SHEET. | | | | | | 3) FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE. | | | | | | 4) DUCT SMOKE DETECTORS REQUIRED IN SUPPLY DUCT WHERE | | | UNIT IS GREATER THAN 2000 CFM UNLESS REQUIRED IN SUPPLY | | | AND RETURN FOR LARGER UNITS. FA-1 NOTE 22. | | | | | | 5) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY TO COMPLY WITH NFPA 101, 2003. CONSTRUCTION, | | | ALTERATION AND DEMOLITION TO COMPLY WITH NFPA 241. | | | PLEASE ADD TO CODE REVIEW ON SHEET CVR. | | | | | | 6) PHYSICAL ADDRESS REQUIRED ON EACH SHEET. | | | | | | 7) PHONE NUMBER FOR WEST PALM BEACH FIRE RESCUE IS | | | INCORRECT. THE CORRECT NUMBER IS (561) 804-4700. SHEET | | | CVR | | | | | | 8) PROVIDE LIFE SAFETY PLAN ILLUSTRATING REQUIRED MEANS | | | OF EGRESS AND TRAVEL DISTANCES. | | | | | | 9) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING THAT COMPLIES WITH NFPA 101, | | | CHAPTER-10. | | | | | | 10) INDICATE ANY DOORS THAT ARE FIRE RATED AND PROVIDE | | | RATING IN MINUTES IN DOOR SCHEDULE. IN ADDITION, RATED | | | DOORS SHALL BE PROVIDED WITH UL LISTED DOOR CLOSERS. | | | | | | 11) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM | | | OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH | | | BACKGROUND FOR COMMERCIAL BUILDINGS. | | | | | | 12) KNOX BOX IS REQUIRED ON BUILDING FOR AFTER NORMAL | | | BUSINESS HOURS EMERGENCY ACCESS. CONTACT WPBFR BUREAU | | | OF FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE. | | | | | | 13) PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW | | | TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY? | | | | | | 14) IF FIRE DEPARTMENT CONNECTION FOR PROJECT IS NEW, | | | KNOX LOCKING CAPS ARE REQUIRED. | | | | | | | | | A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS | | | COMMENTS HAVE BEEN ADDRESSED WOULD HELP EXPEDITE THE | | | PLAN REVIEW PROCESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2008-07-31 13:46:50 | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-03 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-03 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2008-10-03 16:51:44 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-18 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-18 |
Time |
09:26 |
Sent To |
E |
|
| Notes |
| 2008-09-18 09:27:23 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-02 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-02 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2008-09-02 11:41:08 | TO "COMM" BD#48 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-06 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-06 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2008-08-06 09:20:09 | TO "COMM" BD#38 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-31 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-03 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2008-07-03 16:36:59 | TO "COMM" BD#38 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-25 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-21 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2008-08-25 13:51:52 | *************PROVISO************** | | | | | | DOCUMENTATION FROM APPLIANCE MANUFACTURER SHALL BE | | | PROVIDED SHOWING ALL OUTDOOR APPLIANCES WHICH ARE | | | EXPOSED TO WIND ARE DESIGNED TO RESSIST WIND PRESSURES | | | IN ACCORDANCE WITH FBCM SECTION 301.13. THIS | | | INFORMATION SHALL BE SUBMITTED FOR PLAN REVIEW PRIOR TO | | | INSTALLATION OF OUTDOOR APPLIANCES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-07-21 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-07-18 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2008-07-21 16:27:58 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | ADMINISTRATIVE COMMENTS: | | | | | | 1. PG CVR: IN THE CODE REVIEW SECTION, PLEASE NOTE THE | | | FOLLOWING DISCREPANCIES: | | | ITEM #4 SHOULD BE: 2005 NATIONAL ELECTRICAL CODE | | | ITEM #5 SHOULD BE: 2003 FLORIDA FIRE PREVENTION CODE? | | | ITEM #7 SHOULD BE: 2004 FLORIDA BUILDING CODE, BUILDING | | | CHAPTER 13. | | | ITEM #9 SHOULD BE: WEST PALM BEACH CONSTRUCTION | | | SERVICES DEPARTMENT / 561-805-6700 | | | ITEM #11 SHOULD BE: WEST PALM BEACH FIRE DEPARTMENT / | | | 561-804-4724 | | | | | | 2. PAGES CVR, IND AND ALL A PAGES: THESE PAGES (ON ONE | | | OF THE TWO SETS SUBMITTED) DO NOT CONTAIN ORIGINAL | | | SIGNATURE