| 2008-07-01 16:21:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.THE PRODUCT APPROVAL SUBMITTED FOR THE BUILDING |
| | PERMIT (AND REVIEWED BY DESIGNER OF RECORD) WAS |
| | NOA05-0919.06 WHICH HAS A DP OF -76.8 FIELD, -84.3 |
| | PERIMETER/CORNER.THE DESIGN PRESSURE FOR THE JOB, |
| | "CLADDING -83.1 ALL ZONES" REQUIRES THAT ZONE 2&3 |
| | FASTENING BE USED ON THE ENTIRE JOB.THE PRODUCT |
| | APPROVAL SUBMITTED HAS A DESIGN PRESSURE LIMITATION OF |
| | -59.4 AND -97.5. |
| | |
| | TO USE THE NEW PRODUCT, ADVANTAGE-LOK II RATHER THAN |
| | ADVANTAGE LOK STANDING SEAM 26 GAGE, PLEASE SUBMIT AS A |
| | REVISION TO THE BUILDING PERMIT.HAVE THE PRODUCT |
| | APPROVAL REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL. |
| | |
| | THE PERMIT WILL BE ISSUED WITH A PROVISO THAT ZONE 3 |
| | FASTENING BE USED ON THE ENTIRE ROOF, ZONES 1, 2, AND |
| | 3, UNLESS THE BUILDING PERMIT IS REVISED TO REDUCE THE |
| | DESIGN PRESSURE REQUIREMENT FOR THE ROOF.TO CLARIFY, |
| | PLEASE MARK ON PAGE 3 OF THE PRODUCT APPROVAL WHICH |
| | FASTENING YOU PROPOSE TO USE FOR EACH ZONE. |
| | |