Plan Review Details - Permit 08070127
Plan Review Stops For Permit 08070127
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2009-01-07 Cont ID  
Sent By jwitmer Date 2009-01-07 Time 13:31 Rev Time 0.55
Received By jwitmer Date 2009-01-07 Time 13:31 Sent To PC
Notes
2009-01-07 13:33:56BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY
 CONT: ALLIANCE
 TEL: (561)818-7777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW SKETCH# 5& 6
 8X11 & 11X17
 ACTION: REVIWED
 2 HR RATED VESTIBULE ASSEMBLY
  
 VESTIBULE IS PART OF A 2HR RATED STAIRWELL ENCLOSURE
 AND TO COMPLY WITH 1019.1. ( ALTERNATE MEANS AND
 MATERIALS)
 REVIEWED BY ITERUM B.O. ROBERT BROWN
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2009-01-04 Cont ID  
Sent By jwitmer Date 2009-01-04 Time 08:49 Rev Time 0.50
Received By jwitmer Date 2009-01-04 Time 08:49 Sent To  
Notes
2009-01-04 09:15:42IMPROV CITY PLACE
 BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY AVE SUITE# 250
 CONT: ALLIANCE CONTRACTING
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW #8 1/2" X 11" FILLING OF TRASH CHUTE
 OPENING
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD ARCHITECT JORDON SOPOURN DOES
 NOT INDICATE ANY TRASH CHUTE OPENINGS ON THE FLOOR
 PLANS A120.1-A120.4, PLEASE PROVIDE LOCATION AND SIZE
 OF OPENING. THE OTHER ISSUE
 IS THE 8 1/2" X 11" DETAIL HAS NOT BEEN REVIEWED BY THE
 DESIGNER OF RECORD.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 2) 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, IF PRACTICING AS A DULY AUTHORIZED ENGINEERING
 BUSINESS THERE NAME AND LICENSE NUMBER OF THE ENGINEER
 AND THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS THROUGH WHICH THE
 ENGINEER IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2009-01-04 Cont ID  
Sent By jwitmer Date 2009-01-04 Time 08:22 Rev Time 0.50
Received By jwitmer Date 2009-01-04 Time 08:22 Sent To  
Notes
2009-01-04 08:48:48BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY AVE SUITE# 250
 CONT: ALLIANCE CONTRACTING
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW # 4 SHEET A130.4
 ACTION: DENIED
  
 1) SHEET A130.4 INDICATES A NEW BAR AND NEW ROLL DOWN
 DOOR BY OVERHEAD DOOR CO. THE CONTRACTOR HAS NOT
 SUBMITTED ANY PRODUCT APPROVAL FOR THIS OPENING, PLEASE
 SEE REQUIREMENTS FOR NEW DOOR REVIEW. FL BLD CODE
 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS: ROLL DOWN DOOR
 BY OVERHEAD DOOR CO.
  
 1A) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
  
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 1B) 1609. 6.2.2 COMPONENTS AND CLADDING.
  
 1C) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 1D) ( IF APPLICABLE) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 1E) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-04 Cont ID  
Sent By jwitmer Date 2009-01-04 Time 07:57 Rev Time 1.50
Received By jwitmer Date 2009-01-04 Time 07:08 Sent To  
Notes
2009-01-04 08:22:00REVISION # 4 DATED 12-01-2008
 SHEETS REVIEWED: OK
 A120.2, A120.4, A130.2, A180.1, A180.4 & A500.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 09:58 Rev Time 0.77
Received By jwitmer Date 2009-01-02 Time 09:58 Sent To PC
Notes
2009-01-02 10:16:29BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY
 CONT: ALLIANCE
 TEL: (561)818-7777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW DATED DEC. 5/2008
 8X11
 ACTION: DENIED
 2 HR RATED VESTIBULE ASSEMBLY
  
 1) 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLANS FAIL
 TO INDICATE THE LOCATION OF THIS VESTIBULE. SPOKE WITH
 ARCHITECT JORY SOPOURN III ABOUT THIS REVISION, AND
 WHAT WILL BE REQUIRED
 FOR THE CITY TO ACCEPT THE DETAIL UNDER SECTION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 AND EQUIPMENT, APPROVED BY THE INTERUM BUILDING
 OFFICIAL ROBERT BROWN.
  
 A) PROVIDE ADDITIONAL INFORMATION WHEREAS WHERE EACH OF
 THE AREAS ON THE PLAN IS LOCATED, STAIRWELL, ABOVE
 CEILING AND OR IMPROV TENANT SPACE.
  
 B) PROVIDE A FULL HEIGHT DETAIL WITH CEILING OR DECK
 ABOVE TO TENANT FLOOR SPACE, INDICATE CEILING LEVEL,
 UNDERSTOOD THAT THE DRYWALL OF THE ENCLOSURE DOES NOT
 EXTEND TO DECK ABOVE, THAT IS THE REASON FOR THE 2 HR
 RATED CEILING WITHIN THE VESSTIBULE, NO FUEL LOADS TO
 BE ABOVE THE RATED CEILING!
  
 C) PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF THE
 REVISON FOR CLARIFICATION.
  
 VESTIBULE IS PART OF A 2HR RATED STAIRWELL ENCLOSURE
 AND TO COMPLY WITH 1019.1. ( ALTERNATE MEANS AND
 MATERIALS)
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 14:14 Rev Time 0.77
Received By jwitmer Date 2008-11-12 Time 14:14 Sent To  
Notes
2008-11-12 14:16:37REVISION:
 SK-1 BAR JOIST- DETAILS AT POINT LOADING
 SK-2 MASONARY OPENING DETAIL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-07 Cont ID  
Sent By jwitmer Date 2008-10-07 Time 10:42 Rev Time 2.22
Received By jwitmer Date 2008-10-07 Time 10:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-26 Cont ID  
Sent By jwitmer Date 2008-09-26 Time 14:02 Rev Time 2.22
Received By jwitmer Date 2008-09-26 Time 14:01 Sent To  
Notes
2008-09-26 14:15:14 
 BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY # 250
 CONT: ALLIANCE
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:REVIEWED
  
  
  
 BUILDING PROVISOS:
 1) NEEDS NOC TO BE RECORDED BEFORE FIRST INSPECTION
  
 2) THIRD SET OF PLANS ARE REQUIRED FOR THE THRESHOLD
 INSPECTOR WILL BE IN THE BUILDING DEPARTMENT
 MONDAY 9-28-08 FOR REVIEW AND STAMPING
  
 3) THRESHOLD BUILDING MEETING WITH KEN CONRAD THE
 THRESHOLD ENGINEER & INSPECTOR
 WILL TAKE PLACE MONDAY 9-29-08
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By jwitmer Date 2008-09-10 Time 09:30 Rev Time 1.66
Received By jwitmer Date 2008-09-10 Time 09:30 Sent To  
Notes
2008-09-10 09:37:55BUILDING REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY # 250
 CONT: ALLIANCE
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPT. 10,2008
  
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT (3) OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT
 CONSIDERED A THRESHOLD BUILDING REQUIRING A THRESHOLD
 INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS
 WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) SECOND REQUEST, THRESHOLD INSPECTION PLAN FL S. S.
 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 2A) SECOND REQUEST, 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) SECOND REQUEST, THRESHOLD INSPECTOR WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 JERALD SMITH MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561)805-6667 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED. THE THRESHOLD INSPECTOR FORMS ARE
 STILL ATTACHED TO THE FIRST ROUND OF BUILDING COMMENTS.
  
 2C) SECOND REQUEST, I COULD NOT LOCATE THE REQUIRED FL
 S S 633 STATEMENT, IT USUALLY IS LOCATED IN EITHER THE
 COVER PAGE WITH GENERAL INFORMATION OR PROJECT
 INFORMATION OR ON THE LIFE SAFETY SHEET A120.1.
 THRESHOLD BUILSING, REQUIRED STATEMENT, W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By jwitmer Date 2008-07-23 Time 07:12 Rev Time 6.50
Received By jwitmer Date 2008-07-23 Time 07:12 Sent To  
Notes
2008-07-23 07:18:39BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY # 250
 CONT: ALLIANCE
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 105.13.1
 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR
 TO PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPECTION PLAN
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B)THRESHOLD INSPECTOR
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT JERALD SMITH MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6667 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BUILSING, REQUIRED STATEMENT,
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3) NOTE ISSUED PERMIT NUMBER 08060710 WILL ALSO NEED TO
 MEET THE REQUIREMENTS FOR THRESHOLD BUILDINGS LISTED IN
 COMMENT # 2A-2C. FL S. S. 553.71(7) .
  