AND RAISED SEAL OF THE ARCHITECT. RATHER THEY | | | CONTAIN WHAT APPEARS TO BE A PRINTED SEAL AND | | | PHOTOCOPIED SIGNATURE. PLANS AND SPECIFICATIONS SHALL | | | BE SIGNED AND SEALED BY THE DESIGNER OF RECORD IN | | | ACCORDANCE WIT FBCB 106.1, FS 481 AND FAC RULE | | | 61G1-16. | | | | | | 3. PAGE CVR: THIS IS AN EXISTING BUILDING. THE DESIGN | | | PROFESSIONAL MUST ELECT ONE OR A COMBINATION OF LEVELS | | | OF ALTERATION IN ACCORDANCE WITH FBCEB 301.5. | | | | | | 4. PAGES MP, E AND FP: A TITLE BLOCK SHALL BE USED ON | | | EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND | | | LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING | | | THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS IN ACCORDANCE WITH FAC RULE | | | 61G15-23.002(2). | | | | | | CODE COMMENTS: | | | | | | 5. PG MP-1: THE AIR DISTRIBUTION DEVICE SCHEDULE | | | REMARKS FOR SD1 AND SD2 REFER TO A DETAIL ON PAGE | | | MP-1.3. PAGE MP-1.3 IS NOT INCLUDED IN THE SUBMITTED | | | PLANS. PLEASE SHOW WHERE THIS INFORMATION CAN BE FOUND. | | | FBCM 603.1, FBCM 106.1.1. | | | | | | 6. PG MP-1: PROVIDE OUTSIDE AIR CALCULATIONS SHOWING | | | OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, REQUIRED | | | VENTILATION RATES AND AMOUNTS PROVIDED IN ACCORDANCE | | | WITH FBCM 403.3 OR 403.4. | | | | | | 7. PG MP-1: EF SCHEDULE NOTE #1 CALLS FOR EF-1 TO BE | | | INTELOCKED WITH LIGHT SWITCH IN BATHROOMS. THIS FAN | | | NEEDS TO RUN WHENEVER RTU-2 IS RUNNING (WHETHER OR NOT | | | LIGHT SWITCH IS ON) AS RECIRCULATION OF AIR FROM THESE | | | SPACES IS PROHIBITED AND ALL AIR SUPPLIED TO THE | | | BATHROOMS SHALL BE EXHAUSTED IN ACCORDANCE WITH FBCM | | | 403.2.1(3). | | | | | | 8. PG MP-1.1: FLOOR PLAN SHOWS A 20X14 SUPPLY DUCT AND | | | AN 18X12 RETURN DUCT, BOTH FROM RTU-5, PENETRATING A | | | 2-HOUR FIRE RESISTANCE RATED WALL. THESE PENETRATIONS | | | ARE REQUIRED TO BE PROTECTED WITH FIRE DAMPERS IN | | | ACCORDANCE WITH FBCM 607.5. SHOW HOW THESE DUCT | | | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH | | | THIS SECTION. THE RATED DUCT PENETRATION DETAIL #6 ON | | | PAGE MP-1.2 IS NOT APPLICABLE AS IT IS RATED FOR 1-HOUR | | | (THE WALL IS 2-HOUR) AND THE SIZES OF THE PENETRATING | | | DUCTS EXCEED THE MAXIMUM ALLOWED IN THE INSTRUCTIONS | | | WHICH ACCOMPANY THE THROUGH-PENETRATION DETAIL. | | | | | | 9. PG MP-1.1: SEVERAL DUCT BRANCHES DO NOT HAVE SIZES | | | SHOWN ON FLOOR PLAN. SOME OF THESE BRANCH SISZES CAN BE | | | DETERMINED BASED ON THE NECK SIZE SHOWN ON THE AIR | | | DISTRIBUTION SCHEDULE BUT SOME CAN NOT. EXAMPLE: PLEASE | | | SHOW ON PLANS THE SIZES OF THE TRANSFER DUCTS AT | | | RESTROOM VESTIBULE 114. PLEASE CHECK PLANS FOR ALL | | | DUCTS WHICH ARE MISSING SIZES ON PLANS AND PROVIDE THE | | | MISSING INFORMATION. AIR DISTRIBUTION SYSTEMS SHALL BE | | | DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED | | | DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1. | | | | | | | | | 10. PG MP-1.2: CURB AND HURRICANE STRAP DETAILS CONTAIN | | | CONFLICTING INFORMATION. PLEASE COORDINATE DETAILS AND | | | CLARIFY THE WIND RESISTANCE METHOD TO BE USED FOR CURB, | | | RTU AND EXHAUST FANS. PROVIDE WIND LOAD CALCULATIONS | | | FOR OVERTURN AND UPLIFT FOR ALL ROOFTOP APPLIANCES FOR | | | BUILDING REVIEW IN ACCORDANCE WITH FBCM 301.13. | | | | | | 11. PG MP-1.2: IN ADDITION TO THE COMMENTS ABOVE, | | | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE | | | EXPOSED TO WIND SHALL BE DESIGNED TO RESIST THE WIND | | | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS | | | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, BUILDING PER FBCM 301.13. PROVIDE SUPPORTING | | | DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING | | | THESE RTU?S AND EXHAUST FANS ARE DESIGNED TO RESIST | | | WIND PRESSURES IN ACCORDANCE WITH THIS SECTION. PLEASE | | | NOTE THAT THIS REQUIREMENT APPLIES TO THE CONSTRUCTION | | | OF THE APPLIANCES THEMSELVES AND NOT JUST THE | | | ATTACHMENT TO THE BUILDING STRUCTURE. | | | | | | 12. PG MP-2.1 CONDENSATE DRAIN DETAIL: AUXILIARY OR | | | SECONDARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE | | | WITH FBCM 307.2.3. A FLOAT SWITCH MAY BE INSTALLED | | | INSIDE THE RTU ON THE PRIMARY DRAIN PAN TO COMPLY WITH | | | THIS SECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-11 