Plan Review Details - Permit 08070087
Plan Review Stops For Permit 08070087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By mjacobs Date 2008-08-21 Time 08:26 Rev Time 0.00
Received By mjacobs Date 2008-08-20 Time 17:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By mjacobs Date 2008-07-25 Time 07:28 Rev Time 0.00
Received By mjacobs Date 2008-07-24 Time 09:58 Sent To  
Notes
2008-07-25 07:28:15BUILDING PLAN REVIEW
 PERMIT: 08070087
 ADD: 400 N. FLAGLER DR. #1504
 CONT: A MCGILL REMODELING LLC.
 TEL: (561)632-9354
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-24-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDING AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, ARCHITECTURAL DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*
 6)PROVIDE DETAIL ELEVATION DRAWINGS AND FRAMING
 DETAILS FOR THE NEW WALLS AND SOFFITS INDICATING ALL
 MATERIALS, FASTENER AND FLOOR ATTACHMENTS OF THE STUD
 SPACING.
 7)THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER
 CHAPTER 6 AND THE USE AND OCCUPANCY PER CHAPTER 3.
 8)FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS IIC RATING OR NOT LESS THAN 50
 (45 IF FIELD TESTED) WHEN IN ACCORDANCE WITH ASTM E
 492. PROVIDE INFORMATION ON THE SOUND PROOFING OF THE
 FLOOR.
 9)FBC 106.3.5.1.1(5)* FS553.79 (2) NOW THE FIRE
 SPRINKLER SYSTEM WILL BE ALTERED, FIRE SPRINKLER PLANS
 ARE REQUIRED TO SHOW THE NEW LAYOUT OF THE SPRINKLER
 HEADS. THIS INFORMATION CAN BE SHOWN ON THE CEILING
 PLANS.
 10)TABLE 803.5 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-05 Cont ID  
Sent By btrobaug Date 2009-02-05 Time 12:12 Rev Time 0.00
Received By btrobaug Date 2009-02-05 Time 10:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 12:21 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 12:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-10 Cont ID  
Sent By btrobaug Date 2008-07-10 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2008-07-09 Time 16:02 Sent To  
Notes
2008-07-10 10:36:43 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET-3 UNLESS OTHERWISE NOTED.
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), CIRCUIT #14 DOES NOT COMPLY.
  
 2} CIRCUIT #15 APPEARS AT THE KITCHEN COUNTER AS WELL
 AS THE WASHER IN VIOLATION OF 210.52(B)(1) "RECEPTACLE
 OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM,
 DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE
 TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS
 REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT.".
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.THERE IS NO
 RECEPTACLES SHOWN INDICATING COUTERTOP REQUIREMENTS.
  
 4} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE
 LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND
 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME
 ON THE PLAN.
  
 5} NOTE #20 INDICATES CUTTING THE STRUCTURE. PROVIDE
 ENGINEERING INDICATING THE STRUCTURAL INTEGRITY OF THE
 CEILING OR FLOOR ABOVE WILL NOT BE COMPROMISED, SIGNED
 AND SEALED.
  
 6} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 7} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE, PUT A ON THE PLAN FOR CLARITY IN THE FIELD.
  
 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-18 Cont ID  
Sent By mawillia Date 2008-08-18 Time 12:43 Rev Time 0.00
Received By mawillia Date 2008-08-18 Time 12:33 Sent To  
Notes
2008-08-18 12:43:42*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1 AND A-3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 10:00 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 10:00 Sent To  
Notes
2008-07-22 10:06:12***DENIED***
  
 1) SEE ELECTRICAL COMMENT #6 AND MAKE CORRECTIONS IF
 APPLICABLE. SMOKE DETECTORS ARE TIED TO A FIRE ALARM
 SYSTEM AND DETECT PARTICLES OF COMBUSTION WHEREAS SMOKE
 ALARMS NOTIFY OCCUPANTS BY WAY OF AN AUDIBLE ALARM.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-05 Cont ID  
Sent By adarroug Date 2009-02-05 Time 08:37 Rev Time 0.00
Received By adarroug Date 2009-02-05 Time 08:37 Sent To E
Notes
2009-02-05 08:37:54TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 10:27 Sent To  
Notes
2008-08-12 13:33:11TO "BOB"#3
2008-08-06 10:27:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 15:55 Rev Time 0.00
Received By tgordon Date 2008-07-02 Time 15:52 Sent To  
Notes
2008-07-02 15:55:11TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-25 Cont ID  
Sent By tgordon Date 2008-07-25 Time 15:54 Rev Time 0.20
Received By tgordon Date 2008-07-25 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-13 Cont ID  
Sent By mperson Date 2008-08-13 Time 14:25 Rev Time 0.00
Received By mperson Date 2008-08-13 Time 14:25 Sent To  
Notes
2008-08-13 14:26:58NOTE: FIXTURE CHANGE OUT ONLY.
  
 ***************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By mperson Date 2008-07-25 Time 13:54 Rev Time 0.00
Received By mperson Date 2008-07-25 Time 13:54 Sent To  
Notes
2008-07-25 14:34:29PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS) PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR
 PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT
 APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-07 Cont ID  
Sent By choops Date 2008-07-07 Time 13:30 Rev Time 0.00
Received By choops Date 2008-07-07 Time 13:30 Sent To  
Notes
2008-07-07 13:30:18*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.