 4) LIFE SAFETY PLAN A120.1 IN THE PLAN NOTES AND IN THE
 REQUIRED EGRESS WIDTHS ( 0.3 STAIRS AND 0.2 HORIZONTAL
 AREAS) DOES NOT INDICATE THAT SMOKE CONTROLLED SEATING
 HAS BEEN ACHIEVED AND THE CALCULATIONS ARE BASED ON
 SMOKE CONTROLLED SEATING SEE 1024.6.1. PLEASE PROVIDE
 EITHER COMPLIANCE WITH ALL THE REQUIREMENTS OF 1024.6.2
 OR INDICATE THE FACTORS IN 1024.6.1 FOR RAMPS AND
 STAIRS.
 NOTE A300.1 THE HIGHEST RAISED FLOOR SECTION APPEARS TO
 ONLY BE 14'-0" TO THE CORRUGATED ROOF DECK NOT MEETING
 THE REQUIREMENT OF 1024.6..2.2.
  
 5) LIFE SAFETY PLAN A120.1 & A130.2 THE MAIN ENTRY
 DOOR# 8 INTO THE SHOW ROOM SWING IN THE WRONG
 DIRECTION, PLEASE SEE 1024.2 & 1008.1.2.
 1024.2 EVERY ASSEMBLY OCCUPANCY SHALL BE PROVIDED WITH
 A MAIN ENTRANCE/EXIT. THE MINIMUM AGGREGATE WIDTH OF
 THE MAIN ENTRANCE FOR GROUP A OCCUPANCIES SHALL BE
 SUFFICIENT TO ACCOMMODATE 50 PERCENT OF THE OCCUPANT
 LOAD AND SHALL BE AT THE LEVEL OF EXIT DISCHARGE OR
 SHALL CONNECT TO A STAIRWAY OR RAMP LEADING TO A
 STREET. EACH LEVEL OF A GROUP A OCCUPANCY SHALL HAVE
 ACCESS TO A MAIN EXIT AND SUCH ACCESS SHALL HAVE
 SUFFICIENT CAPACITY TO ACCOMMODATE 50 PERCENT OF THE
 OCCUPANT LOAD OF SUCH LEVELS. WHERE THE MAIN EXIT FROM
 AN ASSEMBLY OCCUPANCY IS THROUGH A LOBBY OR FOYER, THE
 AGGREGATE CAPACITY OF ALL EXITS FROM THE LOBBY OR FOYER
 SHALL BE PERMITTED TO PROVIDE THE REQUIRED CAPACITY OF
 THE MAIN EXIT REGARDLESS OF WHETHER ALL SUCH EXITS
 SERVE AS ENTRANCES TO THE BUILDING.
  
 1008.1.2 EGRESS DOORS SHALL BE SIDE SWINGING. DOORS
 SHALL BE SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  
 6) WHILE THE FRONT ENTRY DOORS 1,2 & 3 WILL TAKE 50% OF
 THE OCCUPANT LOAD THE OTHER 50% OF THE OCCUPANT LOAD
 WILL NEED TO BE TAKEN THROUGH THE OTHER DESIGNATED
 EXITS, NO OF THE UNKNOWNS IS AT THE EXIT DOOR# 4 THERE
 IS A COVERED PATIO AREA BUT IS NOT CLEAR AS TO WHAT THE
 DOUBLE HASHED LINE INDICATES IS THIS A FENCED IN AREA
 OR IS THIS OPEN FOR THE OCCUPANTS CAN DISPERSE ONCE
 THEY ARE THROUGH DOOR # 4.
 IF THIS IS A FENCED IN AREA THEN BOTH DOORS 4& 5 OR
 12'-0" OF DOOR OPENING ARE EXITING A 5'-0" AREA, PLEASE
 CLARIFY THIS AREA. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. 1004.5 EGRESS CONVERGENCE.
  
 7) LS A120.1 & A130.2 & A130.3 EXIT HALLWAY
 CONVERGENCE, THE EXIT CORRIDOR THAT BACKS UP TO THE
 SHOW ROOM IS 5'-5 1/2" WIDE AND OPENS UP TO 10'-4 PLUS
 STAIRS FROM THE UPPER SHOWROOM SEATING AREA. THE
 CAPACITY OF THE HALLWAY IS 620 OCCUPANTS BUT DROPS TO
 170 OCCUPANTS AT DOOR # 5. DOOR # 6 AGAIN SWINGS THE
 WRONG WAY TO BE CONSIDERED AN EGRESS DOOR,1008.1.2.
 EVEN WITH BOTH DOORS SWINGING IN THE DIRECTION OF
 TRAVEL YOU WOULD ONLY BE ALLOWED 340 OCCUPANTS THROUGH
 CREATING A CONVERGENCE ( BOTTLE NECKING EFFECT).
 1004.5.
  
 8) LS A120.1 FROM DOORWAY# 5 THROUGH THE CORRIDOR THAT
 LEADS TO THE LOBBY OR VESTIBULE AREA DOES NOT HAVE
 EXIT/ EMERGENCY LIGHT WITH BATTERY BACK UP.
  
 9) LS A120 VESTIBULE IS CURRENTLY SET UP AS A WAITING
 AREA FOR THE NEXT SHOW AND NO EXIT PATH IS PROVIDED FOR
 THE EXITING PATTRENS. CURRENTLY THIS AREA WILL HOLD
 OVER 100 OCCUPANTS REQUIRING TWO EXITS AND OVER 1/3RD
 THE DISTANCE APART. SEE TABLE 1014.1. PLEASE REVISE
 SHOWING THE DOORS FROM THE SHOW ROOM REVERSED AS AN
 EXIT (COMMENT# 5) . INDICATE THE EGRESS PATH FROM THE
 SHOW ROOM AND HOW
 CROWD CONTROL WILL BE ESTABLISHED FOR THOUGHS EXITING
 AND FOR THE PATTRENS WAITNG FOR THE NEXT SHOW.
  
 10) SHEET A500.1 DOOR SCHEDULE EGRESS DOORS THAT ARE
 MISSING PUSH BAR PANIC DEVICE HARDWARE, DOOR 8 WHEN
 REVERSE, DOOR 6 WHEN REVERSED, DOOR 5,17, 23 & 26.
 1008.1.9
 ASSEMBLY OCCUPANCY WHEN LOADS OF 100 OR MORE
 OCCUPANTS.
  
 11) SHEET A 130.2 IN THE UPPER RIGHT SECTION OF THE
 PLAN AND LOWER RIGHT SECTION OF THE PLAN THERE IS A SET
 OF STAIRS WHERE THE HANDRAIL DOES NOT FOLLOW THE DECENT
 PAST THE LAST RISER BUT MAKES A TURN
 IMMEDIATELY, PLANS CALL FOR A DETAIL 5 / A400.3 THE
 DETAIL IS BLANK. 11-4.9.4(2) AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL. THE PLANS
 INDICATE THE LAST RISER IN LINE WITH THE WALL NOT
 ALLOWING THE NOT ALLOWING THE SLOPE TO CONTINUE IN A
 STRAIGHT LINE.
  
 12) LS A120.1 THE RAMP AT THE TOP OF THE SHEET FAILS TO
 HAVE 6'-0" CLEARENCE AT THE BOTTOM LANDING.
 11-4.8.4(2).
  
 13) SHEET A130.2 DETAIL INDICATES 3STAIR DETAILS 4, 5&6
 A400.3 PLEASE CORRECT, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, WRONG DETAILS.
  
 14) SHEET A 130.3 OFFICE BOTTOM OF RAMP DOES NOT HAVE A
 6'-0" CLEAR BOTTOM RAMP. SEE 11-4.8.4(2).
  
 15) SHEET A 130.3 TICKET OFFICE AT DOOR # 4 THE FIRE
 EXTINGUISHER IS HIDDEN BEHIND THE DOOR WHEN OPENED. NO
 CODE SECTION JUST A BAD LOCATION IF NOT VISIBLE.
  
 16) LS A120 PLAN FAILS TO INDICATE COMPLIANCE WITH
 PLACEMENT OF WHEELCHAIR LOCATIONS. 11-4.33.3.
  
 17) LS A120 INDICATE COMPLIANCE WITH 11-4.33.6
 PLACEMENT OF LISTENING SYSTEMS.
  
 18) LS A120 SHOW COMPLIANCE WITH 11-4.32.1-2.
  
 19) A140.5 PLEASE PROVIDE SQ FT OF ROOM AND OF THE
 RAISED PLATFORM AREA, 410.4.
  
 20) A140.1 FLOOR FINISHES PLEASE PROVIDE CARPET
 DOCUMENTATION WITH COMPLIANCE OF SECTION 804.5.1 ,
 CLASS II FOR THE ASSEMBLY OCCUPANCY.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-04-23 Cont ID  
Sent By dwise Date 2009-04-23 Time 20:59 Rev Time 0.00
Received By dwise Date 2009-04-23 Time 20:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-03-29 Cont ID  
Sent By dpalmer Date 2009-03-29 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2009-03-29 Time 08:37 Sent To PC
Notes
2009-03-29 09:57:22** DENIED REVIEW **
  
 *** DENIED REVISIONS***
  
 1) NOTE: AS GIVEN ON ORIGINAL PROVISO AND IN PREVIOUS
 NOTES, PLEASE REVISE PLANS TO CONFORM TO THE MINIMUM
 CODES FOR LIGHTING CONTROLS IN FBC 13-415.1.ABC.1.1,
 .1.2 AND .1.3. EXAMPLES WERE GIVEN ON PREVIOUS REVIEWS
 HOWEVER PLANS STILL DO NOT SHOW ITEMS NEEDED.
  