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-11 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-22 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-22 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2008-07-22 13:57:11 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET A0 DEMOLITION PLAN, KEYED NOTES #3 STATES | | | "REMOVE EXISTING RESTROOM FIXTURES", HOWEVER SHEET A2 | | | FLOOR PLAN IN WOMENS #111 AND MENS #112 BATHROOM | | | HANDICAP STALLS THE LAVATORIES ARE NOT BEING | | | REINSTALLED. PER FBC-2004 CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE SECTION 11-4.17.3 EXCEPTIONS | | | (1)(2). | | | | | | (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL | | | CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF | | | SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 | | | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL | | | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO | | | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION | | | 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO | | | COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH | | | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED | | | FIXTURE COUNT FOR THE BUILDING. | | | (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN | | | THE CORNER, DIAGONAL TO THE DOOR. | | | | | | 2. SHEET A7 DETAIL 1, ENLARGED RESTROOM: CLEARLY | | | INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING | | | SPACE FOR THE FOLLOWING FIXTURES ON THE DETAIL | | | COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE THE FOLLOWING SECTIONS. | | | A} SECTION 11-4.15.5 CLEARANCES, DRINKING FOUNTAIN | | | (30"X48"). | | | B} SECTION 11-4.16.2 CLEAR FLOOR SPACE, WATER CLOSETS | | | (SEE FIGURE 28). | | | C} SECTION 11-4.18.3 CLEAR FLOOR SPACE, URINALS | | | (30"X48"). | | | D} SECTION 11-4.19.3 CLEAR FLOOR SPACE, LAVATORIES | | | (30"X48" AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH | | | THE LAVATORY). | | | E} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR | | | TURNING SPACE SHALL BE 180-DEGREE WITH A MINIMUM 60" | | | CLEAR FLOOR SPACE. (CLEARLY INDICATE TURNING SPACE IN | | | BATHROOM, BATHROOM ACCESSIBLE STALLS, AND DRINKING | | | FOUNTAIN ROOM) | | | | | | 3. SHEET A7 DETAIL 4, ENLARGED OFFICE/BREAKROON PLAN: | | | CLEARLY INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR | | | TURNING SPACE FOR THE BREAKROOM SINK ON THE DETAIL | | | COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE THE FOLLOWING SECTIONS. | | | A} SECTION 11-4.24.5 CLEAR FLOOR SPACE, SINK (30"X48" | | | AND CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19" | | | UNDERNEATH THE SINK). | | | B} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR | | | TURNING SPACE SHALL BE 180-DEGREE WITH A MAIMUM 60" | | | CLEAR FLOOR SPACE. | | | | | | 4. SHEET MP-1 NOTES LOCATED BELOW PLUMBING FIXTURE | | | SCHEDULE: PLEASE ADD THE FOLLOWING FOR THE HC | | | ACCESSIBLE URINAL COMPLIANT WITH FBC-2004 CHAPTER 11, | | | FLORIDA ACCESSIBILITY CODE SECTION 11-4.18.4 FLUSH | | | CONTROL FOR THE URINAL MAXIMUM 44" A.F.F. | | | | | | 5. SHEET MP-2 DETAIL 3, WATER RISER DIAGRAM: THE 12" | | | AIR CHAMBERS SPECIFIED IN THE DETAIL ARE NOT COMPLIANT | | | WITH THE FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER. | | | PER 604.9, A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK CLOSING VALVES ARE UTILIZED. PLEASE DELETE | | | THE 12" AIR CHAMBERS ON THE RESUBMITTAL. | | | | | | 6. SHEET MP-2 DETAIL 5, WATER HEATER DETAIL: CLEARLY | | | INDICATE THE FOLLOWING ON THE WATER HEATER DETAIL | | | COMPLIANT WITH THE FBC-2004 PLUMBING SECTIONS. | | | A} SECTION 504.4 RELEIF VALVE. | | | B} SECTION 504.5 RELIEF VALVE APPROVAL. | | | C} SECTION 504.6 RELIEF OUTLET WASTE. | | | D} SECTION 504.6.1 DISCHARGE. | | | E} SECTION 607.3 THERMAL EXPANSION CONTROL. | | | | | | 7. ALL MP SHEETS FROM MP-1 THRU MP2.1 REQUIRE A | | | CERTIFICATE OF AUTHORIZATION NUMBER ON THESE SHEETS. | | | PER FAC 61G15-23.002(2). | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-07-22 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-07-22 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2008-07-22 09:27:11 | NOT REQUIRED: NO EXTERIOR WORK FALLING UNDER THE | | | PURVIEW OF ZONING IS PROPOSED. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |