Plan Review Details - Permit 08070109
Plan Review Stops For Permit 08070109
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-26 Cont ID  
Sent By mjacobs Date 2008-08-26 Time 08:40 Rev Time 0.00
Received By mjacobs Date 2008-08-26 Time 08:09 Sent To PC
Notes
2008-08-26 08:09:33NEW SHEETS A-1 AND A-2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-23 Cont ID  
Sent By mjacobs Date 2008-07-23 Time 07:47 Rev Time 0.00
Received By mjacobs Date 2008-07-22 Time 12:30 Sent To  
Notes
2008-07-23 07:45:50PROVISOR: THE BREAK ROOM SINK SHALL MEET THESE
 REQUIREMENTS.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHESCOMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHESUNDERNEATH THE SINK.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-25 Cont ID  
Sent By btrobaug Date 2008-08-25 Time 08:40 Rev Time 0.00
Received By btrobaug Date 2008-08-25 Time 08:29 Sent To  
Notes
2008-08-25 08:40:15 

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-09 Time 15:35 Rev Time 0.00
Received By btrobaug Date 2008-07-09 Time 13:58 Sent To  
Notes
2008-07-09 15:35:18 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 09:35 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 12:39 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 12:39 Sent To B
Notes
2008-11-12 12:39:35TO "MJACOBS" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 14:52 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 14:52 Sent To  
Notes
2008-08-20 17:06:12TO "BOB"#13
2008-08-15 14:52:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By lmartine Date 2008-07-24 Time 09:30 Rev Time 0.00
Received By lmartine Date 2008-07-03 Time 11:27 Sent To  
Notes
2008-07-09 10:11:57TO "BOB"#6
2008-07-03 11:31:27WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-10 Cont ID  
Sent By tgordon Date 2008-07-10 Time 07:57 Rev Time 0.30
Received By tgordon Date 2008-07-10 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By mperson Date 2008-08-21 Time 08:21 Rev Time 0.00
Received By mperson Date 2008-08-21 Time 08:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By mperson Date 2008-07-23 Time 13:18 Rev Time 0.00
Received By mperson Date 2008-07-23 Time 13:18 Sent To  
Notes
2008-07-23 13:53:27PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PER FBC-2004 PLUMBING TABLE 403.1, MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES, FOR A GROUP B BUSSINESS
 OCCUPANCY A DRINKING FOUNTAIN IS REQUIRED AND IT SHALL
 BE ACCESSIBLE PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE THE FOLLOWING SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE. (CLEARLY INDICATE THE CLEAR FLOOR SPACE ON SHEET
 A-1 DETAIL 2 FLOOR PLAN)
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. PROVIDE A SANITARY ISOMETRIC RISER DIAGRAM FOR THE
 PROPOSED SINK IN BREAK ROOM #102 AND FOR THE REQUIRED
 DRINKING FOUNTAIN. PER FBC-2004 CHAPTER 1 (W.P.B. AS
 AMENDED), SECTION 106.3.5.1.3 PLUMBING(4)(6)(13).
  
 3. PER FBC-2004 CHAPTER 1 (W.P.B. AS AMENDED), SECTION
 106.3.5.1.3, PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC
 POTABLE WATER RISER DIAGRAM IS REQUIRED FOR THE
 PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER **607.3,
 AND LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS EXISTING
 OR PROPOSED.
  
 4. SHEET A-1 DETAIL 2, FLOOR PLAN INDICATES A SINK IN
 BREAKROOM #102: PLEASE PROVIDE THE FOLLOWING
 INFORMATION PER FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS FOR THE SINK.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
  
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. (CLEARLY INDICATE THE CLEAR FLOOR SPACE ON SHEET
 A-1 DETAIL 2 FLOOR PLAN)
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
 NOTE: CLEARLY INDICATE THE WHEEL CHAIR TURNING SPACE
 IN SHEET A-1 DETAIL 2 FLOOR PLAN.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-07-24 Cont ID  
Sent By jroach Date 2008-07-24 Time 23:28 Rev Time 0.00
Received By jroach Date 2008-07-24 Time 23:28 Sent To  
Notes
***NONE***