 A) IN THE PREVIOUS REVIEW COMMENTS WERE GIVEN WITH
 RESPECT TO THE BATHROOMS. THESE NOW SHOW *SINGLE POLE*
 SWITCHES AS THE SEPARATE SPACE CONTROL AND OVER RIDES
 TO THE LIGHTING CONTROL PANEL WHICH THESE LIGHTS ARE
 CIRCUITED.
 THE FIRST ITEM IS THAT ALL THE LIGHTING SHALL BE TURNED
 OFF ON THIS BUILDING AUTOMATICALLY. ALL SEPARATE SPACES
 SHALL HAVE CONTROLS EITHER OF THE FOLLOWING: A DEVICE
 WHICH OVER RIDES THE SCHEDULED SYSTEM OR AUTOMATED
 SINGLE CONTROLS FOR SUCH SPACE. ( AN EXAMPLE WOULD BE
 OCCUPANCY SENSORS). IN EITHER CASE THESE DEVICES MUST
 BE AUTOMATED.
 SEE SECTIONS ABOVE.
  
 B) ANOTHER AREA IS WHEN ENTERING THROUGH THE FRONT DOOR
 TO SEPARATE BAR SEATING AREA THERE IS NO OVER RIDE
 CONTROLS OR A OCCUPANCY SENSOR WHICH RIDES THE TIME OF
 DAY SCHEDULING.
 SEE SECTIONS ABOVE.
  
 C) LIGHTING CIRCUITS/RELAY NUMBERS ON RPA OR ANY OTHER
 PANEL HAVE NOT ALL BEEN UPDATED. WHERE IS E-3, 5 ETC
 THE NOTES MENTIONS TO DIMMING CONTROL POWER BOOSTER
 PANEL HOWEVER THE NOTES FOR CONNECTION OF POWER BOOSTER
 PANEL TO THE PANEL RPA ARE NOT COMPLETE.
 THERE IS NO INDICATION FOR CIRCUITING IN RPA OF MANY OF
 THESE CIRCUITS UNDER THE CONTROL OF THE LIGHTING
 CONTROL PANEL.
  
 ** ONCE AGAIN AS REQUESTED ON PROVISO ON 9/24/08,
 PROVIDE COMPLETE FUNCTIONALITY OF SYSTEM.
 PLEASE BE SURE TO ALSO SEE FBC 1006.1.2, NFPA-101
 7.8.1.2.2 FOR CONTROLS FOR *MINIMUM* LIFE SAFETY.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 UPDATING ALL LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE SAME EXAMPLE GIVEN IS RESTROOM LIGHTING. THESE
 NEEDS TO BE INCLUDED IN CALCULATIONS BASED ON THE FACT
 NEW FIXTURES ARE SHOWN. IN OTHER BATHROOMS NO
 INFORMATION ON FIXTURES ARE SHOWN YET THESE ARE FIGURED
 INTO CALCULATIONS.
 PLEASE SEE SHEET E2.2 FOR EXAMPLE: THE LARGE RESTROOMS
 DO NOT INCLUDE ANY FIXTURE INFORMATION. THIS IS THE
 SAME FOR THE SMALLER LOCATIONS ALSO.
  
 3) NOTE: AS GIVEN ON PREVIOUS REVIEW. PLEASE UPDATE ALL
 CIRCUITING ON ALL PANELS WITH PLANS. PLEASE SEE E PANEL
 CIRCUIT #12, NOTED AS BILLIARD ROOM. THIS ROOM NO
 LONGER EXISTS.
 408.4
 ** THIS IS ONLY ONE EXAMPLE; THERE ARE OTHERS. ALL
 CIRCUITS NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN
 WHICH THEY FEED.
  
 4) NOTE: AS NOTED ON PREVIOUS REVIEW: PLEASE UPDATE ALL
 LOAD CALCULATIONS. ONE EXAMPLE WAS GIVEN THAT NOT ALL
 LOADS ON PANELS WERE UPDATE AND CARRIED THROUGH.
 AN EXAMPLE: PANEL *B* PHASE A AND OTHER PHASES ALSO.
 PLEASE GO OVER ALL LOADS ON ALL PANELS AND UPDATE ALL.
 THIS IS ONE EXAMPLE GIVEN AS A BENEFIT.
 220, 220.12,220.14,220.42,220.44 ETC
 215.3, 230.42
  
 5) NOTE: ONE SET OF PLANS IS BEING RETAINED BY THIS
 OFFICE. ONLY TWO SETS WILL BE GIVEN BACK.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-01-02 Cont ID  
Sent By dpalmer Date 2009-01-02 Time 18:54 Rev Time 2.00
Received By dpalmer Date 2009-01-02 Time 18:54 Sent To  
Notes
2009-01-02 18:55:06** DENIED REVIEW OF REVISIONS **
  
 1) NOTE: PLEASE LABEL ALL REVISIONS ON PLANS WITH
 CLOUDS WITH REVISION NUMBER IDENTIFICATION AS NOTED IN
 TITLE BLOCKS. THERE HAVE BEEN TWO SETS OF REVISIONS
 MADE HOWEVER UNTIL NOW NO REVISIONS WERE SUBMITTED FOR
 REVIEW. THE NUMERICAL DESIGNATION IS ON PLANS HOWEVER
 THE REVISED ITEMS HAVE NOT BE IDENTIFIED.
 FBC 106.5, 106.1.1, NEC 2005, FBC 2005 FOR CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION NEEDED.
  
 2) NOTE: PLEASE SEE PROVISO ISSUED IN SEPTEMBER OF
 2008. NO REVISED ELECTRICAL PLANS HAVE COME INTO THIS
 OFFICE GIVING THE FUNCTIONALITY OF THE TENANT SPACE
 LIGHTING CONTROL SYSTEM IN ORDER TO VERIFY NOT ONLY
 LIGHTING CONTROL COMPLIANCE PER FBC CHAPTER 13 BUT ALSO
 THE LIGHTING FOR EGRESS UNDER NORMAL, EMERGENCY AND
 SHOW CONDITIONS.
 THIS WAS A REQUEST OF DESIGNER SO THE SYSTEM COULD BE
 WORKED OUT.
 THE PROJECT IS NOW REQUESTING A TCO AND ONLY SOME ITEMS
 HAVE BEEN REVISED ON PLANS. SOME ITEMS ON PLANS ARE NOT
 COMPLETE AND THE COMMENTS FROM PREVIOUS PROVISO IS
 STILL IN NEED OF ADDRESSING.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3. LS 101 7.8, 7.9, FBC
 1006.1
  
 A) PLEASE SEE THERE ARE LIGHTING FIXTURES ON PLANS
 WHICH HAVE BEEN REVISED WHICH NOW DO NOT INDICATE ANY
 CIRCUITING OR CONTROLS. SEE RECESSED FIXTURES AND
 SCONCES AT ENTRANCE INTO CLUB AREA AS ONE EXAMPLE.
  
 B) PLEASE SEE CIRCUITING ON THE LIGHTING CONTROL PANEL
 SHALL BE UPDATED FOR ALL ALONG WITH PANEL SCHEDULES.
 ONE EXAMPLE OF COORDINATION IS THE BILLIARD ROOM WHICH
 IS STILL SHOWN AS CIRCUIT #12 ON THE RPA PANEL YET
 THERE IS NO LONGER A BILLIARD ROOM.
 THIS IS ONLY ONE.
  
 C) NOTE: PLEASE SEE AREAS SUCH AS THE LARGE MULTI-GANG
 BATHS WHICH DO NOT COMPLY WITH SEPARATE SPACE CONTROL
 EVEN THOUGH THEY ARE WIRED TO THE LIGHTING CONTROL
 PANEL. PLEASE SEE 13-415.1.ABC.1.2. THIS MUST HAVE
 SEPARATE CONTROL.
 PLEASE SEE OTHER SMALLER BATHS WHICH INDICATE MOTION
 SENSORS HOWEVER VERIFY THESE AS DUAL TECHNOLOGY IN
 ORDER TO MEET THE LIFE SAFETY CODE FOR OCCUPANTS IN ANY
 STALL AREAS.
  
 D) PLEASE REVISE ALL PHOTO-METRICS FOR NORMAL, AND SHOW
 TIMES. AT THE REQUEST OF THE DESIGNER THIS WAS GOING TO
 BE MEASURE AND SHOWN ONCE INSTALLED. IT WAS KNOWN TO
 BOTH THE ARCHITECT AND KAMM CONSULTING THAT IF THE
 STAIR LEVEL LIGHTING AND OTHER AREAS DID NOT MEET THE
 MINIMUM IN THE LIFE SAFETY CODE THAT FIXTURES MAY NEED
 TO BE ADDED. THIS NEEDS TO BE CONFIRMED AND SHOWN.
 RECORD PLANS NEED TO SHOW THIS. A FIELD INSPECTION MAY
 ALSO BE NEEDED.
  
 ** THE PROVISO WAS GRANTED IN ORDER TO PERMIT THE
 PROJECT AND TO GET EVERYTHING STARTED. THE PROVISO IS
 GIVEN TO GIVE THE CONTRACTOR AND THE DESIGN TEAM THE
 OPPORTUNITY TO OBTAIN INFORMATION ETC AND REVISE PLANS.
 IN THE MEETING HELD BEFORE PERMIT ISSUANCE THIS
 REVIEWER SPECIFICALLY MENTION REVISED PLANS NEEDED TO
 BE SUBMITTED IN PLENTY OF TIME WITH ALL INFORMATION
 BEFORE FINAL INSPECTIONS WERE BEING SCHEDULED.
 SUBMITTING THE PLANS THE WEEK BEFORE NEEDED FINALS IS
 NOT ENOUGH TIME TO DO REVIEWS, ADDRESS ANY POSSIBLE
 COMMENTS AND FOR PLANS TO BE ON THE SITE FOR
 INSPECTIONS.
  
  
 3) NOTE: PREVIOUS PLANS CLEARLY INDICATE THE EXISTING
 TRANSFORMER TEA AS GROUND MOUNTED, NOW THE POWER PLANS
 INDICATES THIS AS ABOVE. TRANSFORMERS OVER 50KVA ARE
 NOT PERMITTED ABOVE THE CEILING. PLEASE EXPLAIN WHAT IS
 MEANT BY *ABOVE* AS STATED ON PLANS.
 PLEASE SEE 450.13 AS THE LOCATION NEEDS TO BE VERIFIED
 MEETING CODE COMPLIANCE.
  
 4) NOTE: LOADS ON PANELS AND EQUIPMENT ALONG WITH
 CIRCUITING HAS BEEN REVISED HOWEVER NOT ALL LOADS ETC
 HAVE BEEN CARRIED THROUGH. ONE EXAMPLE IS PANEL K1
 WHICH HAS A SUBSTANTIALLY INCREASED LOAD WHICH AFFECTS
 H1A YET THE LOAD ON THE MAIN SERVICE LOAD CALCULATIONS
 HAS NOT BEEN REVISED. THE PLANS IN FACT SHOW THE SAME
 LOADS AS NOTED ON ORIGINAL PERMITTED PLANS.
  
 5) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS NEED TO
 BE UPDATED WITH ALL LIGHTING IF ALLOWANCES FOR ALL
 LIGHTING IS GOING TO BE USED. AN EXAMPLE OF THIS IS THE
 ALLOWANCE BEING FIGURED FOR RESTROOMS YET NO FIXTURES
 WITH ANY INFORMATION IS ON PLANS. MAY NOT USE THE SQ FT
 WITHOUT INCLUDING ALL LIGHTS. AS THESE SUPPOSEDLY ARE
 EXISTING TO REMAIN PLEASE REMOVE. IF THESE ARE NEW,
 THEN REVISED ALL INFORMATION FOR FIXTURES ETC
 13-415.2.ABC.1.1,.1.2.
 ALL SPECIFIC FIXTURES NEED TO BE LISTED WITH
 MANUFACTURE AND MODEL NUMBER ETC. THE VERIFICATION OF
 LIGHTING COMPLIANCE CAN NOT BE CONFIRMED.
 PLEASE KEEP IN MIND ALL WATTAGE USED FOR CALCULATIONS
 SHALL BE BASED ON THE RATING OF FIXTURE NOT THE FIXTURE
 BULB RATING.
 ALL FIXTURES SHALL CONTAIN A LISTING FROM A NRTL.110.3
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 13:32 Sent To PC
Notes
2008-12-01 13:32:52 
 ** FAILED REVISION**
  
  
 1) NOTE: PLEASE SUBMIT COORDINATING PLANS FOR REFLECTED
 CEILING WITH RESPECT TO LIGHTING AND AREAS.
 FOR EXAMPLE: SHEETS A180.1 AND OTHERS IN ARCHITECTURAL
 SET WHICH WERE JUST RECENTLY REVISED DO NOT CONTAIN
 MANY OF THE SAME LIGHTING FIXTURES WHICH ARE ON THE
 ELECTRICAL PLANS.
 PLEASE SEE AREAS SUCH AS THE * SEATING AREA* OUTSIDE
 THE RESTROOMS WHICH ON ELECTRICAL PLANS IS SHOWN AS A *
 PRIVATE BILLIARD ROOM*.
  
 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE
 CALCULATIONS. PLEASE EXPLAIN HOW THE LIGHTING DESIGN
 WATTAGE HAS GONE DOWN FROM PERMITTED PLANS WHEN
 FIXTURES SUCH AS THE *E* FIXTURE HAS ACTUALLY INCREASED
 IN THE WATTAGE. IN FACT FIXTURE *E* HAS MORE THAN
 DOUBLED IN THE WATTAGE ON THE FIXTURE LEGEND.
 PLEASE BE SURE TO COORDINATE ALL.
 13-415.2,13-415.2.ABC.1.1,1.2.
  
 3) NOTE: PLEASE SEE * PROVISO* FROM PERMIT ISSUANCE.
 PLEASE SUBMIT INFORMATION AND DOCUMENTATION FOR
 FUNCTIONALITY OF LIGHTING CONTROL SYSTEM AND SEQUENCE
 OF OPERATION.
 13-415.1.ABC.1.1,.1.2 AND.1.3.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 14:39 Sent To  
Notes
2008-11-24 14:40:42ELECTRICAL REVISIONS SUBMITTED UNDER STRUCTURAL PERMIT
 ALONG WITH MECHANICAL REVISIONS HAVE BEEN ROUTED TO
 ADRIANNA MCKENZIE. PLANS SUBMITTED UNDER INORRECT
 PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2008-09-24 Time 16:58 Sent To  
Notes
2008-09-24 16:58:12 
 ** PROVISO/REDLINED **
  
 1) NOTE: SYSTEM FUNCTIONS FOR LIGHTING CONTROLS AND
 EGRESS LIGHTING SHALL BE VERIFIED FOR MEETING LIFE
 SAFETY CODE 7.8.1.2.2, 7.8.1.3 7.9.1 AND FBC
 1006.1.2.THE SYSTEM OPERATION FOR LIFE SAFETY EGRESS
 UNDER NORMAL AND EMERGENCY CONDITIONS WILL BE FIELD
 INSPECTED AND FINAL PLANS SHALL PROVIDE A DETAILED
 SEQUENCE OF OPERATION.
 THIS OFFICE MAY FIELD INSPECT SYSTEM FOR FUNCTIONALITY
 MEETING THE FBC CHAPTER 13, 11, 10 AND LS 101 7.8, 7.9.
  
 2) NOTE: AS OF REVIEW SHEETS FA.01 AND 2.1 ARE MISSING
 FROM ONE SET. NEED TO BRING IN BEFORE FIRE REVIEW AND
 PLACE IN SETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 15:24 Sent To  
Notes
2008-09-12 15:25:10 
  
  
  
 ** DENIED 2ND REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS DO NOT MEET
 SECTIONS OF THE CODES GIVEN ON PREVIOUS REVIEW. SOME
 SPECIFIC EXAMPLES WILL BE GIVEN BELOW.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
  
 FOR EXAMPLE: PLANS INDICATE LIGHTING CONTROL CIRCUIT
 E-38 WHICH BY NOTES TAKE THIS BACK TO THE LIGHTING
 CONTROL PANEL *RPA*. BASED ON THE ONLY TWO SWITCH BANKS
 NOTED, THIS IS NOT PART OF EITHER SWITCH BANK.
  
 FOR EXAMPLE: PLEASE SEE CIRCUITS E-30 AND E20 WHICH ARE
 SHOWN TO EXIT/EGRESS HALLWAYS. WHERE ARE THE SEPARATE
 CONTROLS REQUIRED?
 ** PLEASE BE SURE TO SEE COMMENTS BELOW WITH RESPECT TO
 LIFE SAFETY NFPA-101.
  
 FOR EXAMPLE: PLEASE SHOW WHERE AND HOW AREAS AS NOTED
 ABOVE FOR SEPARATE CONTROLS MEET SECTIONS. THE OCCUPANT
 IS REQUIRED TO SEE *ALL* LIGHTING WHICH IS BEING
 CONTROLLED OR MEET THE EXCEPTIONS IN THE CODE. THE
 PLANS DO NOT SHOW THIS.
  
  
 ** THIS IS ONLY A COUPLE OF EXAMPLES. THIS IS GIVEN AS
 A BENEFIT ONLY AND IS NOT ALL ITEMS WHICH NEED TO BE
 ADDRESSED WITH RESPECT LIGHTING CONTROLS.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.2.1,
 13-415.2.ABC .2.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS. PLEASE BE SURE TO SEE THE CODE SECTIONS
 AS GIVEN AND PLEASE COORDINATE ALL LIGHTING ON THE
 FIXTURE LEGEND AND THE CALCULATIONS.
  
 ONE EXAMPLE: PLEASE SEE FIXTURE *J* WHICH INDICATES
 THIS ON THE LIGHTING PERFORMANCE CALCULATIONS AS A
 35WATT FIXTURE HOWEVER SEE SHEET E0.1 WHICH INDICATES
 THIS SAME FIXTURE AS 150WATT.
  
 ** THIS WAS ONLY ONE EXAMPLE: PLEASE COORDINATE *ALL*
 FIXTURES, THE NUMBER OF FIXTURES, THE TYPES OF
 FIXTURES, THE COUNT ETC.
  
 3) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101
 7.8.1.2.2. BASED ON PLANS AND NOTES ABOVE THE LIGHTING
 IN EGRESS/EXIT HALLWAYS ARE BEING SHOWN ON THE LIGHTING
 CONTROL PANEL *RPA* WHICH IS OK, HOWEVER IF THIS
 LIGHTING CONTROL PANEL OR THE OVER RIDES SHOWN TURN OFF
 THE LIGHTING AT ANY POINT, THESE AREAS ARE LEFT IN
 TOTAL DARKNESS WITH NO OVER RIDE DEVICES SUCH AS FAIL
 SAFE OCCUPANCY SENSORS ETC.
 THIS IS A MAJOR LIFE SAFETY ISSUE AND BASED ON THE
 CODE(S) THE METHOD OF CONTROLS IN THESE AREAS AND ANY
 EGRESS AREA NEEDS TO BE RE-=CONSIDERED IN DESIGN.
 PLEASE BE SURE TO SEE THE NEXT COMMENT.
  
 4) NOTE: PLEASE SEE TYPE *M* FOR EXAMPLE: THE FIXTURE
 LEGEND INDICATES THIS FIXTURE IS TO BE SELECTED HOWEVER
 BASED ON THIS FIXTURE BEING LOCATED IN MANY EGRESS
 PATHS OR CORRIDORS.
 AS THIS FIXTURE SIMPLY NOTES TO SEE ARCHITECTURAL FOR
 HEIGHTS AND THE SPECIFIC FIXTURE IS NOT CALLED OUT
 PLEASE KNOW A SPECIFIC FIXTURE IS REQUIRED TO BE SHOWN
 MEETING CODE COMPLIANCE ALONG WITH HEIGHTS/LOCATIONS
 ETC TO MEET FBC 11.4.4.1
  
 11-4.4.1 GENERAL.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 8(A)]. OBJECTS MOUNTED WITH THEIR LEADING EDGES
 AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED FLOOR
 MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8(A) AND FIGURE
 8(B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS
 MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO
 80 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR
 FINISHED FLOOR [SEE FIGURE 8(C) AND FIGURE 8(D)].
 PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF
 AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE
 8(E)].
 11-4.4.2 HEADROOM. WALKS, HALLS, CORRIDORS,
 PASSAGEWAYS, AISLES, OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES (2030 MM) MINIMUM CLEAR HEAD ROOM [SEE
 FIGURE 8(A)]. IF VERTICAL CLEARANCE OF AN AREA
 ADJOINING AN ACCESSIBLE ROUTE IS REDUCED TO LESS THAN
 80 INCHES (2032 MM) (NOMINAL DIMENSION), A BARRIER TO
 WARN BLIND OR VISUALLY-IMPAIRED PERSONS SHALL BE
 PROVIDED [SEE FIGURE 8(C-1)].
  
 ** BE SURE TO SEE OTHER FIXTURES IN OTHER LOCATIONS.
 THERE ARE THREE HALLWAYS (AS NOTED ON PLANS) WHICH TYPE
 *M* FIXTURES ARE OF CONCERN.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 EGRESS STAIRS PER LS 101 7.8.1.3. THE NEW PHOTO-METRICS
 SUBMITTED DO NOT INDICATE THE 10FT CANDLE UNDER NORMAL
 LEVELS.
 *** ALL STAIRS INCLUDING AREAS WHERE PERFORMANCES ARE
 LOCATED. ** DURING TIMES OF PERFORMANCES LIGHTING
 LEVELS ARE PERMITTED TO MEET EXCEPTIONS HOWEVER ALL
 OTHER NORMAL TIMES OF OCCUPANCY MUST MEET THE *MINIMUM*
 FOR THE LIFE SAFETY CODE.
 DUE TO THE AMOUNT OF THE SCOPE OF WORK SOME BATHROOM
 AREAS WILL BE REQUIRED TO ADD BATTERY BACK UP LIGHT
 FIXTURES OF SOME KIND. FOR EXAMPLE: PLEASE SEE RESTROOM
 AND CORRIDOR IN NE CORNER TENANT SPACE.
  
 6) NOTE: PLEASE COORDINATE PANELS AND RISER:
  
 FOR EXAMPLE: PANEL *H1* SHOWS A SUB-FEED TO A
 TRANSFORMER *T1* YET THERE IS NO TRANSFORMER *T1* ON
 RISER OR PLANS.
 240.21,310.16,240.4, 450.3 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 7) NOTE: PLEASE EXPLAIN HOW THE THREE POLE BREAKERS ON
 PANELS K1 AND H1 TAKE SPACE FOR 6-POLES EACH.
 WHAT TYPE OF BREAKER DOES THIS? PLEASE SUPPLY CUT SHEET
 FOR THIS TYPE OF BREAKER OR IS THIS A MISPRINT OF SOME
 SORT? NE C110.3,90.7
  
 8) NOTE: PLEASE SHOW COMPLETE LOAD CALCULATIONS ON
 EXISTING SERVICE IN WHICH NEW LOADS ARE BEING ADDED.
 PLEASE EXPLAIN HOW THE LOAD FOR WHAT IS BEING ASSUMED
 AS TRANSFORMER TEA IS NOT THE SAME ON PANEL *H1*.
 220.87
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE AT THIS TIME. ONE SET OF ELECTRICAL PLANS ARE
 BEING RETAINED AND WILL BE PLACED WITH PREVIOUS PLANS
 RETAINED.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 17:14 Sent To  
Notes
2008-07-18 17:14:45** DENIED REVIEW **
  
 1) NOTE: **** PLEASE READ ****
 IT IS IMPORTANT TO UNDERSTAND THAT THE PLANS SUBMITTED
 ARE NOT COMPLETE. THERE ARE SEVERAL ITEMS MISSING FROM
 MINIMUM CODE COMPLIANCE DESIGN. AS MANY OF THESE ITEMS
 ARE NOT SHOWN A COMPLETE REVIEW FOR MINIMUM CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE
 TO SEE ALL COMMENTS BELOW AND UNDERSTAND THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 ** CALLED KAMM CONSULTING AND SPOKE TO ART KAMM WITH
 RESPECT TO PLANS. MR. KAMM MADE COMMENT THAT INCORRECT
 PLANS WERE SIGNED, SEALED AND SUBMITTED.
 ONE COPY OF ELECTRICAL PLANS WERE RETAINED.
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WITH ALL
 CIRCUITING FOR ALL LIGHTING.
 NEC 408, 240.4, 310.16 ETC
 FBC 106.1.1, 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTS AND EXIT LIGHTS.
  
 4) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLIANCE WITH
 FBC 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. MOST
 REQUIRED LIGHTING CONTROLS ARE MISSING FROM PLANS.
  
 5) NOTE: PLEASE COMPLETE PLANS FOR IDENTIFICATION OF
 ALL LIGHTING FIXTURES. PLEASE SUBMIT COMPLETE LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PARTIAL LIGHTING DENSITIES SHOWN ON
 E-2.1 ARE NOT CODE COMPLIANT IN ANY WAY.
  
 6) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY
 SIDE OF TRANSFORMER TEA TO PANEL K1 SHALL MEET OR
 EXCEED THE OVER CURRENT PROTECTION IN WHICH THE TAPPED
 CONDUCTORS TERMINATES. TYPICALLY IT IS PERMITTED TO GO
 TO THE NEXT SIZE UP HOWEVER NOT ON THE SECONDARY SIDE
 OF A TRANSFORMER.
 240.4,310.16,240.21,240.6 ETC
 ** THIS IS A LIFE SAFETY AND FIRE HAZARD AND SHALL BE
 CORRECTED EVEN IF EXISTING.
  
 7) NOTE: PLEASE SEE RISER SHOWS PANELS E AND F YET THE
 PANEL SCHEDULES WERE NOT SUBMITTED ON SHOWN ON PLANS.
 408.4, 215.5, 240.21, 408.36
 FBC 106.3.5.1.2, 106.1.1
  
 8) NOTE: PLEASE SUBMIT PHOTO-METRICS AND LIGHTING
 LEVELS FOR ALL EGRESS PATHS. PLEASE SEE NFPA-101 2006
 7.8.1.3, 7.9.2.1
 AS FIXTURES ARE NOT COMPLETEAND UNCLEAR IT IS NOT
 KNOWN ALL FIXTURES WHICH MAY PROVIDE THE BACK UP
 ILLUMINATION.
  
 9) NOTE: PLEASE SEE 450.13 AS THE TRANSFORMER ARE NOTED
 AS BEING ABOVE THE CEILING WHICH IS NOT PERMITTED.
  
 10) NOTE: PLEASE SEE A NOTE ON PLANS MENTIONS THE
 REQUIRED GFI PROTECTION HOWEVER PLEASE INDICATE THE
 PROTECTION BY THE DEVICE OR THE CIRCUIT. PLEASE SEE
 THAT ALL RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT
 THE FEED COUNTER SPACES SHALL BE PROTECTED FOR 15/20AMP
 AND 125V.
 PLEASE SEE RECEPTACLES WITHIN 6FT OF WET BAR SINKS
 SHALL ALSO CONTAIN GFI PROTECTION.
 210.8B2
  
 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE TO ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED. THE USE OF *LIGHTING
 OR RECEPTACLES* IS NOT ACCEPTABLE. 408.4
 FBC 106.1.1,106.1.2,106.5
  
 12) NOTE: PLEASE BE SURE THE LATEST ADOPTED CODES FOR
 ELECTRICAL, LIFE SAFETY DESIGN IS STATED ON PLANS. 2005
 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 13) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR BASE FIRE
 ALARM SYSTEM.
 PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3 FOR
 MINIMUM DEVICES FOR ADA COMPLIANCE.
  
 14) NOTE: PLEASE SEE LIFE SAFETY CODE CHAPTER 7
 NFPA-101.7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT
 IS NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS: NO EXIT 7
 7.8.10.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM (IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-07 Cont ID  
Sent By mawillia Date 2009-01-07 Time 18:52 Rev Time 0.00
Received By mawillia Date 2009-01-07 Time 17:50 Sent To  
Notes
2009-01-07 18:42:55*****REVISION #4, DATED 12/01/2008, APPROVED*****
  
  
 REVIEWED REVISED SHEETS A120.2, A120.4, A130.2, A130.4,
 A180.1, A180.4, AND A500.1; SHEETS A120.2, A120.4, AND
 A500.1 WERE FIRE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By mwennerg Date 2008-11-04 Time 12:09 Rev Time 0.00
Received By mwennerg Date 2008-11-04 Time 12:09 Sent To  
Notes
2008-11-04 12:09:33REVISION DATED 10/17/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-09-16 Cont ID  
Sent By mwennerg Date 2008-09-16 Time 10:04 Rev Time 0.00
Received By mwennerg Date 2008-09-16 Time 10:04 Sent To  
Notes
2008-09-16 10:07:49***PROVISO***
  
 COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED PER
 PREVIOUS MEETING.
  
 1) THIS WRITER PROVIDED THE INCORRECT EDITION FOR NFPA
 13. THE CORRECT EDITION SHOULD READ 2002.
  
 2) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING
 THRESHHOLD BUILDING REQUIREMENTS.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By mwennerg Date 2008-07-24 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2008-07-24 Time 13:56 Sent To  
Notes
2008-07-24 14:11:15***DENIED***
  
 1) PLEASE ADD THE FOLLOWING CODE TO APPLICABLE CODE
 SECTION:
 A) FIRE SPRINKLER WORK SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 13, 2003.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL. ADDITIONALLY, PROVIDE A FIRE
 SPRINKLER LAYOUT WITH MASTER PERMIT SUBMITTAL.
  
 3) EXISTING BUILDING FIRE PROTECTION SYSTEMS SHALL
 REMAIN IN SERVICE. CONTACT WPB BUREAU OF FIRE
 PREVENTION AT (561) 804-4724 SHOULD ANY INTERUPTION OF
 REQUIRED SYSTEMS OCCUR.
  
 4) JOB SITE TO BE CLEANED OF EXCESS DEBRIS DAILY OR
 MORE FREQUENTLY TO MAINTAIN SAFE OPERATION.
  
 5) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING THAT IS SPECIFIC TO THIS PROJECT.
  
 6) PROVIDE PRESCRIPTIVE STENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 7) KNOX BOX IS REQUIRED FOR AFTER NORMAL BUSINESS HOURS
 EMERGENCY SERVICE ACCESS. CONTACT WPB BUREAU OF FIRE
 PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 8) EGRESS DOORS SERVING AN AREA OR ROOM THAT SERVES
 GREATER THAN (100) OCCUPANTS SHALL BE PROVIDED WITH
 PANIC OR FIRE EXIT HARDWARE.CLEARLY IDENTIFY APPLICABLE
 DOORS. RATED DOORS SHALL BE PROVIDED WITH UL LISTED
 CLOSERS FOR POSITIVE LATCH EFFECT. PLEASE ADD TO DOOR
 SCHEDULE.
  
 9) OCCUPANT LOAD SIGNS TO BE POSTED PRIOR TO FINAL
 INSPECTION.
  
 10) RAMPS TO COMPLY WITH NFPA 101, SEC. 7.2.5.
  
 11) DOOR SWINGS IN AREAS OR ROOMS SERVING (50) OR MORE
 OCCUPANTS SHALL SWING IN THE DIRECTION OF TRAVEL.
  
 12) HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM. NEW HOOD SUPPRESSION
 SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF UL 300
 FOR WET CHEMICAL AGENT. SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR NEW OR ALTERED HOOD/SUPPRESSION
 SYSTEMS.
  
 13) SOFFITS SHALL NOT INTERFERE WITH OR OBSTRUCT FIRE
 SPRINKLER COVERAGE.
  
 14) SOME SHEETS ILLUSTRATE AN EXIT SIGN LEADING
 OCCUPANTS FROM THE MAIN EAST EXIT HALLWAY INTO A
 SEATING AREA WITH OBSTRUCTION OF TABLES AND CHAIRS.
 PLEASE CORRECT AND CORRELATE ALL SHEETS.
  
 15) ELECTRICAL POWER PLAN (SHEET E-3.1) DOES NOT
 INDICATE ANY LAY OUT OF FIRE ALARM EQUIPMENT. IN
 ADDITION, SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED
 FOR FIRE ALARM REMODEL OR INSTALLATION.
  
 16) HOW WILL THIS PROJECT IMPACT EXISTING MEANS OF
 EGRESS, MORE SPECIFICALLY EXIT DISCHARGE?
  
 17) THE DOOR SWING FROM THE VESTIBULE IS CONFLICTING ON
 DIFFERENT SHEETS. PLEASE CORRELATE INFORMATION.
  
 18) CONTACT BUREAU OF FIRE PREVENTION PRIOR TO CUTTING
 OR WELDING OPERATIONS. WORK SHALL COMPLY WITH NFPA
 51B.
  
 19) DUCT SMOKE DETECTORS IN ADDITION TO FAN SHUT DOWN,
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 20) PLEASE EXPLAIN HOW SMOKE WOULD BE REMOVED OR
 RELOCATED SHOULD A FIRE EMERGENCY OCCUR.
  
 21) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 17:12 Rev Time 0.00
Received By kstevens Date 2009-01-05 Time 18:56 Sent To  
Notes
2009-01-06 17:33:01REVISION DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P6.1 THERE ARE CHANGES TO THE GAS RISER DIAGRAM
 THAT ARE NOT CLOUDED NOR INDICATED WITH A REVISION
 NUMBER. EACH REVISION SHALL BE INDICATED WITH A CLOUD
 AND A REVISION NUMBER. (SEE P19G 35,000 BTU DELETED AT
 THE END OF LINE 2, P23G 225,000 BTU STUB OUT PIPE SIZE
 CHANGED TO 1-1/2" LINE 2. -- SEE P17G 70,000 BTU ADDED
 TO LINE 1, P25G 140,000 BTU DELETED FROM LINE 1). ALSO
 CLARIFY THE P57G ON LINE 1 IS INDICATED AS 224,000 BTU,
 BUT THE P57G ON LINE 2 IS INDICATED AS 168,000 BTU. IS
 THIS A DIFFERENT GAS APPLIANCE? IF SO PLEASE SUBMIT THE
 MANUF. SPECIFICATION FOR THE NEW P57G SHOWING LISTING
 AND BTU LOAD.
  
 2. SHT P6.1 SHOWS A REVISION 4 IN THE REVISION INDEX
 THAT IS NOT SHOWN ON THE RISER DIAGRAMS. PLEASE CLARIFY
 AS THIS REVISION HAS NOT BEEN APPROVED OR REVIEWED.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-09-23 Cont ID  
Sent By kstevens Date 2008-09-23 Time 09:27 Rev Time 0.00
Received By kstevens Date 2008-09-23 Time 09:27 Sent To  
Notes
2008-09-23 09:38:14 
  
  
 PASSED/PROVISO
  
 1. SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS APPLIANCES
 AT THE TIME OF PERMIT APPLICATION SHOWING LISTING & BTU
 LOAD. BTU LOAD SHALL REFLECT THE BTU LOAD SHOWN ON THE
 GAS RISER ON PLANS.
  
 2. PIPE SIZES FOR APPLIANCES RED LINED APPLIANCES P19G,
 P23G & P57G SHALL BE 1-1/2" NOT 1-1/4" AS INDICATED.
 PIPE SIZE FOR THE GAS MAIN LINE SHALL BE MINIMUM 2-1/2"
 UPSTREAM OF APPLIANCE P24G. TABLE 402.4(2) FBC-FUEL GAS
 -- REVISION REQUIRED.
  
 3. WATER FILTER SHALL MEET NSF-42 REQUIREMENTS. MANUF.
 SPECIFICATIONS REQUIRED AT THE TIME OF FINAL PLUMBING
 INSPECTION.
  
  
  
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-09-22 Cont ID  
Sent By kstevens Date 2008-08-27 Time 10:07 Rev Time 0.00
Received By kstevens Date 2008-08-27 Time 10:07 Sent To  
Notes
2008-09-22 10:09:10DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 REQUIREMENTS FOR PERMIT FOLLOW:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE
 IWH'S.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 I. N/A
 J. N/A
 K. OK
  
 L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT
 FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME
 SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402.
 ****RESPONSE NOTED, BUT PIPE SIZE AND VALVE TO EACH
 APPLIANCE SHALL BE FULL SIZE. SEE TABLE 402.4(6).
  
 M. OK
  
 ***********NEW COMMENT***********
  
 1B. INDICATE IF THE GAS PIPING WILL BE WELDED OR SCREW
 PIPE ON THE PLANS. IF WELDED THEN THE WELDING PROCEDURE
 AND WELDING CERTIFICATIONS & PICTURE I.D. OF THE PERSON
 WELDING THE PIPE ARE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By kstevens Date 2008-07-09 Time 10:05 Rev Time 0.00
Received By kstevens Date 2008-07-09 Time 10:05 Sent To  
Notes
2008-09-22 10:06:48DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 REQUIREMENTS FOR PERMIT FOLLOW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT 9(A) IS ADDRESSED.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 K. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- (NO UNIONS
 INDICATED)
  
 L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT
 FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME
 SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402.
  
 M. SHUT OFF VALVES ARE REQUIRED FOR LINES 1 & 2 AS THEY
 ENTER THE TENANT SPACE. SECTION 409.3.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 11:16 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 11:16 Sent To E
Notes
2009-04-06 11:16:42TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-03-18 Cont ID  
Sent By adarroug Date 2009-03-18 Time 16:00 Rev Time 0.00
Received By adarroug Date 2009-03-18 Time 16:00 Sent To E
Notes
2009-03-18 16:05:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 15:52 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 15:52 Sent To B
Notes
2009-01-06 15:53:12TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 15:45 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 15:45 Sent To B
Notes
2009-01-06 15:45:37TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 08:52 Sent To  
Notes
2008-12-26 08:53:06TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 08:40 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 08:40 Sent To E
Notes
2008-12-26 08:40:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 08:37 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 08:37 Sent To M
Notes
2008-12-26 08:37:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 08:31 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 08:31 Sent To P
Notes
2008-12-26 08:31:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-12-16 Time 16:16 Sent To B
Notes
2008-12-16 16:17:20TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 09:02 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 09:02 Sent To B
Notes
2008-11-05 09:02:56TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2008-12-01 Time   Rev Time 0.00
Received By rmcdouga Date 2008-10-30 Time 11:32 Sent To  
Notes
2008-10-30 11:34:11REVISION FOR BAR JOIST REINFORCING DETAIL TO JIM
 WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 09:43 Sent To  
Notes
2008-10-24 09:46:04TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 09:02 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 09:02 Sent To B
Notes
2008-10-24 09:03:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-03 Cont ID  
Sent By shill Date 2008-10-03 Time 14:22 Rev Time 0.00
Received By shill Date 2008-10-03 Time 14:22 Sent To B
Notes
2008-10-03 14:23:02TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 13:27 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 13:27 Sent To  
Notes
2008-09-22 13:34:20TO "COMM" BD#63--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 14:42 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 14:42 Sent To  
Notes
2008-08-25 14:43:05TO "COMM" BD #39.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-24 Cont ID  
Sent By mwennerg Date 2008-07-24 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 14:18 Sent To  
Notes
2008-07-03 14:41:26TO "COMM" BD#24--EXPEDITED--
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-01-07 Cont ID  
Sent By rregueir Date 2009-01-07 Time 19:46 Rev Time 0.00
Received By rregueir Date 2009-01-07 Time 19:44 Sent To PC
Notes
2009-01-07 19:46:00M0.1, M2.1 AND M7.1 REV6, M6.1 REV5,

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-11-24 Cont ID  
Sent By rregueir Date 2008-11-24 Time 19:34 Rev Time 0.00
Received By rregueir Date 2008-11-24 Time 19:06 Sent To PC
Notes
2008-11-24 19:34:49REVISED M0.1, M2.1, M6.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-09-09 Cont ID  
Sent By rregueir Date 2008-09-09 Time 08:39 Rev Time 0.00
Received By rregueir Date 2008-09-09 Time 08:23 Sent To  
Notes
2008-09-09 08:39:40KITCHEN EQUIPMENT PLANS SHOW NEW WALK-IN COOLERS AND/OR
 FREEZERS. SEPARATE PERMITS ARE REQUIRED FOR THE
 INSTALLATION OF THESE ITEMS. SUBMIT SEPARATE PLANS AND
 SPECIFICATIONS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-15 Cont ID  
Sent By rregueir Date 2008-07-15 Time 16:54 Rev Time 0.00
Received By rregueir Date 2008-07-15 Time 13:23 Sent To  
Notes
2008-07-15 15:42:32KITCHEN EQUIPMENT PLANS SHOW NEW WALK-IN COOLERS AND/OR
 FREEZERS. SEPARATE PERMITS ARE REQUIRED FOR THE
 INSTALLATION OF THESE ITEMS. SUBMIT SEPARATE PLANS AND
 SPECIFICATIONS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-06-25 Cont ID  
Sent By dwise Date 2009-06-25 Time 20:01 Rev Time 0.00
Received By dwise Date 2009-06-25 Time 20:00 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 17:07 Rev Time 0.00
Received By kstevens Date 2009-01-06 Time 17:07 Sent To  
Notes
2009-01-06 17:12:05REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P0.1 SHOWS MANY CHANGES TO THE EQUIPMENT
 SCHEDULE THAT ARE NOT INDICATED WITH A REVISION NUMBER
 , NOR CLOUDED AS REQUIRED. ALL REVISIONS SHALL BE
 INDICATED WITH A CLOUD AND A REVISION NUMBER. SECTION
 106.1.3. -- THE REVISION INDEX SHOWS A REVISION 4 THAT
 IS NOT INDICATED ON THE FLOOR PLAN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 17:06 Rev Time 0.00
Received By kstevens Date 2009-01-05 Time 18:55 Sent To  
Notes
2009-01-06 17:07:27REVISIONS OK -- SHTS P2.1, P3.1 & P5.1 -- SHTS P2.1 &
 P5.1 SHOW A REVISION 4 IN THE REVISION INDEX THAT WAS
 NOT FOUND OR APPROVED.

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-12-10 Cont ID  
Sent By kstevens Date 2008-12-10 Time 16:12 Rev Time 0.00
Received By kstevens Date 2008-12-10 Time 16:12 Sent To  
Notes
2008-12-10 16:24:30REVISIONS DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P0.1, P2.1 & P5.1 THE PRINTED NAME OF THE
 ENGINEER SIGNING AND SEALING THE PLANS IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. (MIRCLA PELLA). FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT P0.1 EQUIPMENT SCHEDULE. CHANGES TO THE GAS
 EQUIPMENT IN INDICATED. REVISIONS ARE REQUIRED FOR THE
 FLOOR PLAN AND THE GAS ISOMETRIC RISER DIAGRAM TO
 REFLECT THE CHANGES. SECTION 106.3.5.2.
  
 3. SHT P0.1 EQUIPMENT SCHEDULE. ITEMS P85, P88C, P88H &
 PB4.2 ARE NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 4. ALL CHANGES TO THE WATER PIPING SHALL BE INDICATED
 WITH REVISIONS TO THE FLOOR PLAN AND THE WATER
 ISOMETRIC RISER DIAGRAM. SECTION 106.3.5.1.3.
  
 5. SHT P5.1 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 CHANGES ON THE FLOOR PLAN. UPSTREAM OF THE CONNECTION
 TO THE RISER THERE IS A P-2 AND TWO FLOOR DRAINS SHOWN
 ON THE FLOOR PLAN BUT NOT ON THE RISER DIAGRAM. PLEASE
 CORRLEATE. SECTION 106.1.1.
  
 6. PLEASE TURN OFF ALL PREVIOUS REVISION CLOUDS AND
 REVISION NUMBERS FOR REVISIONS 1 & 2 AS THEY DELAY THE
 REVIEW PROCESS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-09-23 Cont ID  
Sent By kstevens Date 2008-09-23 Time 09:25 Rev Time 0.00
Received By kstevens Date 2008-09-22 Time 15:58 Sent To  
Notes
2008-09-23 09:26:54PASSED/PROVISO -- WATER FILTER SHALL MEET THE
 REQUIREMENTS OF NSF-42. -- MANUF. SPECIFICATIONS
 REQUIRED AT THE TIME OF FINAL PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-27 Cont ID  
Sent By kstevens Date 2008-08-27 Time 10:30 Rev Time 0.00
Received By kstevens Date 2008-08-26 Time 12:58 Sent To  
Notes
2008-08-27 10:46:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A120.1 CODE ANALYSIS INDICATES GROSS AREA @
 15,832SF & NET AREA @ 15,304SF, BUT THE ADDITION OF THE
 SHOWROOM, STAGE, BUSINESS, KITCHEN, BAR & WAITING AREAS
 ONLY ADD UP TO 11, 864SF. PLEASE CLARIFY. SECTIONS 1004
 & 403 & TABLES 1004.1.2 & 403.1. ALSO THE COVERED PATIO
 AREA IS NOT INCLUDED IN THE ANALYSIS. PLEASE INDICATE
 THE OCCUPANT LOAD AND IF THERE IS SEATING IN THIS AREA.
 SECTIONS 1004.8 & 403.1.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2. SHT A120.1 PER TABLES 1004.1.2 & 403.1 & SECTION
 403.1.1.2, 10 WATER CLOSETS ARE REQUIRED FOR THE MEN.
 THIS MAY CHANGE WITH THE OCCUPANCY OF THE COVERED PATIO
 ESTABLISHED AND ADDED TO TOTAL.
 ****RESPONSE NOTED, BUT DUE TO NEW INFORMATION
 REQUIRED, IT IS INDICATED THAT THERE ARE "ALOT OF SEATS
 IN THE SPACE, BUT A LOT OF PEOPLE WILL TAKE JUST A
 DRINK (THIS IS A COMEDY CLUB)" (SEE ATTACHED SHEETS)
  
 3. OK
  
 4. SHT P0.1 PLUMBING SCHEDULE: ITEMS P21, P36.2, P68,
 PB4.1 & PB4.2C SHOWN ON THE SCHEDULE WERE NOT FOUND ON
 THE FLOOR PLAN. -- ITEM P45 INDICATES QTY 1 ON THE
 SCHEDULE, BUT 2 WERE FOUND ON THE FLOOR PLAN. -- ITEM
 PB1 INDICATES QTY 2 ON THE SCHEDULE, BUT 3 WERE FOUND
 ON THE FLOOR PLAN. -- ITEM PB4C INDICATES QTY 2 ON THE
 SCHEDULE, BUT ONLY 1 WAS FOUND ON THE FLOOR PLAN. --
 ITEM PB28 INDICATES QTY 5 ON THE SCHEDULE, BUT ONLY 4
 WERE FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT ITEMS P21 & P68 ARE STILL NOT
 FOUND ON THE FLOOR PLAN.
  
 5. OK
 6. OK
 7. OK
  
 8. THE WATER FILTER INDICATED ON ITEM PB4.2C SHT P0.1
 SHALL MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
 SECTIONS 106.1.2 & 611.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 9. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 REQUIREMENTS FOR PERMIT FOLLOW:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE
 IWH'S.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 I. N/A
 J. N/A
 K. OK
  
 L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT
 FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME
 SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402.
 ****RESPONSE NOTED, BUT PIPE SIZE AND VALVE TO EACH
 APPLIANCE SHALL BE FULL SIZE. SEE TABLE 402.4(6).
  
 M. OK
  
 ***********NEW COMMENT***********
  
 1B. INDICATE IF THE GAS PIPING WILL BE WELDED OR SCREW
 PIPE ON THE PLANS. IF WELDED THEN THE WELDING PROCEDURE
 AND WELDING CERTIFICATIONS & PICTURE I.D. OF THE PERSON
 WELDING THE PIPE ARE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By kstevens Date 2008-07-09 Time 11:15 Rev Time 0.00
Received By kstevens Date 2008-07-07 Time 15:59 Sent To  
Notes
2008-07-09 11:57:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT A120.1 CODE ANALYSIS INDICATES GROSS AREA @
 15,832SF & NET AREA @ 15,304SF, BUT THE ADDITION OF THE
 SHOWROOM, STAGE, BUSINESS, KITCHEN, BAR & WAITING AREAS
 ONLY ADD UP TO 11, 864SF. PLEASE CLARIFY. SECTIONS 1004
 & 403 & TABLES 1004.1.2 & 403.1. ALSO THE COVERED PATIO
 AREA IS NOT INCLUDED IN THE ANALYSIS. PLEASE INDICATE
 THE OCCUPANT LOAD AND IF THERE IS SEATING IN THIS AREA.
 SECTIONS 1004.8 & 403.1.3.
  
 2. SHT A120.1 PER TABLES 1004.1.2 & 403.1 & SECTION
 403.1.1.2, 10 WATER CLOSETS ARE REQUIRED FOR THE MEN.
 THIS MAY CHANGE WITH THE OCCUPANCY OF THE COVERED PATIO
 ESTABLISHED AND ADDED TO TOTAL.
  
 3. BECAUSE OF THE TOTAL AMOUNT OF SEATING THE UTILITY
 DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE SHALL BE CONTACTED TO DETERMINE THE
 REQUIREMENTS FOR THE GREASE INTERCEPTOR. PLEASE CONTACT
 RODNEY (561) 644-1821, FAX (561) 822-2287 OR E-MAIL HIM
 AT [email protected]. ARTICLE III SECTION 90-124(7).
  
 4. SHT P0.1 PLUMBING SCHEDULE: ITEMS P21, P36.2, P68,
 PB4.1 & PB4.2C SHOWN ON THE SCHEDULE WERE NOT FOUND ON
 THE FLOOR PLAN. -- ITEM P45 INDICATES QTY 1 ON THE
 SCHEDULE, BUT 2 WERE FOUND ON THE FLOOR PLAN. -- ITEM
 PB1 INDICATES QTY 2 ON THE SCHEDULE, BUT 3 WERE FOUND
 ON THE FLOOR PLAN. -- ITEM PB4C INDICATES QTY 2 ON THE
 SCHEDULE, BUT ONLY 1 WAS FOUND ON THE FLOOR PLAN. --
 ITEM PB28 INDICATES QTY 5 ON THE SCHEDULE, BUT ONLY 4
 WERE FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 5. SHT P2.1 ITEM P48 SHALL DRAIN INTO THE SANITARY
 SYSTEM AND NOT THE GREASE SYSTEM. ARTICLE III SECTION
 90-124(7)(B). PLEASE SHOW PROPER CONNECTION.
  
 6. SHT P2.1 ITEM P61 INDICATED ON THE FLOOR PLAN IS NOT
 SHOWN ON THE SCHEDULE SHT P0.1. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 7. SHT P5.1 FLOOR SINK TO ITEM 48 SHALL DRAIN INTO THE
 SANITARY SYSTEM AND NOT THE GREASE SYSTEM. ARTICLE III
 SECTION 90-124(7)(B). PLEASE SHOW PROPER CONNECTION.
  
 8. THE WATER FILTER INDICATED ON ITEM PB4.2C SHT P0.1
 SHALL MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
 SECTIONS 106.1.2 & 611.1.
  
 9. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 REQUIREMENTS FOR PERMIT FOLLOW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT 9(A) IS ADDRESSED.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 K. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- (NO UNIONS
 INDICATED)
  
 L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT
 FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME
 SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402.
  
 M. SHUT OFF VALVES ARE REQUIRED FOR LINES 1 & 2 AS THEY
 ENTER THE TENANT SPACE. SECTION 409.3.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-30 Cont ID  
Sent By eschneid Date 2008-10-30 Time 14:51 Rev Time 0.00
Received By eschneid Date 2008-10-30 Time 14:51 Sent To  
Notes
2008-10-30 14:51:47RESTAMP

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-24 Cont ID  
Sent By eschneid Date 2008-09-24 Time 10:45 Rev Time 0.00
Received By eschneid Date 2008-09-24 Time 10:45 Sent To  
Notes
2008-09-24 10:45:22RESTAMP

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-11 Cont ID  
Sent By eschneid Date 2008-07-11 Time 12:06 Rev Time 0.00
Received By eschneid Date 2008-07-11 Time 12:06 Sent To  
Notes
***NONE***